Levelflex M FMP43 with FOUNDATION Fieldbus
Parameter
Position
Indicator
language
092
back to home
093
format display
094
no.of decimals
095
sep. character
096
unlock parameter
0A4
3)
If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.
Endress+Hauser
5.5.8
Display Block
Operation
The display block contains the parameters required to parametrise the display module VU331
(which is contained in the remote display and operating unit FHX40). These parameters can also be
addressed by using the VU331 display module.
The display block is opened by clicking on the "display" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. In order to resume operation, change
3)
MODE_BLK to AUTO
Block administration parameters
Parameter
MODE_BLK
TAG_DESC
BLOCK_ERROR
Methods
The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the
operation of the device. A method is an interactive sequence of steps that must be followed in order
to obtain a particular function from the device.
The Levelflex M has got the following methods:
• Display
Most of these methods are identical to the respective function group in the operating menu. A
detailed description of them can be found in the "Description of Instrument functions", BA245F/
00/en.
Instrument specific parameters
rel.
Variable Name
Index
13
PARLANGUAGE
14
PARBACKTOHOME
15
PARFORMATDISPLAY_FT
16
PARNOOFDECIMALS
17
PARSEPARATIONCHARACTER
18
PAROPERATIONCODE
.
Description
See description in Resource block. The possible operating modes of the sensor block are:
– AUTO: the block is operating as normal.
– OOS: the block is out of service.
User description of the intended application of the block.
Shows the error status associated with the block components
– Out-of-Service: the block is in OOS mode.
Size
[bytes]
1
2
1
1
1
2
Type
Access Storage
Class
Unsigned8
RW
non-vol.
Integer16
RW
non-vol.
Unsigned8
RW
non-vol.
Unsigned8
RW
non-vol.
Unsigned8
RW
non-vol.
Unsigned16
RW
non-vol.
Operation
Changeable
in Mode
Auto, OOS
Auto, OOS
Auto, OOS
Auto, OOS
Auto, OOS
OOS
49