Endress+Hauser HART Levelflex M FMP45 Operating Instructions Manual

Endress+Hauser HART Levelflex M FMP45 Operating Instructions Manual

Guided level radar for interface measurement
Hide thumbs Also See for HART Levelflex M FMP45:
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP45
Guided Level Radar for Interface Measurement
HART/4 to 20 mA
6
BA365F/00/en/03.08
71060887
Valid as of software version
01.08.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser HART Levelflex M FMP45

  • Page 1 Operating Instructions Levelflex M FMP45 Guided Level Radar for Interface Measurement HART/4 to 20 mA BA365F/00/en/03.08 71060887 Valid as of software version 01.08.zz...
  • Page 2 Commissioning via Endress+Hauser operating program In the "Commissioning" section, you learn how to switch on the device and check the functions. Additional information on the operation via the Endress+Hauser operating program (FieldCare) can be found in Operating Instructions BA027S/04. Æ...
  • Page 3 An overview of all the device functions can be found on → ä 80. An extensive description of all the device functions can be found in BA366F - "Description of Device Functions" on the enclosed CD-ROM. Operating Instructions can also be found on our homepage: www.endress.com Endress+Hauser...
  • Page 4 Brief overview Levelflex M FMP45 with HART/4...20 mA Endress+Hauser...
  • Page 5: Table Of Contents

    Incoming acceptance, transport, storage ..12 Contact addresses of Endress+Hauser ... 71 Installation conditions ..... . 13 General information on interface measurement .
  • Page 6: Safety Instructions

    The device is accompanied by separate Ex documentation, which is an integral part of this documentation. The installation regulations, connection values and safety instructions listed in this document must be observed. • Ensure that all personnel are suitably qualified. • Measuring point requirements with regard to measurement and safety must be observed. Endress+Hauser...
  • Page 7: Safety Conventions And Icons

    This may be a potential equalization line or a star grounding system depending on national or company codes of practice. Temperature resistance of the connection cables t >85°C States that the connection cables must be resistant to a temperature of at least 85 °C. Endress+Hauser...
  • Page 8: Identification

    2.1.1 Nameplate The following technical data are given on the device nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany Serial number LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 9 Type of probe: Compact, basic version Remote, cable 3m, top entry Remote, cable 3m, side entry Special version, to be specified Housing: A F12 Alu, coated IP68 NEMA6P F23 316L IP68 NEMA6P C T12 Alu, coated IP68 NEMA6P, separate conn. compartment Endress+Hauser...
  • Page 10 V *Gas phase comp. 450mm/18" reference rod, EN10204-3.1 material, NACE MR0175 (316L wetted) inspection certificate Special version, to be specified FMP45- Complete product designation ⇓ Please enter probe length in mm or inch / 0.1 inch inch / 0.1 inch Probe length LN → ä 41 Endress+Hauser...
  • Page 11: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus complies with the statutory requirements of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 12: Installation

    3.2.3 Storage Pack the device so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C to +80 °C. Endress+Hauser...
  • Page 13: Installation Conditions

    Levelflex M FMP45 with HART/4...20 mA Installation Installation conditions 3.3.1 Dimensions Housing dimensions Dimensions for process connection and probe type → ä 14. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing (Aluminium) L00-T12xxxx-06-00-00-en-001 max. 94 F23 housing...
  • Page 14 3 x Ø 8 rope: Ø 4 (0.16”) Ø 10 internal thread: M14 on 4 (0.16”) rope Ø 16 (0.63”) Ø 42,4 (1.67” ) Ø 42,4 (1.67”) (on 1½” thread or flange) Ø 22 (0.87”) L00-FMP45Ixx-06-00-00-en-001 Endress+Hauser...
  • Page 15: General Information On Interface Measurement

