CHAPTER 8: COMMUNICATIONS
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
F12: Auxiliary relay operation (enumeration)
Value
Description
0
Non-failsafe
1
Failsafe
F13: Ground CT type (enumeration)
Value
Description
0
50:0.025 CBCT
1
Residual
F14: Enable/disable value (enumeration)
Value
Description
0
Disable
1
Enable
F15: VT connection type (enumeration)
Value
Description
0
Line (A-B)
1
Phase (A-N)
F16: Manual/auto value (enumeration)
Value
Description
0
Manual
1
Auto
F17: Interlock input function (enumeration)
Value
Description
0
Not used
1
Process interlock A
2
Process interlock B
3
Process interlock C
4
Process interlock D
5
Plant interlock
6
Lockout reset
7
Setpoint access
8
Auto permissive
9
Auto start A
10
Auto start B
11
Reset emergency stop trip
12
Reset undercurrent trip
13
Two-wire control
14
Test switch
15
Remote permissive
16
Communication select
17
Interlock counter
F18: Interlock stop / latched trip (enumeration)
Value
Description
0
Interlock stop
MODBUS MEMORY MAP
Value
Description
18
Auxiliary relay 1 inhibit
19
Wye-delta 1M contact
20
Wye-delta 2S contact
21
Undervoltage restart inhibit
22
Autotransformer 2S contact
23
Process interlock E
24
Process interlock F
25
Process interlock G
26
Process interlock H
27
Process interlock I
28
Process interlock J
29
Stop A
30
Stop B
31
Remote reset
32
Motor select A/B
33
Duty select manual/auto
34
Bypass contact
8–45