Pilz PSSu K F FAU B Operating Manual page 22

Table of Contents

Advertisement

Function description
}
Receiver position
}
IP address (default IP address: 169.254.1.2)
Further information is available in PAS4000's online help.
The input filter time can be configured in increments of 100 µs. The input filter time de-
pends on the edge configured for fast shutdown. For each input filter time that is con-
figured, there are two values each for the rising and the falling edge:
}
Safely filtered out; indicates which signals are safely filtered out.
}
Safely detected; indicates which signals are safely detected.
Configured in-
put filter time
(FZ)
200
300
400
500
...
...
...
3100
3200
3300
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
INFORMATION
If the input filter times are short, the module's electromagnetic immunity to-
wards electromagnetic faults will deteriorate.
NOTICE
Signal times are only guaranteed if input pairs (I00 and I01, I02 and I03) are
used.
Fast shutdown with rising edge
Safely filtered
out signal time
(µs)
13
30
130
230
FZ - 270
...
...
2830
2930
3030
Fast shutdown with falling edge
Safely detected
Safely filtered
signal time (µs)
out signal time
(µs)
100
10
200
110
300
210
400
310
FZ -100
FZ - 190
...
...
...
...
3000
2910
3100
3010
3200
3110
Safely detected
signal time (µs)
200
300
400
500
FZ
...
...
3100
3200
3300
| 22