    • Emulsion layers in the vicinity of the interface can severely dampen the signal. However, emulsion layers up to 50 mm are permitted. • The measuring range for interface measurement is limited to 10 m. Larger measuring range available on request. Endress+Hauser...
  • Page 16 L00-FMP40xIx-04-00-00-en-004 Fig. 2: Connection diagram for HART loop converter HMX50 (example: passive 2-wire device and current outputs connected as power source) The HART loop converter HMX50 can be acquired using the order number 71063562. Additional documentation: TI429F and BA371F. Endress+Hauser...
  • Page 17: Special Information On Interface Measurement

    A plastic centering disk has to be used for interface measurement (see Accessories → ä 57). L00-FMP4xIxx-17-00-00-xx-003 Note! Rope and rod probes can only be freely installed in the tank under certain circumstances - please contact your Endress+Hauser office. Endress+Hauser...
  • Page 18: Installation Instructions

    Please use a sealing ring according to this standard in the form A, C or D and of a material that is resistant to the application. Supporting probes against warping For Ex approval: A support is required for probe lengths ≥ 3 m, (see drawing). Coax probes L00-FMP4xIxx-17-00-00-xx-004 Endress+Hauser...
  • Page 19 The Levelflex M is a perfect replacement for a conventional displacer system in an existing displacer chamber. In addition to the DIN and ANSI flanges, which are available as standard, Endress+Hauser also offers flanges that suit Fischer and Masoneilan displacer chamber (special product) for this purpose. Thanks to menu-guided local operation, commissioning the Levelflex M only takes a few minutes.
  • Page 20 Process connection with G 1½" and 1½" NPT adapter HT 400 °C XT 280 °C high temperature version (type of probe B) extended temperature version (type of probe A) tank insulation tank insulation max. 280° C (536° F) max. 400° C (752° F) L00-FMP45xxx-17-00-00-en-002 Endress+Hauser...
  • Page 21 • If installing at an angle, the probe length must be limited, depending on the angle of installation. – Up to 1 m = 30° – Up to 2 m = 10° – Up to 4 m = 5° mounting angle L00-FMP4xIxx-17-00-00-en-048 Endress+Hauser...
  • Page 22 Installation with remote electronics • When installing, please observe the instructions on → ä 19. • Mount housing on a wall or pipe (vertically or horizontally) as shown in the diagram. wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5 ENDRESS+HAUSER...
  • Page 23: Post-Installation Check

    • Does the device correspond to specifications at the measuring point, including process temperature and pressure, ambient temperature, measuring range, etc.? • Are the measuring point number and labeling correct (visual inspection)? • Is the measuring device adequately protected against rain and direct sunlight (see → ä 57)? Endress+Hauser...
  • Page 24: Wiring

    " Before connection please note the following: ● The power supply must be identical to the data on the Caution! nameplate (1). ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Switch off power supply before connecting up the device. Order Code: Ser.-No.:...
  • Page 25 " Before connection please note the following: ● The power supply must be identical to the data on the nameplate (1). Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Switch off power supply before connecting up the device. Order Code: Ser.-No.:...
  • Page 26: Connecting The Measuring Unit

    EMC immunity. Cable gland Type Clamping area Standard, EEx ia, IS Plastic M20x1.5 5 to 10 mm EEx em, EEx nA Metal M20x1.5 7 to 10.5 mm Terminals For wire cross-sections of 0.5 to 2.5 mm Endress+Hauser...
  • Page 27 • The measuring device is used with integrated overvoltage protection with 600V gas tube surge arrester in the T12 housing, refer to product overview on → ä 8 • This protection is achieved by the use of other appropriate measures (external protection devices e.g. HAW262Z). Endress+Hauser...
  • Page 28 Wiring Levelflex M FMP45 with HART/4...20 mA 4.2.1 HART connection with Endress+Hauser RMA422 / RN221N FieldCare FXA193 4...20 mA RMA422 ENDRESS + HAUSER RMA 422 RN221N 1 2 3 4 dsdmdm df das. asdas fa asas la. FMP40: LIC0001 ONLINE...
  • Page 29: Recommended Connection

