Checklist for commissioning
The following checklist refers to the configuration via the NI-Fieldbus configurator. In general, the
operation is rather similar for other network design tools.
1.
Configure the network and integrate the device.
– Identify the device by means of the device ID and serial number.
– If appropriate, assign a new PD_TAG.
2.
Configure the resource block.
– Check the position of the hardware switch in WRITE_LOCK
– If "locked" is displayed, change the position of the DIP-switch.
– If appropriate, change the block tag (right-hand click on tree).
– Set MODE_BLK_TARGET to Out-of-Service.
– Reset the device to factory values by using the function RESTART => Defaults
(this function may also be available with a right-hand click on the device name)
– If appropriate, assign a tag description (TAG_DESC).
– Set MODE_BLK_TARGET to Auto.
3.
Configure the Sensor block.
– If appropriate, change the block tag (right-hand click on tree).
– Set MODE_BLK_TARGET to Out-of-Service.
– If appropriate, assign a tag description (TAG_DESC)
– Configure the device as described in Chapter 6.4.
– Set MODE_BLK_TARGET to Auto.
4.
Configure the analog input block.
– If appropriate, change the block tag (right-hand click on tree).
– Set MODE_BLK_TARGET to Out-of-Service.
– If appropriate, assign a tag description (TAG_DESC).
– Set Channel to measured value or distance.
– Set L_TYPE to "DIRECT" if the OUT value is to be in technical units e.g. ft to "INDIRECT"
if the OUT value is to be scaled.
– Set the desired output damping in PV_TIME.
– If appropriate, set the advisory and critical alarms.
– Set MODE_BLK_TARGET to Auto.
5.
Link the function blocks in the function block editor.
6.
Download the configuration (menu configure).
7.
If appropriate, check the configuration by using the SIMULATE function.