Installation
20
The probe must be mounted opposite the
agitator.
If possible, check whether a non-contact
process, ultrasonic or level-radar would be
better suited, particularly if the agitator
generates large mechanical loads on the probe.
3.3.4
Notes on special installation situations
Installation at an angle
• For mechanical reasons, the probe should be
installed as vertically as possible.
• The maximum mounting angle is
– up to 1 m = 30°
– up to 2 m = 10°
– up to 4 m = 5°.
Levelflex M FMP43 with FOUNDATION Fieldbus
L00-FMP43xxx-17-00-00-xx-005
L00-FMP43xxx-17-00-00-xx-006
Endress+Hauser