    • Is the terminal assignment correct (see → ä 24 and → ä 25)? • Is the cable gland tight? • Is the housing cover screwed tight? • If power is supplied: Is the device ready for operation and is the liquid crystal display lit? Endress+Hauser...
  • Page 30: Operation

    (e.g. "medium property (003)") ➜ 5) Press ) once return to previous function (e.g. "tank shape (002)") ➜ Press ) twice return to Group selection 6) Press ) to return to Measured value display L00-FMP4xIxx-19-00-00-en-002 Endress+Hauser...
  • Page 31 The third digit numbers the individual functions within the function group: → • Basic setup • Tank Properties • Process Properties In the following section, the position is always indicated in brackets (e.g. "Tank Properties" (002)) after the function described. Endress+Hauser...
  • Page 32: Display And Operating Elements

    Primary measuring value Position indicator ENDRESS + HAUSER Description Secondary measuring value Unit Symbol – Selection list Function groups -> Functions HOME F000 F001 F002 F003 F004 ... FG00 FG01 FG02 Help text FG03 FG04 FG05 FG06 Envelope FG07 curve L00-FMP4xIxx-07-00-00-en-002 Endress+Hauser...
  • Page 33 Contrast settings of the LCD Hardware locking/unlocking Following hardware locking, it is not possible to operate the device via the display or communication! Unlocking can only be performed via the display. A release code must be entered to do so. Endress+Hauser...
  • Page 34: Local Operation

    It is not possible to unlock the hardware by communication here. All parameters can be displayed even if the device is locked. ⇒ ENDRESS + HAUSER Press simultaneously – ⇓ ⇓ The LOCK_SYMBOL appears on the LCD. Endress+Hauser...
  • Page 35 There is no need to change these parameters under normal circumstances and, consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.
  • Page 36 • Application Param. (0A8) • Customer Unit (042) • Medium Propert. 2 (018) • The mapping can be deleted in the "Cust. Tank Map" (055) function of the "Extended Calibr" (05) function group. • A complete "Basic Setup" (00) must be performed. Endress+Hauser...
  • Page 37: Displaying And Acknowledging Error Messages

    Error" (0A2) function. FieldCare FieldCare is Endress+Hauser's plant asset management tool based on FDT technology. You can use FieldCare to configure all your Endress+Hauser devices, as well as devices from other manufacturers that support the FDT standard. It is compatible with the following operating systems: WinNT4.0, Win2000 and Windows XP.
  • Page 38 Operation Levelflex M FMP45 with HART/4...20 mA Menu-guided commissioning L00-fmp-Ixxx-20-00-00-en-033 Signal analysis via envelope curve L00-fmp-Ixxx-20-00-00-en-034 Endress+Hauser...
  • Page 39: Hart Communication

    4 PROCESS COND. Bksp Page 5 END OF PROBE FIELD COMMUNICATOR SAVE HOME L00-FMPxxxxx-07-00-00-yy-005 Note! • Further information on the HART handheld terminal is given in the appropriate Operating Instructions included in the carrying case of the Field Communicator 375. Endress+Hauser...
  • Page 40: Commissioning

    (this message appears the first time the device is switched on) ⇓ The current measured values PV (interface layer) and SV (level) are displayed in the standard settings. ⇓ After is pressed, you reach the group selection. This selection enables you to perform the basic setup Endress+Hauser...
  • Page 41: Basic Setup

    UP = thickness upper medium SD = safety distance - setting in 015 basic setup (standard) tank shape process properties empty calibr. full calibr. upper block.dist partially filled Standard fully flooded optio n (description see BA366F) safety settings linearisation extended calibr. Standard L00-FMP4xIxx-19-00-00-en-001 Endress+Hauser...
  • Page 42 • If the power supply fails, all preset and configured values remain safely stored in the EEPROM. " Caution! All functions are described in detail, as is the overview of the operating menu itself, in BA366F - "Description of Device Functions" on the enclosed CD-ROM. Endress+Hauser...
  • Page 43: Basic Setup With The Vu331

