This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Other documents The following additional documents are available online at www.turck.com: Data sheet TBEN-Accessories list (D301367) Operating instructions TBEN-S2-4IOL (D301369)
CAD files in numerous export formats. The contact details of Turck subsidiaries worldwide can be found on p. [} 242]. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
4.1.1 Display elements The device has the following LED indicators: Power supply Group and bus errors Status Diagnostics Properties and features Fibre-glass reinforced housing Shock and vibration tested Fully potted module electronics Protection class IP65/IP67/IP69K Multiprotocol functionality: PROFINET IO Device, EtherNet/IP Device or Modbus TCP-Slave 4-pin M8-connectors for voltage supply Tw 4-pin M8 connectors for the connection to Ethernet Digital modules with up to 8 digital in-/outputs...
4.3.2 Digital modules – extended digital functions In PROFINET, the extended digital functions are configured via device parameterization via GSDML file. In EtherNet/IP, the functions are provided in special catalog files for RSLogix from Rockwell Automation. In Modbus TCP the extended functions are configured via Modbus re- gisters.
IP address. Detailed information about BEEP can be found in the document "BEEP – Backplane Ethernet Ex- tension Protocol” 100002454. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
SPS/HMI/Service/Engineering 24 VDC Ethernet Fig. 7: Network structure, example 3 4.4.1 Ethernet daisy chain - max. number of connected modules Prerequisites: Optimized network: only TBEN-S-modules in the daisy chain, no additional switches, no third-party devices exchange of pure process data, no acyclic data Cycle time Maximum number TBEN-S modules 1 ms...
Accessories for mounting, connecting and parameterizing can be found in product database or the accessories list for TBEN (D301367) under www.turck.com. The accessories are not part of the scope of delivery. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Mounting The device can be mounted on a DIN rail according to EN 60715 (TS35) or screwed onto an even mounting plate. Both composite and individual assembly are possible. Mounting the device in Zone 2 and Zone 22 DANGER Explosive atmosphere Risk of explosion through spark ignition When used in Zone 2 and Zone 22: ...
Attach TBEN-S modules to a mounting plate Fasten the module or module composite to a mounting plate with two M4 screws per device. The maximum tightening torque for the M4 screws is 1.3 Nm Avoid mechanical stresses. Optional: Ground the device.
5.6.2 Fieldbus and I/O level shielding The fieldbus and the I/O level of the TBEN-S modules can be grounded separately. Fig. 22: Fieldbus and I/O level shielding The grounding ring (2) and the grounding contact (4) are connected to each other and form the module grounding.
With mounted grounding clip: The shielding of the fieldbus is connected to the reference potential of the installation via the module grounding of the I/O level. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
5.6.5 Grounding the device – mounting on a mounting plate For mounting onto a mounting plate: Fix the TBEN-S module with an M4 metal screw through the lower mounting hole. The shielding of the M8 flanges for the I/O level is connected to the reference potential of the installation via the M4 metal screw.
6.2.1 QuickConnect and Fast Start-Up applications Do not use crossover cables in QuickConnect and Fast StartUp applications. Connect incoming Ethernet cables to P1. Connect outgoing Ethernet cables to P2. Connecting the supply voltage The device is provided with two 4-pin M8 plug connectors for connecting the power supply. V1 and V2 are galvanically isolated.
4 BK ( ) 1 BN (+) C0...C7 With 3-wire connection, the actuator is sup- plied via pin 1 but is not switched. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 31
TBEN-S1-4DIP-4DOP Inputs 3 BU GND 4 BK ( ) 1 = V AUX1 3 = GND V1 4 = Signal In 1 BN (+) C0…C3 C0...C3 Outputs 2-wire connection: 1 = V AUX2 3 BU GND 3 = GND V2 4 = Signal Out 4 BK ( ) C4…C7...
Page 32
2 = Signal In/Out 3 = GND V2 4 = Signal In/Out 5 = FE C2...C3 Supply VAUX (pin1), switchable per connector Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Connecting analog sensors and actuators The devices provide 5-pin M12 connectors for connecting analog sensors and actuators. Fig. 42: M12 connector for connecting analog sensors and actuators Connect the sensors and actuators to the device according to the pin assignment. ...
Page 34
NOTE The 2 wire and 3 wire connection are only possible in the single ended voltage or current measurement mode. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 35
TBEN-S2-4AI – thermocouple NOTICE Wrong channel parameterization (operation mode) Possible destruction of thermo couples Please observe correct channel parameterization. Do not connect thermo couples to channels which are parameterized as voltage or respectively current input. Connect the analog sensors and actuators to the device according to the pin assignment. ...
