Near Zero; Comparison Timing - Unipulse F377A Operation Manual

Digital indicator
Hide thumbs Also See for F377A:
Table of Contents

Advertisement

- Hysteresis operation
Indicated Value
HI Limit
LO Limit
0
HI Output
HI Status Display
LO Output
LO Status Display
Output ON
Status ON
OK Output
OK Status Display

■Near zero

By this function, it is detected that the indicated value is near zero.
 Near-zero ON: | indicated value | ≦ near zero set value
 Near-zero OFF: | indicated value |> near zero set value
Setting range: 00000 - 99999
Near-zero ON/OFF is closely related to the SI/F Print Out (stable) and Comparison timing.
For details, see the sections "SI/F Print Out" on page 40 and "Comparison timing" on page
43.
How to set
SET.
Work Setting

■Comparison timing

Set the operating condition of HI-LO limit comparison. Select the condition from the following.
ALL:
HI-LO limit comparison is performed continuously.
MD:
HI-LO limit comparison is performed when the indicated value is stable.
Set the stable parameters by the stable operation.
NZ:
HI-LO limit comparison is performed when the indicated value is not near zero.
Set the near zero parameters by the near zero operation.
MD+NZ: HI-LO limit comparison is performed when the indicated value is stable and not near zero.
HOLD:
HI-LO limit comparison is performed when the indicated value is held.
How to set
SET.
Work Setting
Output OFF
Output ON
Status OFF
Status ON
Output OFF
Status OFF
Status ON
Comp. Setting
Comp. Setting
5 SETTING OF FUNCTIONS
Hysteresis Range
Time
Output OFF
Status OFF
Output ON
Status ON
(Exsample :
 HI Output and LO Output and OK output)
Status ON
Page 2
Page 2
Chapter
5
43