    The setting for the upper blocking distance is an integral part of the basic setup if "Flooded" is selected. • A change in the total level when "Flooded" is selected impacts the accuracy. Endress+Hauser...
  • Page 44 Rise time: 0 s Function "Empty Calibr." (005) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). E = empty calibration (= zero) L00-FMP4xIxx-14-00-06-en-001 Endress+Hauser...
  • Page 45 Rod probe in bypass Rope probe in free field Coax probe The blocking distances indicated are preset. Measurements in free field available on request. Larger measuring range available on request. Note! Reliable measurement cannot be guaranteed within the blocking distance. Endress+Hauser...
  • Page 46 [mm] L00-FMP4xxxx-05-00-00-en-001 L00-FMP4xxxx-05-00-00-en-002 If the DC value is less than 7 for rope probes, then measurement is not possible in the area of the tensioning weight (0 to 250 mm from end of probe; lower blocking distance). Endress+Hauser...
  • Page 47 – Liquefied gases, e.g. N , CO – Liquefied gas, e.g. propane – Solvent 1.6 to 1.9 – Freon – Palm oil 1.9 to 2.5 – Mineral oils, fuels – Benzene, styrene, toluene 2.5 to 4 – Furan – Naphthalene Endress+Hauser...
  • Page 48 • Distance to level incorrect -> empty tank/bypass and perform mapping over the entire probe length (see BA366F - "Description of Device Functions"). • Distance to interface incorrect -> check entry for "Medium Prop." (003). ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 49: Envelope Curve With Vu331

    Note! If the cyclic envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimized. Endress+Hauser...
  • Page 50: Function "Envelope Curve Display" (0E3)

    Difference curve = envelope curve - mapping (empty curve) The mapping (empty curve) should be a good representation of the probe and the empty tank or silo. Ideally, only the signals from the medium being measured remain in the difference curve. Endress+Hauser...
  • Page 51 L00-FMP4xIxx-07-00-00-en-005 Horizontal Zoom mode Press , to get to the envelope curve navigation. You are in the Horizontal Zoom mode. is displayed. You now have the following options: • increases the horizontal scale. • reduces the horizontal scale. L00-FMP4xIxx-07-00-00-xx-001 Endress+Hauser...
  • Page 52 The zoom and shift settings configured are retained. The Levelflex does not use the standard display until you activate the "Recording Curve" function (0E2) again. ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
  • Page 53: Basic Setup With Endress+Hauser Operating Program

    Levelflex M FMP45 with HART/4...20 mA Commissioning Basic setup with Endress+Hauser operating program Proceed as follows to perform the basic setup with the operating program: • Start the operating program on the PC and establish a connection. • Select the "Basic Setup" function group in the navigation window.
  • Page 54 • Enter the application parameters: – Tank Properties – Process Properties L00-fmp-Ixxx-20-00-00-en-036 Basic Setup, step 3/3: • Enter the application parameters: – Empty calibration – Full Calibration – Upper Blocking Distance – Medium Properties – Dist. Interface – Dist. Level L00-fmp-Ixxx-20-00-00-en-039 Endress+Hauser...
  • Page 55: User-Specific Applications (Operation)

    After the basic setup, an evaluation of the measurement with the aid of the envelope curve is recommended. L00-fmp-Ixxx-20-00-00-en-034 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA366F - "Description of Device Functions" on the enclosed CD-ROM. Endress+Hauser...
  • Page 56: Maintenance

    They contain the related replacement instructions. All the spare parts kits, including the order numbers, which you can order from Endress+Hauser to repair the Levelflex M are listed on → ä 65, 67. For further information on service and spare parts, please contact Endress+Hauser Service.
  • Page 57: Accessories