Page 36
2 = AO + 3 = GND V2 4 = AO –/GND V2 5 = FE Flange = FE C0...C3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
The device is factory set to IP address 192.168.1.254 and does not have a PROFINET device name. The IP address can be set via the Turck Service Tool, the DTM, the web server, a DHCP server or PROFINET DCP. The following example shows the setting of the IP address via the Turck Service Tool.
Page 38
Change the IP address and if necessary the network mask and gateway. Accept the changes by clicking Set in device. Fig. 46: Turck Service Tool – Change device configuration Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Parameterizing and Configuring Parameters – overview 8.1.1 I/O channel parameters Parameters – Digital Modules Default values are shown in bold. Parameter name Value Meaning Description Dec. Hex. DMOD Extended digital Activates or deactivates the ex- 0x00 disabled function tended functions (input filter, im- 0x01 Input filter and pulse pulse stretch, counter or PWM...
Page 40
Pt500, -200…850 °C, -328…1562 °F 0x07 Pt500, -200…150 °C, -328…302 °F 0x08 Pt1000, -200…850 °C, -328…1562 °F 0x09 Pt1000, -200…150 °C, -328…302 °F Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 41
Parameter name Value Meaning Description Dec. Hex. 0x0A Ni1000, -60…250 °C, -76…482 °F 0x0B Ni1000, -60…150 °C, -76…302 °F RTDW RTD wiring type 0x00 2-wire 0x01 3-wire 0x02 4-wire RWT Resistance wiring 0x00 2-wire type 0x01 3-wire 0x02 4-wire Mains suppression 0 0x00 0x01 50 Hz...
Page 42
Set the measurement range of the voltage out- 0x01 0…10 V put. 0x02 2…10 V 0x03 0…5 V 0x04 1…5 V Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.1.2 PROFINET parameters For PROFINET, a distinction must be made in the parameters between the PROFINET device parameters and the parameters of the I/O channels Parameters_TBEN_S2-4IOL . PROFINET device parameters Default values are shown in bold. Parameter name Value Meaning Description Output behavior at set to 0...
Counter value MSB Frequency Ch0 0x0005 Frequency MSB Frequency LSB Status 0x0006 Module status 0x0007 FCE - COM V1 ARGEE Diag Warn Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 45
TBEN-S1-8DIP-D Word no. Bit no. Inputs 0x0000 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 Diagnostics 0x0001 VERR VERR VERR VERR VERR VERR VERR VERR Latch input 0x0002 Counter Ch0 0x0003 Counter value LSB 0x0004 Counter value MSB Frequency Ch0 0x0005 Frequency MSB Frequency LSB...
Page 46
Frequency LSB Status 0x0006 PWM Diagnostics Ch7 0x0007 PWM OUT ERR Module status 0x0008 FCE - COM V1 ARGEE Diag Warn Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 47
TBEN-S1-4DXP Word no. Bit no. Inputs 0x0000 C3P4 C2P4 C1P4 C0P4 Diagnostics 0x0001 ERR3 ERR2 ERR1 ERR0 - VERR VERR Ch2-3 Ch0-1 Latch input 0x0002 DX3 DX2 DX1 Counter Ch0 0x0003 Counter value LSB 0x0004 Counter value MSB Frequency Ch0 0x0005 Frequency MSB Frequency LSB...
Page 48
PWM OUT ERR PWM Diagnostics Ch7 0x0008 PWM OUT ERR Module status 0x0009 FCE - COM V1 ARGEE Diag Warn Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 50
Diagnostic message at the device Force Mode activated System power supply too low (< 18 VDC). V2 too low (< 18 VDC). Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.2.2 Process input data – analog modules TBEN-S2-4AI Word no. Bit no. Inputs 0x0000 Analog value channel 0 0x0001 Analog value channel 1 0x0002 Analog value channel 2 0x0003 Analog value channel 3 Diagnostics 0x0004 Channel 1 Channel 0 LLVU UFL OFL WBR V1 ULVE RTDSC CJE LLVU UFL OFL WBR V1 ULVE RTDSC CJE...
Page 52
Diagnostic message at the device Force Mode activated System power supply too low (< 18 VDC). V2 too low (< 18 VDC). Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Process output data – overview 8.3.1 Process output data – digital modules TBEN-S1-8DIP Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 CNT_ Reset TBEN-S1-8DIP-D Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 CNT_ Reset TBEN-S2-8DIP-D...
