Function description
Fig.: On test for dual-pole outputs
Legend
Fig.: Off test for dual-pole outputs
Legend
Fig.: Discharge voltage test
Legend
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
t 2
t 1
t 1
t
Max. pulse duration of on test (4 ms)
1
t
Max. waiting time between the on tests (approx. 4 ms)
2
t
Repetition time of on test in normal circumstances (approx. 2 s)
3
t 3
t
Pulse length of off test (0.2 ms)
1
t
Max. waiting time between the off tests (approx. 4 ms)
2
t
Repetition time of off test in normal circumstances (approx. 2 s)
3
t 1 (2 min)
[1]
[1] Start of off test for dual-pole outputs
t1 Waiting time between discharge voltage tests (2 min)
t2 Pulse duration of discharge voltage test (approx. 0.3 ms)
t 3
t 3
t 1
t 2
t 1