    Levelflex M FMP45 with HART/4...20 mA Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A weather protection cover made of stainless steel is available for outdoor installation (order code: 543199-0001).
  • Page 58: Commubox Fxa191 Hart

    TI404F/00/en. Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser Common Data Interface) to the USB port of a personal computer or laptop. For details refer to TI405C/07/en. Note! For the following Endress+Hauser devices you need the "ToF adapter FXA291" as an additional accessory: •...
  • Page 59: Fhx40 Remote Display And Operation

    20m; for HART 20m; for PROFIBUS PA/FOUNDATION Fieldbus Additional options: Basic version Mounting bracket, pipe 1"/ 2" FHX40 - Complete product designation To connect the FHX40 remote display, use the appropriate cables provided for the communication version of the device. Endress+Hauser...
  • Page 60: Troubleshooting

    Connect the plug Ready Display works? of the display. correctly The display is possibly defective. Output current between 3.6 …22mA ? Contact Endress+Hauser Service Not ok Output current Correct the Check cabling Current is ok? Ready < 3.6 mA ? (2 wire) cabling <...
  • Page 61: System Error Messages

    Temperature at the electronics too high or Check temperature, replace HF module defective HF module if defective W512 Recording of mapping - Mapping active Wait a few seconds until alarm please wait disappears W601 Linearization ch1 curve not Linearization not monotone increasing Correct table monotone Endress+Hauser...
  • Page 62 Perform a reset if necessary A671 Linearization ch1 not Linearization table is in edit mode Switch on linearization table complete, not usable W681 Current ch1 out of range Current out of valid range (3.8 mA to Check calibration and linearization 21.5 mA) Endress+Hauser...
  • Page 63: Application Errors

    → The measured values Echo threshold for the Check the DK value setting in → for the interface and the total level too high "Medium Properties" (003). total level are identical F m/ft expected actual E m/ft t → Endress+Hauser...
  • Page 64 60 mm. F m/ft level expected actual E m/ft t → Interface measured Emulsion layer present Emulsion layer affects the → value jumps measurement. Please contact Endress+Hauser. F m/ft actual actual expected expected E m/ft t → Endress+Hauser...
  • Page 65: Spare Parts

    Spare parts Note! You can order spare parts directly from your Endress+Hauser service organization by giving the serial number which is printed on the transmitter nameplate (→ ä 8). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered.
  • Page 66 52015586 Power unit, CSA, 90 to 250V AC (housing F12) for electronics, 4-wire 40 Display 52026443 Display/operating module VU331 9.4.2 Spare parts for Levelflex M FMP45, housing type F23 20 Cover 52018670 Cover F23 316L, sight glass, seal 52018671 Cover F23 316L, seal Endress+Hauser...
  • Page 67 I L O o .: s s b e re a s u ic h r in g ra n 6 .. .3 x . 2 4 .. .2 > 7 0 ° C t > 8 5 ° C L00-FMP41Cxx-00-00-06-xx-002 Endress+Hauser...
  • Page 68 71061455 electronics FMP4x, 2-wire, HART, interface 31 HF module 52019780 HF module LEVELFLEX-M 35 Terminal module / power unit 52013302 Terminal module Ex d, 4-pin, 2-wire, HART, T12 52018949 Terminal module EEx ia, 4-pin, HART, T12, OVP 40 Display 52026443 Display/operating module VU331 Endress+Hauser...
  • Page 69 . 20 > 70 > 70 °C °C t >8 Gehäuse F12 5° C t >8 Gehäuse T12 5° C Version 280° C Version 400° C flange or thread flange or thread Flansch / Gewinde Flansch / Gewinde L00-FMP45xxx-00-00-06-xx-001 Endress+Hauser...
  • Page 70 Troubleshooting Levelflex M FMP45 with HART/4...20 mA 55 Probe without process connection On request. Endress+Hauser...
  • Page 71: Return

    Levelflex M FMP45 with HART/4...20 mA Troubleshooting Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the grooves for seals and crevices which could contain fluid residues.
  • Page 72: Technical Data

