Basic Setup With Display Vu331 - Endress+Hauser Fieldbus Levelflex M FMP43 Operating Instructions Manual

Guided level-radar
Hide thumbs Also See for Fieldbus Levelflex M FMP43:
Table of Contents

Advertisement

Commissioning
ENDRESS + HAUSER
+
E
ENDRESS + HAUSER
+
E
ENDRESS + HAUSER
+
E
!
!
58
6.4

Basic setup with display VU331

Function "measured value" (000)
This function displays the current measured value in the selected unit (see "customer unit" (042))
function). The number of digits after the decimal point can be selected in the "no.of
decimals" (095) function.
6.4.1
Function group "basic setup" (00)
Function "tank properties" (002)
This function is used to select the tank properties.
Options:
• Standard
• Aluminum tank
• Plastic tank
• Bypass / pipe
• Coax probe
• Concrete wall
Standard
The "standard" option is recommended for normal containers for rod and rope probes.
Aluminum tank
The "aluminum tank" option is designed especially for high aluminum silos that cause an increased
level of noise when empty. This option is only useful for probe lengths greater than 4 m. The
"standard" option must be selected for short probes (< 4 m)!
Note!
If "aluminum tank" is selected, the device calibrates of its own accord when first filled, depending
on the medium's properties. Slope errors can, therefore, occur when beginning the first filling
procedure.
Plastic tank
Select the "plastic tank" option when installing probes in wood or plastic containers without
metallic surfaces at the process connection (see installation in plastic containers). When using a
metallic surface at the process connection, the "standard" option is sufficient!
Note!
In principle, it is preferable to use a metallic surface at the process connection!
Levelflex M FMP43 with FOUNDATION Fieldbus
Endress+Hauser

Advertisement

Table of Contents
loading

Table of Contents