Pilz PSSu K F FAU B Operating Manual page 55

Table of Contents

Advertisement

Wiring
Pin assignment of connector with spring-loaded terminals (1-row/10-pin):
PSSu A Con 1/10 C
X21:
n.c.: not connected
I 00: Input 0
I 01: Input 1
I 02: Input 2
I 03: Input 3
T 00: Test pulse output T0
or +24 V output (periphery supply)
T 00: Test pulse output T0
or +24 V output (periphery supply)
T 01: Test pulse output T1
or +24 V output (periphery supply)
T 01: Test pulse output T1
or +24 V output (periphery supply)
0 V: 0 V (periphery supply)
X22:
24 V: +24 V (external periphery supply)
O 02: Output 1, single-pole
O 02: Output 1, single-pole
O 03: Output 2, single-pole
O 03: Output 2, single-pole
0 V: 0 V (periphery supply)
0 V: 0 V (periphery supply)
0 V: 0 V (periphery supply)
0 V: 0 V (periphery supply)
0 V: 0 V (external periphery supply)
Pin assignment of connector with spring-loaded terminals (1-row/4-pin):
PSSu A Con 1/4 C
X34:
24 V: +24 V (transmitter's supply voltage)
ESY: Signal to control the transmitter's light source
EON: Signal to switch the transmitter's light source on and
off
0 V: 0 V (periphery supply)
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
X21
NC
1
I00
I01
I02
I03
T 00
T00
T01
T01
10
0 V<
1
10
X34
1
ESY
EON
4
| 55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pssu k f fau p312421312420

Table of Contents