    Is in the Function group "Basic Setup" (00) as of → ä 43. Maximum measured error Resolution • Digital: 1 mm • Analog: 0.03 % of the measuring range Reaction time The reaction time depends on the configuration. Shortest time: • 2-wire electronics: 1 s Endress+Hauser...
  • Page 73 5.7 % 13.2 % 76 % Special versions of FMP45 are available which provide a compensation method for the gas phase effect. Please contact your local Endress+Hauser representative. 10.1.4 Operating conditions: environment Ambient temperature range Ambient temperature at the electronics: -40 °C to +80 °C The function of the LCD display is restricted at T <-20 °C and T...
  • Page 74 80 °C with separate [°C] housing 66 °C compact: F12 housing T12 housing 56 °C compact: F23 housing -250 -200 -100 [°C] tank insulation permitted process connection temperature L00-FMP45xxx-05-00-00-en-003 Storage temperature -40 °C to +80 °C Endress+Hauser...
  • Page 75 The measured value can be affected by strong electromagnetic fields when installing rod and rope probes without a shielding/metal wall, e.g. plastic, and in wooden silos. • Interference emission to EN 61326 - x series, Class A equipment. • Interference immunity: the measured value can be affected by strong electromagnetic fields. Endress+Hauser...
  • Page 76 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical. • ASME B 16.5a - 1998 Tab. 2-2.2 F316 • ASME B 16.5a - 1998 Tab. 2.3.8 N10276 • JIS B 2220 Endress+Hauser...
  • Page 77 Probe length Probe length Probe length Weight of flange Weight of flange Weight of flange Weight of flange Material • Housing: – Housing F12/T12: aluminum (AlSi10Mg), seawater-resistant, chromatized, powder-coated – Housing F23: 316L, corrosion-resistant steel • Sight window: glass Endress+Hauser...
  • Page 78 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. Manufacturer declaration Permitted pressures, temperatures and load cycles as per EN 13445 and AD- data sheet S2 (for FMP45).
  • Page 79 Documentation Note! This supplementary documentation can be found on our product pages on www.endress.com. • Technical Information (TI386F/00/en) • Safety Manual "Functional safety manual" (SD174F/00/en) • Certificate "Allgemeine bauaufsichtliche Zulassung" (approval from the German Institute of Structural Engineering) (ZE256F/00/en) Endress+Hauser...
  • Page 80: Appendix

    + sw-no. serial no. distance unit Note! The default values of the parameters are typed in boldface. L00-FMP4xIxx-19-00-01-en-003 Endress+Hauser...
  • Page 81 4 mA value 20 mA value sim. level interface sim. volume interface display test dist. interface application par. not modified modified download mode L00-FMP4xIxx-19-00-02-en-003 Endress+Hauser...
  • Page 82: Description Of Functions

    The dielectric constant (DK) of the medium has a direct impact on the degree of reflection of the high-frequency pulses. In the case of large DK values, such as for water or ammonia, there is strong pulse reflection while, with low DK values, such as for hydrocarbons, weak pulse reflection is experienced. Endress+Hauser...
  • Page 83 32 points, which is based on a table entered manually or semi- automatically, can be activated on site or via remote operation. This function allows the level to be converted to units of volume or mass, for example. Endress+Hauser...
  • Page 84 • With a personal computer, FXA193 (RS232C) or FXA291 and ToF adapter FXA291 (USB) and the Endress+Hauser operating software. FieldCare is a graphical operating software for devices from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-pulse). It assists with commissioning, data backup, signal analysis and documentation of the measuring point.
  • Page 85: Index

    Nameplate ........8 Endress+Hauser...
  • Page 86 Levelflex M FMP45 with HART/4...20 mA Index Endress+Hauser...
  • Page 87 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 88 www.endress.com/worldwide BA365F/00/en/03.08 71060887 CCS/FM+SGML 6.0/ProMoDo 71060887...