Technical data

Measured variable
Output signal
Signal on alarm
Linearization
Reference operating
conditions
Maximum measured error
Resolution
Reaction time
Influence of ambient
temperature
94
10
Technical data
10.1

Additional technical data

10.1.1
Input
The measured variable is the distance between the reference point (see Fig on → ä 14) and the
product surface.
The level is calculated subject to the empty distance entered (E, see Fig. on → ä 102).
Alternatively, the level can be converted by means of linearization (32 points) to other variables
(volume, mass).
10.1.2
Output
• FOUNDATION Fieldbus
Error information can be accessed via the following interfaces:
• Local display:
– Error symbol (→ ä 34)
– Plain text display
• Current output, failsafe mode can be selected (e.g. according to NAMUR recommendation
NE 43).
• Digital interface
The Levelflex M linearization function enables conversion of the measured value to any desired
length or volume unit, mass or %. Linearization tables for volume calculation in cylindrical tanks are
preprogrammed. Any other tables with up to 32 value pairs can be input manually or semi-
automatically. The creation of a linearization table with the ToF Tool or FieldCare is particularly
convenient.
10.1.3
Performance characteristics
• Temperature = +20 °C ± 5 °C
• Pressure = 1013 mbar abs. ±20 mbar
• Relative humidity (air) = 65 % ±20%
• Metallic tank, no internals, distance to tank wall > 500 mm
• Medium: water (DK > 7), respectively oil (DK = 2)
• Probe length > 500 mm
Is in Function group "basic setup" (00) starting from → ä 58.
• Digital: 1 mm
The reaction time depends on the configuration.
Shortest time:
• 2-wire electronics: 1 s
The measurements are carried out in accordance with EN 61298-3:
• Digital output (HART, PROFIBUS PA, FOUNDATION Fieldbus):
– average T
: 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C
K
Levelflex M FMP43 with FOUNDATION Fieldbus
Endress+Hauser