  • Page 1 PSSu E PD(-T) Decentralised system PSSuniversal I/O Operating instructions 21304-EN-04...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Changing an electronic module during operation Section 6 Wiring General wiring guidelines 6.1.1 Mechanical connection of the base modules Terminal configuration Section 7 Operation Messages Display elements 7.2.1 Display elements for module diagnostics Section 8 Technical details Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 4 Contents Section 9 Order reference Product Accessories Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 5: Introduction

    Introduction Validity of documentation This documentation is valid for the products PSSu E PD and PSSu E PD-T. It is valid until new documentation is published. The module PSSu E PD-T is suitable for use where there are increased environmental re- quirements (see Technical Details).
  • Page 6 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 7: Overview

    The module routes the periphery supply from the module bus to the base module ter- minals. LED for: – Periphery supply Application range depends on the base module T-type: PSSu E PD-T: for increased environmental requirements Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 8: Front View

    2D code 3: Labelling strip for the terminal configuration on the base module 4: Name of electronic module 5: Connection level 1 6: Connection level 2 7: Connection level 3 8: Connection level 4 Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 9 10: Round connection holes (connection levels 1, 2, 3 and 4) for connecting the signal lines 11: Mounting slot for colour marker to label the connection level (connection levels 1, 2, 3 and 4) Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 10: Safety

    The module may be used for additional connections to the periphery supply. The periphery supply can be drawn from the connections, but may not be fed through that route. The module PSSu E PD-T is suitable for use where there are increased environmental re- quirements (see Technical Details).
  • Page 11: Safety Regulations

    In safety-related applications, please comply with the mission time T in the safety-re- lated characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 12: Function Description

    The module does not have to be configuriert. Status information is not available in the pro- cess image. 4.3.1 Addresses in the process image The module does not occupy any addresses in the process image. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 13: Installation

    5.1.1 Dimensions Base modules with four connection levels: 12,6 mm 8,1 mm 52,1 mm (0.496") (0.319") (2.051") 12,6 mm 72,6 mm (0.496") (2.858") Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 14: Installing The Base Module

    Push the base module back [2] until you hear it lock into position. On the mounting rail, slide the base module to the left until you hear the two lateral mounting hooks on the adjacent module lock into position [3]. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 15: Inserting And Removing An Electronic Module

    This is how the base module is coded. The mechanics of the electronic modules are designed for 50 plug in/out cycles. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 16: Inserting An Electronic Module

    Installation 5.3.1 Inserting an electronic module Procedure: The electronic module must audibly lock into position [1]. Mark the electronic module using the labelling strips [2]. Schematic representation: Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 17: Removing An Electronic Module

    All FS hardware outputs on the PSSu system switch to a safe condition. – The substitute values are used for the modules' FS outputs, with Valid Bits = FALSE. CAUTION! Sparking can cause interference and errors! Only change the module when the load is switched off! Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 18: Wiring

    Insert the screwdriver [4] into the square hole [1]. – Insert the stripped cable into the round fixing hole [2], as far as it will go [5]. – Pull out the screwdriver [6]. – Check that the cable is firmly seated. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 19 To crimp the ferrules you can use crimp pliers (crimp form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from Weidmüller, for example. – Maximum torque setting: 0.8 Nm Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 20: Terminal Configuration

    12 -22: 0 V periphery supply PSSu BP-C 1/8 C-T (12-22 linked within the base mod- ule) 13 -23: C-rail supply (13-23 linked within the base mod- ule) 14 -24: +24 V periphery supply (14-24 linked internally) Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 21 14 -24: +24 V periphery supply (14-24 linked internally) 15 -25: 0 V periphery supply (15-25 linked within the base mod- ule) 16 -26: C-rail supply (16-26 linked within the base mod- ule) Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 22: Operation

    Description Colour Status 24 V - - - Periphery sup- ply: No supply voltage or er- ror in the sup- ply voltage green Periphery sup- ply is error- free Polarity of the periphery sup- Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 23: Technical Details

    93 % r. h. at 40 °C Condensation during operation Not permitted Short-term EN 61000-4-2, EN 61000-4-3, EN EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-6-2, EN 61000-4-6 61000-6-4 Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 24 76,0 mm Width 12,6 mm 12,6 mm Depth 60,2 mm 60,2 mm Weight 28 g 28 g Mechanical coding Type Colour Light grey Light grey Where standards are undated, the 2015-03 latest editions shall apply. Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 25: Order Reference

    PSSu BP-C1 1/12 S-T Base module with C-rail and screw terminals, T-type 314 622 PSSu BP-C1 1/12 C Base module with C-rail and cage clamp terminals 312 623 PSSu BP-C1 1/12 C- Base module with C-rail and cage clamp terminals, T-type 314 623 Operating instructions PSSu E PD(-T) 21304-EN-04...
  • Page 26 Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95446300 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...