Endress+Hauser Fieldbus Levelflex M FMP43 Operating Instructions Manual page 27

Guided level-radar
Hide thumbs Also See for Fieldbus Levelflex M FMP43:
Table of Contents

Advertisement

Levelflex M FMP43 with FOUNDATION Fieldbus
"
Caution!
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA's).
Make sure you use the specific cable gland.
-
-
Endress+Hauser
Wiring in T12 housing
Before connection please note the following:
FOUNDATION
Fieldbus devices are marked on the
nameplate (1). The voltage is determined by the
FOUNDATION
Fieldbus standard and the desired safety
concept. (see chapter 4.3).
Connect potential matching line to transmitter earth terminal
before connecting up the device.
Tighten the locking screw:
It forms the connection between the probe and the housing
earth potential.
Connect up the Levelflex M as follows:
Before unscrew housing cover (2) at seperate connection room
turn off the power supply!
Insert cable (3) through gland (5).
Use screened, twisted wire pair.
Only ground screening of the line (5) on sensor side.
Make connection (see pin assignment).
Tighten cable gland (4).
Screw on housing cover (2).
Switch on power supply.
5
plant
1 2
3 4
ground
- +
ENDRESS+HAUSER
LEVELFLEX-M
Order Code:
Ser.-No.:
LN=
PN=
1
Profibus PA
FOUNDATION
Fieldbus
90 ... 253 V AC 1VA
10,5 ... 32 V DC 1W
16 ... 3
V DC 0,8W
4 ... 20 mA HART
2-wire
4-wire
TA > 70°C :
t >85°C
if modification
X =
see sep. label
Dat./Insp.:
4
3
1 2
3 4
Wiring
Made in Germany
D-79689 Maulburg
IP68 / NEMA 6P
Patents
D01301-A
2
L00-FMP41Cxx-04-00-00-en-006
27

Advertisement

Table of Contents
loading

Table of Contents