TECHNICAL SPECIFICATIONS
1.2.4

Communications

1.2.5

Conformance

1–8
CONTACTOR A AND B OUTPUT RELAYS
Operating current:..............8 A maximum
Operating voltage: .............380 V AC / 125 V DC maximum
Make/carry: ...........................8 A continuous at 30 V DC / 250 V AC (resistive loads)
3.5 A continuous at 30 V DC / 250 V AC (inductive loads, PF = 0.4)
Switching capacity: ...........2500 VA / 300 W maximum at 30 V DC / 250 V AC (resistive loads)
1250 VA / 220 W maximum at 30 V DC / 250 V AC (inductive loads, PF = 0.4)
Configuration: ......................SPST-NO, form-A
Contact material:................silver alloy (AgCdO)
Minimum permissible load: 5 V DC, 10 mA minimum
AUXILIARY 1 AND 2 OUTPUT RELAYS
Operating current:..............8 A maximum
Operating voltage: .............380 V AC / 125 V DC maximum
Make/carry: ...........................8 A continuous at 30 V DC / 250 V AC (resistive loads)
3.5 A continuous at 30 V DC / 250 V AC (inductive loads, PF = 0.4)
Switching capacity: ...........2000 VA / 240 W maximum at 30 V DC / 250 V AC (resistive loads)
875 VA / 170 W maximum at 30 V DC / 250 V AC (inductive loads, PF = 0.4)
Configuration: ......................SPST-NO + SPST-NC, form-C
Contact material:................silver alloy (AgCdO)
Minimum permissible load: 5 V DC, 10 mA minimum
PORTS
Type: ........................................RS485 2-wire, half duplex
Baud rate: .............................1200 bps to 57 kbps
Protocol: .................................Modbus RTU
Functions: ..............................read/write setpoints, read coil status, read actual values, read device status,
execute commands, loopback test
TYPE TESTS
Transients:..............................ANSI/IEEE C37.90.1 Oscillatory/Fast Risetime Transients
IEC 801-4 Electrical Fast Transient/Burst Requirements
Impulse: ..................................IEC 255-5 5 kV Impulse Voltage Test
RFI: ............................................150 MHz, 450 MHz 5W Handheld Transmitter at 25 cm
Static: ......................................IEC 801-2 Electrostatic Discharge
HIPOT: ......................................60255.5 Dielectric Strength: 2.3kV AC for 1 minute
PRODUCTION TEST
HIPOT: ......................................2.1kV AC for 1 second
CERTIFICATION/COMPLIANCE
UL:..............................................UL Listed (File E83849)
UL 508 - Industrial Control Equipment
UL 1053 - Ground Fault Protection Equipment
CSA: ...........................................Certified per C22.2 No. 14 - Industrial Control Equipment
CE: ..............................................IEC 947-1, IEC 1010-1
ISO: ............................................registered to ISO 9001-1994
ENVIRONMENT
Pollution degree: .................2