Analog Input Simulation; Switch Inputs Simulation - GE Multilin MM3 Motor Manager 3 Instruction Manual

Hide thumbs Also See for Multilin MM3 Motor Manager 3:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS
5.8.5
Analog Input
Simulation
] ANALOG INPUT
] SIMULATION
5.8.6
Switch Inputs
Simulation
] CURRENT SIMULATION
]
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
PATH: S7 TESTING

ANALOG INPUT SIMULATION

The analog input simulation settings are programmed as follows:
SIMULATION: Enter "ON" to switch from an actual analog input to the programmed
simulated value. Set to "OFF" after simulation is complete.
SIMULATION ENABLED FOR: Select the desired length of time to enable simulation.
When the programmed time has elapsed, analog input simulation will turn off. If
unlimited is selected, the simulated analog input will be used until simulation is turned
off via the simulation on/off message or via the serial port or until control power is
removed.
ANALOG INPUT: Enter an analog input current in the range of 4 to 20 mA to be
simulated.
PATH: S7 TESTING

SWITCH INPUTS SIMULATION

SIMULATION:
OFF
SIMULATION ENABLED
FOR:
15 min.
ANALOG INPUT
OFF mA
SIMULATION:
OFF
SIMULATION ENABLED
FOR:
15 min.
START A
INPUT: OPEN
START B
INPUT: OPEN
STOP
INPUT: OPEN
CONTACTOR A STATUS
INPUT: OPEN
CONTACTOR B STATUS
INPUT: OPEN
LOCAL ISOLATOR
INPUT: OPEN
INTERLOCK 1
INPUT: OPEN
INTERLOCK 2
INPUT: OPEN
INTERLOCK 10
INPUT: OPEN
S7 TESTING
Range:
ON, OFF
Range:
5 to 305 min. or UNLIMITED in
steps of 5
Range:
4.0 to 20.0 mA or OFF in steps
of 0.1
Range:
ON, OFF
Range:
5 to 300 min. or UNLIMITED in
steps of 5
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
Range:
OPEN, CLOSED
5–41