Endress+Hauser Fieldbus Levelflex M FMP43 Operating Instructions Manual page 67

Guided level-radar
Hide thumbs Also See for Fieldbus Levelflex M FMP43:
Table of Contents

Advertisement

Levelflex M FMP43 with FOUNDATION Fieldbus
reference point of measurement
60 mm
50 mm
40 mm
30 mm
20 mm
10 mm
3 mm
0 mm
- 3 mm
- 10 mm
- 20 mm
- 30 mm
- 40 mm
- 50 mm
- 60 mm
100 mm
Endress+Hauser
Maximum measured error
Typical values under reference operating conditions:
DIN EN 61298-2, percentage values with reference to the span.
Output:
Sum of non-linearity,
non-repeatability
and hysteresis
Offset / zero point
If the reference conditions are not met, the offset/zero point resulting from the installation setup
may be up to ±12 mm. This additional offset/zero point can be compensated for by entering a
correction ("offset" function (057)) during commissioning.
Differing from this, the following measuring error is present in the vicinity of the upper and lower
probe end:
200 mm
Digital
Analog
±3 mm
± 0.06 %
±4 mm
± 0.03 %
200 mm
80 mm
Commissioning
DK = 2
(oils and solvents)
(water-based
DK > 7
medium)
(water-based
DK > 7
medium)
(
oils and solvents
DK = 2
40 mm 20 mm
)
L00-FMP43xxx-05-00-00-en-001
67