MODBUS MEMORY MAP
8–44
Value
Description
1
Available - auto
2
Available - manual
3
Available - manual and auto
4
Running
4
ESD trip or stop (mod)
F8: Motor model (enumeration)
Value
Description
0
Starting
1
Stopped
2
Running
F9: Cause of trip (enumeration)
Value
Description
0
No trip
1
Process interlock A
2
Process interlock B
3
Process interlock C
4
Process interlock D
5
Parameters not set
6
Faceplate stop
7
Process stop
8
Not used
9
Not used
10
Not used
11
Overload
12
Single phase
13
Thermistor
14
Acceleration time
15
Ground fault
16
Stalled rotor
F10: Two characters (ASCII characters)
Format: 7F00 (32 to 127 = ASCII characters)
Format: 007F (32 to 127 = ASCII characters)
F11: Starter type (enumeration)
Value
Description
0
Off
1
Full voltage (direct online) non-
reversing
2
Full voltage (direct online) reversing
3
Wye-delta open transition
4
Two speed
5
Inverter
6
Slip ring
CHAPTER 8: COMMUNICATIONS
Value
Description
17
Not used
18
Local isolator
19
Serial communications failure
20
Internal fault
21
Undercurrent
22
Emergency stop
23
Underpower
24
Analog input high
25
Analog input low
26
Plant interlock
27
Process interlock E
28
Process interlock F
29
Process interlock G
30
Process interlock H
31
Process interlock I
32
Process interlock J
Value
Description
7
Autotransformer open transition
8
Part winding
9
Wye-delta closed transition
10
Autotransformer closed transition
11
Duty/standby
12
Soft starter