CHAPTER 6: DNP POINT LISTS

Analog Input / Analog Input Change

750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
In the following table, the entry in the "Format" column indicates that the format of the
associated data point can be determined by looking up the entry in the Memory Map Data
Formats table. For example, an "F1" format is described in that table as a (16-bit) unsigned
value without any decimal places. Therefore, the value read should be interpreted in this
manner.
The point list for Analog Input (Object 30) and Analog Input Change (Object 32) is shown
below. Refer to the notes following the table for additional details.
Table 3: Analog Inputs DNP Points (Sheet 1 of 8)
Index when Point
Format
Mapping is:
Disable
Enabled
d
n/a
0
n/a
1
n/a
118
n/a
119
0
120
1
121
2
122
3
123
4
124
5
125
6
126
7
127
8
128
9
129
10
130
11
131
12
132
13
133
14
134
15
135
Description
-
User Map Value 1
-
User Map Value 2
-
User Map Value 119
-
User Map Value 120
F49
Phase Time Overcurrent 1
F49
Phase Instantaneous Overcurrent 1
F49
Phase Instantaneous Overcurrent 2
F49
Ground Time Overcurrent
F49
Ground Instantaneous Overcurrent
F49
Neutral Time Overcurrent 1
F49
Neutral Time Overcurrent 2
F49
Neutral Instantaneous Overcurrent 1
F49
Neutral Instantaneous Overcurrent 2
F49
Phase Directional Is Reverse
F49
Neutral Directional Is Reverse
F49
Manual Close Blocking
F49
Cold Load Pickup Blocking
F49
Bus Undervoltage 1
F49
Bus Undervoltage 2
F49
Line Undervoltage 1
ANALOG INPUT / ANALOG INPUT CHANGE
Event
Class
Assigned
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
6 - 5