Safety Characteristic Data - Pilz PSSu K F FAU B Operating Manual

Table of Contents

Advertisement

Technical details
Mechanical data
Connection type
Mounting type
Conductor cross section with
spring-loaded terminals: Flexible
with/without crimp connector
Spring-loaded terminals: Terminal
points per connection
Stripping length with spring-loaded
terminals
Dimensions
Height
Width
Depth
Depth incl. connector (accessor-
ies)
Weight
Where standards are undated, the 2014-04 latest editions shall apply.
9.1

Safety characteristic data

Unit
Operating
mode
Logic
Logic
Input
Digital inputs
1-channel
Digital inputs
2-channel
Digital inputs
1-ch., pulsed
light barrier
Output
SC outputs (1-
pole)
1-channel
SC outputs (1-
pole)
2-channel
SC outputs (2-
pole)
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
312420
Connector strip
plug-in
0,2 - 1 mm², 22 - 18 AWG
1
8 mm
128,9 mm
56 mm
56 mm
72 mm
200 g
NOTICE
You must comply with the safety characteristic data in order to achieve the
required safety level for your plant/machine.
EN ISO
EN ISO
13849-1: 2015
13849-1: 2015
PL
Category
PL e
Cat. 4
PL d
Cat. 2
PL e
Cat. 4
PL e
Cat. 4
PL d
Cat. 2
PL e
Cat. 4
PL e
Cat. 4
312421
Connector strip
plug-in
0,2 - 1 mm², 22 - 18 AWG
1
8 mm
128,9 mm
56 mm
56 mm
72 mm
200 g
EN 62061
EN 62061
SIL CL
PFH
[1/h]
D
SIL CL 3
4,32E-10
SIL CL 2
1,59E-08
SIL CL 3
3,61E-10
SIL CL 3
1,59E-09
SIL CL 2
1,14E-08
SIL CL 3
2,50E-10
SIL CL 3
2,39E-10
EN ISO
13849-1: 2015
T
[year]
M
20
20
20
20
20
20
20
| 68