Status displays and diagnostic messages

Structure of the diagnosis telegram

DP standard diagnosis
Byte 0
...
Byte 5
Channel specific diagnosis
Byte 0
Byte 1
Byte 2
Device specific diagnosis, IOLMM-diagnosis
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Device specific diagnosis, event-diagnosis
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
D301171 - IO-Link master 1108
Header
0×80
Channel
0xC0 + IO-Link-port
Type
DP error code
Header
0×05
Type
0×A0
Slot
0x01
Specifier
0×00
Data_byte0
diagnostic message
Header
0x08
Type
0x81
Slot
0x01
Specifier
0×00
Data_byte0
IOL_EventQualifier
Data_byte1
IOL_ChannelNumber
Data_byte2
IOL_EventCodeLow
Data_byte3
IOL_EventCodeHigh
Number of the IO-Link channel
which sends the diagnostic
message
(see
Table
10:)
Length of the diagnostic
message
Manufacturer specific
Slot of the IO-Link master
module (IOLMM)
Bit 0: UB_TOO_LOW
Bit 1: UB_TOO_HIGH
Bit 2: UL_TOO_LOW
Bit 3: UL_TOO_HIGH
Bit 4...7: reserved
Length
Status message
Slot of the IO-Link master
module (IOLMM)
Events acc. to IO-Link specifi-
cation (see
"IO-Link
events")
3
3-13