A2 STATUS
6.3.3

Motor Status

6–10
PATH: A2 STATUS
MOTOR STATUS
] MOTOR STATUS
]
The motor status actual values display the following information:
MOTOR STATUS: This message indicates the status of the motor. The possible motor
status indications are shown below:
• "UNAVAILABLE": There is at least one condition present that is preventing start
commands from operating. Possible conditions are: a trip is present, the STOP key
is being pressed, the stop switch input is open, one of the process interlock
switches is open, an undervoltage delayed restart is in progress, an
autotransformer start inhibit is in progress, or the
• "AVAILABLE-AUTO": Start commands from the serial port or the Auto Start A / Auto
Start B interlock switch inputs will be performed. Start commands from the Start A
/ Start B switch inputs and the START A/B keys will be ignored.
• "AVAILABLE-MANUAL": Start commands from the Start A / Start B switch inputs
and/or the START A/B keys will be performed. Start commands from the serial port
and Auto Start A / Auto Start B switch inputs will be ignored.
• "RUNNING": At least one contactor output relay is closed.
DELAYED RESTART IN PROGRESS: This message will appear if a delayed undervoltage
restart is in progress. The displayed time indicates the time remaining until the start
sequence will begin.
DELAYED START IN PROGRESS: This message will appear if a delayed start is in
progress. This occurs if one of the auxiliary relays is set to pre-contactor A or B
operation. The displayed time indicates the time remaining until contactor A
energizes.
TRANSFER TIME IN PROGRESS: This message will appear if a high speed to low speed
transition is occurring on a two-speed starter or if a direction change is occurring on
reversing starter. The displayed time indicates either the time remaining until the low
CHAPTER 6: ACTUAL VALUES
MOTOR STATUS:
RUNNING
DELAYED RESTART IN
PROGRESS:
15 s
DELAYED START IN
PROGRESS:
15 s
TRANSFER TIME IN
PROGRESS:
10 s
RESTART INHIBIT
EXTERNAL START
CAUSE OF STOP
CAUSE OF LAST STOP
EXTERNAL STOP
STARTER TYPE
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
setpoint is "OFF".