Wiring

7
Wiring
7.1

General wiring guidelines

Please note:
}
The sensors and actuators may be connected using unshielded cables.
}
The outputs do not need suppression for inductive loads.
}
Use copper wiring
}
Use Pilz pre-assembled cable to connect the module to the receiver
}
Use shielded cables to connect the module to the transmitter. The shield should be con-
nected to a shielded terminal in the control cabinet.
7.2

Connectors' mechanical connection

Please note:
}
The conductor cross section on the spring-loaded terminals without ferrules is 0,2 - 1
mm², 22 - 18 AWG.
}
If you are using multi-core or fine-core cables we recommend ferrules in accordance with
DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm
mend crimping pliers (crimp form A) conforming to EN 60947-1, such as the PZ 6/5 from
Weidmüller, for example.
}
Terminal points per connection: 1
}
Stripping length: 8 mm
7.3

Connect/disconnect the cables

We recommend you use a screw driver with a 0.4 x 2.5 mm (DIN 5264) blade!
Strip the cable:
}
Strip the cable [1] and apply a ferrule if necessary (DIN 46228/Part 1 or DIN 46228/Part
4).
Connect cable:
}
Using the screwdriver, press the actuator button on the spring-loaded terminal down as
far as it will go [2], keep it held down and insert the stripped cable into the plug connec-
tion as far as it will go [2].
}
Check that the cable is firmly seated [3].
Disconnect cable:
}
Using the screwdriver, press the actuator button down as far as it will go [4], keep it held
down and pull the cable out of the plug connection [4].
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
2
. To crimp the ferrules we recom-
| 53