Under /Overvoltage Protection - GE Multilin MM3 Motor Manager 3 Instruction Manual

Hide thumbs Also See for Multilin MM3 Motor Manager 3:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS
5.3.5
Under/
Overvoltage
Protection
] UNDER/OVERVOLTAGE
] PROTECTION
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
PATH: S2 PROTECTION
The undervoltage and overvoltage settings are available only if the
setting is not "OFF". These setpoints are programmed as follows:
UNDERVOLTAGE ALARM LEVEL: This feature functions the same as the undervoltage
trip feature but produces an alarm indication instead of a trip.
UNDERVOLTAGE ALARM DELAY: Enter the delay for activation of the undervoltage
alarm.
UNDERVOLTAGE TRIP LEVEL: If the voltage remains below this value while the motor
is running for the time specified in the
Manager 3 will trip. Set this value to "OFF" if no undervoltage trip is required.
UNDERVOLTAGE TRIP DELAY: Set the
prevent nuisance trips from momentary voltage dips when the undervoltage trip
feature is used.
OVERVOLTAGE ALARM LEVEL: This feature functions the same as the overvoltage trip
feature but produces an alarm indication instead of a trip.
OVERVOLTAGE ALARM DELAY: Enter the delay for activation of the overvoltage alarm.
OVERVOLTAGE TRIP LEVEL: If the voltage remains above this value while the motor is
running for the time specified in the
Manager 3 will trip. Set this value to "OFF" if no overvoltage trip is required.
OVERVOLTAGE TRIP DELAY: Program this setpoint large enough to prevent nuisance
trips from momentary voltage dips when the undervoltage trip feature is used.
UNDER/OVERVOLTAGE PROTECTION
UNDERVOLTAGE ALARM
LEVEL:
OFF V
UNDERVOLTAGE ALARM
DELAY: 10 s
UNDERVOLTAGE TRIP
LEVEL:
OFF V
UNDERVOLTAGE TRIP
DELAY: 10 s
OVERVOLTAGE ALARM
LEVEL:
OFF V
OVERVOLTAGE ALARM
DELAY:
10 s
OVERVOLTAGE TRIP
LEVEL:
OFF V
OVERVOLTAGE TRIP
DELAY:
10 s
UNDERVOLTAGE TRIP DELAY
UNDERVOLTAGE TRIP DELAY
OVERVOLTAGE TRIP DELAY
S2 PROTECTION
Range:
0 to 690 V or OFF in steps of 1
Range:
1 to 60 s in steps of 1
Range:
0 to 690 V or OFF in steps of 1
Range:
1 to 60 s in steps of 1
Range:
0 to 690 V or OFF in steps of 1
Range:
1 to 60 s in steps of 1
Range:
0 to 690 V or OFF in steps of 1
Range:
1 to 60 s in steps of 1
VT PRIMARY VOLTAGE
, the MM3 Motor
long enough to
, the MM3 Motor
5–21