Commissioning
⇒
ENDRESS + HAUSER
–
+
E
62
E
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (=span).
F
Levelflex M FMP43 with FOUNDATION Fieldbus
E = empty calibration (= zero)
E max = probe length – lower blocking distance
0%
100%
F = full calibration (= span)
F max = E – upper blocking distance
0%
L00-FMP4xxxx-14-00-06-en-008
L00-FMP4xxxx-14-00-06-en-009
Endress+Hauser