Eclipse 8/16/32/99 Series - Installation Manual
2.3.4 Connecting Fire Lines
Fire detectors can be connected to every zone set as Fire type zone.
For ECLIPSE 8 and ECLIPSE 16 is possible to realize only 4-wire connection of 12V alarm fire base with one or two
balancing resistors.
For ECLIPSE 32 and ECLIPSE 99 is possible to realize 4-wire connection of 12V alarm fire base with one or two
balancing resistors and also connection of two fire detectors to a doubling zone.
PGM 4 for ECLIPSE 32 and ECLIPSE 99 has a special functionality. The output can be programmed to operate as Fire
zone with realizing of 2-wire connection of standard 24V fire alarm base.
ECLIPSE
8/16/32/99
ECLIPSE
8/16/32/99
ECLIPSE 32/99
Fire
detector
base
Fire
detector
base
*
Fire
detector
base 1
Figure 12. Connecting of Fire detectors
A) Connecting a fire detector with one balancing
resistor
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
programmed at address 3013 – event 61.
The Zone type is programmed at address 2xx1,
where "xx" is the zone number.
B) Connecting a fire detector with two balancing
resistors
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
programmed at address 3013 – event 61.
The Zone type is programmed at address 2xx1,
where "xx" is the zone number.
C) Connecting of two fire alarm detectors to a
zone with set doubling connection style
The PGM 1 must be programmed as Fire Reset
and the active status must be +12V.
The PGM 1 Fire reset option for activation is
Fire
programmed at address 3013 – event 61.
detector
The Zone type is programmed at address 2xx1,
base 2
where "xx" is the zone number.
* Note: Instead of 1k resistor, you can use also
two 510Ohm resistors (by one for every fire
detector), instead one 1K resistor.
D) Realization of 2-wire connection of standard
fire bases to PGM 4 programmed as Fire Zone
at address 3000 in the menus of ECLIPSE32/99
control panel.
16