Connecting The Sounders Circuits; Connecting Fault And Fire Relay Circuits - Teletek electronics MAG8 Installation And Operation Manual

Hide thumbs Also See for MAG8:
Table of Contents

Advertisement

• Operate ALL detection devices applicable to this zone, to ensure correct receipt of a fire
signal and the correct operation of the panel controls. Refer to the User Instructions on
the inside of the panel.
• Repeat the connection process for the other zones stated above. ENSURE the supply
voltages are initially disconnected prior to each stage.
Once the connections of all zones are completed, connect and test
!
any of the other auxiliary circuits BEFORE connecting the sounder
circuits.
5. Connecting the sounder Circuits
• Disconnect the mains power supply and the battery connection.
• Remove the EOL-Resistor from the terminal block of sounder circuit 1 (SND 1) and fit
to the last sounder of circuit one:
• Check all sounder connections.
• Connect sounder circuit ONE to the panel terminal block.
• Apply mains and battery power.
• Press "
RESET" button.
• The panel must be in Normal Operation Mode - only POWER SUPPLY 230V will be
illuminated.
• Activate a zone Call Point. The sounders should operate. Press the RESET button.
Repeat the connection process for the second external sounder circuit, as stated above.
ENSURE the supply voltages are initially disconnected prior to each stage.
If GENERAL FAULT and SOUNDER FAULT/DISABLE LED's illuminate,
there is a wiring/ connection problem. Check the polarity of the connection of
each of the devices, the polarity of the connection of the devices to the Panel
terminal block or whether an earth fault exists.

6. Connecting FAULT and FIRE Relay Circuits

The relays with changeover contacts are intended for control of low voltage devices.
Attention: No mains power should be supplied to the clamps of the
!
FAULT and FIRE relays.
After the connection is established, test each of the circuits for external
device control.
Fire Control Panel MAG8 - Installation and Operation Manual
S1
S2
10K
SN
black
LEGEND
red
brown
9

Advertisement

Table of Contents
loading

Table of Contents