MODBUS MEMORY MAP
8–48
F26: Relay/LED test data (enumeration)
Value
Description
0
Normal operation mode
1
Contactor A on
2
Contactor B on
3
Auxiliary relay 1 on
4
Auxiliary relay 2 on
5
All relays on
6
Running LED on
F27: Auto mode definition (enumeration)
Value
Description
0
Serial
1
Hard-wired
F28: Overload curve (enumeration)
Value
Description
1
Curve #1
2
Curve #2
3
Curve #3
4
Curve #4
5
Curve #5
6
Curve #6
F29: ESD indication (enumeration)
Value
Description
0
Off when healthy
1
On when healthy
F30: Normally open / normally closed indication (enumeration)
Value
Description
0
Normally open (N.O.)
1
Normally closed (N.C.)
F31: Parity (enumeration)
Value
Description
0
None
1
Even
2
Odd
F32: Contactor sequence (enumeration)
Value
Description
0
1S-2S
1
2S-1S
F33: Manufacture month/day (unsigned integer)
Value
Description
FF--
Month in hexadecimal (two most
significant bytes)
CHAPTER 8: COMMUNICATIONS
Value
Description
7
Stopped LED on
8
Tripped LED on
9
Alarm LED on
10
Auto LED on
11
Manual LED on
12
All LEDs on
Value
Description
7
Curve #7
8
Curve #8
9
NEMA class 10
10
NEMA class 15
11
NEMA class 20
12
NEMA class 30
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL