Operation
50
5.5.9
Analog input block
The analog input block conditons the signal output by the Sensor block and outputs signal to the
PCL or other function blocks.
Operation
The resource block is opened by a click on the resource line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. Normally operation is resumed as
soon as MODE-BLK is set to AUTO.
Block administration parameters
Parameter
Description
MODE_BLK
See description in Resource block. The possible operating modes of the Sensor block are:
– AUTO: the block is operating as normal
– MAN: the block is operated with a manually entered primary value.
– OOS: the block is out of service.
TAG_DESC
User description of the intended application of the block.
BLOCK_ERROR
Shows error status of software and hardware components
– Out-of-Service: the block is in OOS mode
– Simulation active: shows the setting of DIP-switch SIM. Input failure/process variable
– configuration error
Output values
Parameter
Description
PV
Either the primary/secondary Sensor block value used to execute the block or a process
value associated with it. Comprises value and status.
OUT
The primary value output as a result of executing the analog input block. Comprises
value and status.
FIELD_VALUE
Raw value of field device in % of PV range with a status reflecting the Sensor condition
before signal characterisation L_Type or filtering V_TIME. Comprises value and status.
Levelflex M FMP43 with FOUNDATION Fieldbus
has BAD status.