MODBUS MEMORY MAP
8–24
Table 8–2: Modbus Memory Map (Sheet 9 of 28)
Modicon
Address
dec.
hex
44157
4156
103C
Overload pickup level
44158
4157
103D
...Reserved...
44159
4158
103E
...Reserved...
44160
4159
103F
...Reserved...
Motor protection: ground fault (read/write setpoints)
44161
4160
1040
Ground fault alarm level
(residual)
44162
4161
1041
Ground fault alarm level
(50:0.025 CT)
44163
4162
1042
Ground alarm delay on run
44164
4163
1043
Ground fault trip level
(residual)
44165
4164
1044
Ground fault trip level
(50:0.025 CT)
44166
4165
1045
Ground trip delay on run
44167
4166
1046
Delay contactor ground
fault trip (Aux. 1)
44168
4167
1047
Delay contactor ground
fault trip (Aux. 2)
44169
4168
1048
...Reserved...
Motor protection: options (read/write setpoints)
44170
4169
1049
Minimize reset time
44171
4170
104A
Stopped motor cooling
time
44172
4171
104B
Overload trip reset
44173
4172
104C
Phase unbalance alarm
44174
4173
104D
Thermal capacity alarm
44175
4174
104E
Open control circuit trip
44176
4175
104F
Reset alarms using the
reset key
44177
4176
1050
Underpower alarm level
44178
4177
1051
Underpower alarm delay
44179
4178
1052
Underpower trip level
44180
4179
1053
Underpower trip delay
44181
4180
1054
Acceleration time alarm
delay
44182
4181
1055
Acceleration time trip delay
* – Maximum setpoint value and 65535 represent OFF; ** – 1/phase current scale factor × A; *** – 101
represents unlimited;
† – Minimum setpoint value represents OFF; ~ – 0.1 × A when high resolution mode is disabled;
0.01 × A when enabled
Description
Range
100 to
125
...
...
...
10 to
101
1 to
151
1 to 60
10 to
101
0 to
151
0 to 50
0 to
1000
0 to
1000
...
0 to 1
5 to
1080
0 to 1
0 to 1
1 to
101
0 to 1
0 to 1
Load protection (read/write setpoints)
2 to
11001
1 to 60
2 to
11001
1 to 60
5 to
1255
5 to
1255
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CHAPTER 8: COMMUNICATIONS
Step
Units
Format
Default
1
0.01 ×
F1
100 = 1.00
× FLC
FLC
...
...
...
...
...
...
...
...
...
1
% of
F1*
65535 =
FLC
OFF
1
0.1 ×
F1*
65535 =
A
OFF
1
s
F1
1
% of
F1*
65535 =
FLC
OFF
1
0.1 ×
F1*
65535 =
A
OFF
1
0.1 ×
F1
10 = 1.0
s
100
ms
F1
100
ms
F1
...
...
...
1
---
F14
1 =
ENABLE
1
minut
F1
es
1
---
F16
0 =
MANUAL
1
---
F14
1 =
ENABLE
1
%
F1*
101 =
OFF
1
---
F14
0 =
DISABLE
1
---
F14
0 =
Disable
1
0.1 ×
F1*
65535 =
kW
OFF
1
s
F1
0.1 ×
1
F1*
65535 =
kW
OFF
1
s
F1
5
0.1 ×
F1*
65535 =
s
OFF
5
0.1 ×
F1*
65535 =
s
OFF
...
...
...
10
0
0
...
30
10
10