Technical features
Supported devices
Frame type
Transmission rate
Transmission physics
Communication modes
Communication
Supply of sensor
R
(Input resistance (burden))
ON
I
(output current)
A
I
AMAX
Isolation voltages
U
(PROFIBUS/ power supply)
TDP
U
TIOLDP
U
(IO-Link-Port/ IO-Link-port)
TIIOL
U
(IO-Link-Port/ power supply)
TIOL
Ambient temperature
t
Ambient
t
Store
relative humidity acc. to
EN 61131-2/EN 50178
Climatic tests
Noxious gas
Vibration resistance
10 to 57 Hz,
constant amplitude 0,075 mm, 1 g
57 to 150 Hz,
constant acceleration 1 g
Vibration mode
Vibration duration
Shock resistance acc. to IEC 68-2-27
Repetitive shock resistance acc. to
IEC 68-2-29,
3-4
(PROFIBUS/ IO-Link-port)
max. 32 byte input / 32 byte output
supports all specified frame types
4.8 kBaud (COM 1) / 38.4 kBaud (COM 2)
corresponds to 3-wire physics (PHY2)
SDPU via function block and FDT/DTM
supports IO-Link specification V1.0
190 mΩ
0.5 A
0.6 A, acc. to IEC 6 11 31-2
1000 V DC
1000 V DC
0 V DC
0 V DC
0 to +55 °C
- 25 to + 70 °C
5 to 95 % (indoor), no condensation (at 45 °C
storage temperature, no functional tests)
acc. to IEC 61131-2
2
– SO
: 10 ppm (rel. humidity < 75 %, no
condensation)
– H
S: 1,0 ppm (rel. humidity < 75 %, no
2
condensation)
yes
yes
frequency cycles with a change rate of
1 octave/min
20 frequency cycles per coordinate axis
18 shocks, semi-sinusoidal 15 g threshold/11
ms, each in ±-direction per space coordinate
1000 shocks, semi-sinusoidal 25 g threshold/
6 ms, each in ±-direction per space coordinate
D301171 - IO-Link master 1108
Need help?