Page 54
Word no. Bit no. Control 0x0000 Outputs 0x0001 Latch reset 0x0002 Counter reset 0x0003 CNT_ Reset PWM Ch3 0x0004 Duty Cycle Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 55
TBEN-S1-8DXP Word no. Bit no. Control 0x0000 Outputs 0x0001 DX7 DX6 DX5 DX4 DX3 Latch reset 0x0002 DX7 DX6 DX5 DX4 DX3 Counter reset 0x0003 CNT_ Reset PWM ch3 0x0004 Duty Cycle PWM ch7 0x0005 Duty Cycle TBEN-S2-8DXP Word no. Bit no.
0x0001 Analog value channel 0 0x0002 Analog value channel 1 0x0003 Analog value channel 2 0x0004 Analog value channel 3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Configuring devices at PROFINET 8.4.1 PROFINET IO device model The technical properties of PROFINET IO devices are defined via their device description file, the GSDML file. A PROFINET IO device consists of 1…n slots, which can also contain 1…n sub slots. Sub slots are placeholders for sub modules and establish the interface to the process.
For the correct cabling in FSU applications please observe the note in the chapter "Connecting the Power supply” [} 27] . Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 59
Fast Start-Up TBEN-S Turck TBEN-S devices support the prioritized start-up (FSU). In order to enable FSU, the field bus nodes have to be configured respectively for example in TIA-Portal (Siemens). Autonegotiation: deactivated Transmission medium/duplex: set to a fixed value ...
Page 60
Configuring devices at PROFINET Activate the prioritized start-up at the I/O device. Fig. 49: TIA-Portal – prioritized start-up, activation at the I/O device Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
(slot 0) 0x03 Module revision STRING read Firmware revision of the module 0x04 Vendor ID WORD read Ident no. Turck 0x05 Module name STRING read The device name assigned to the module 0x06 Module type STRING read Device type of the module...
Page 62
Version number of the Version slave controller. 11…18 0x0B… reserved 0x12 0x13 Input data specific read Input data of the respective I/O-channel Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 63
Index Name Data Type Access Comment 20…22 0x14 … reserved 0x16 0x17 Output data specific read/ Output data of the respect- write ive I/O-channel … … reserved V04.00 | 2021/05...
The GSDML file can be downloaded for free from www.turck.com Ò Adding the GSDML-file: Click Options Manage general station description files (GSD). Fig. 50: Adding the GSDML-file Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 65
Installing the GSDML-file: Define the storage location of the GSDML file and click Install. The device is added to the Hardware catalog of the programming software. Fig. 51: Installing the GSDML-file V04.00 | 2021/05...
Connect the devices to the PLC in the "Devices & networks" editor. Fig. 52: Connecting the device to the PLC Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.5.3 Configuring device functions Ò Select Device view Device overview. Select functions as operation mode, diagnostics etc. from the hardware catalog and add them to the devoce slots via drag&drop. Fig. 53: Configuring the device slots V04.00 | 2021/05...
Assign PROFINET device name. Assign the desired PROFINET device name with Assign name. Fig. 54: Assigning the PROFINET device name Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.5.5 Setting the IP address in TIA Portal Ò Ò Select Device view Properties Ethernet addresses. Assign the desired IP address. Fig. 55: Assigning the IP address V04.00 | 2021/05...
Select the device to be parameterized. Ò Ò Click Properties General Module parameters. Set the device parameters. Fig. 56: Setting module parameters Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.5.7 Going online with the PLC Start the online mode (Go online). The device has been successfully connected to the PLC. Fig. 57: Starting the online mode 8.5.8 PROFINET – Mapping The PROFINET mapping corresponds to the data mapping described in the sections "Evaluating Process Input Data”...
Bit 2 = PROFINET active Bit 15 = Web server active 0x2400 read only V1 in mV: 0 at < 18 V Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 73
Address Access Meaning 0x2401 read only V2 in mV: 0 at < 18 V 0x8000…0x8FFF read only Process data of the inputs (identical to registers 0x0000…0x01FF) 0x9000…0x9FFF read/write Process data of the outputs (identical to registers 0x0800…0x09FF) 0xA000…0xAFFF read only Diagnostics 0xB000…0xBFFF read/write...
Page 74
0x113D. Both registers can also be written with one single request using the function codes FC16 and FC23. The parameters are reset tot default values. Save changes via a subsequent Save service. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Register 0x113E and 0x113F: Save Modbus connection parameters Registers 0x113E and 0x113F are used for the non-volatile saving of parameters in registers 0x1120 and 0x1130 to 0x113B. Procedure: Write 0x7361 to register 0×113E. Write 0x7665 ("save") within 30 seconds in register 0x113F to activate the reset of the re- gisters.
TBEN-S1-8DIP – output registers Meaning of the process output data [} 53] Register no. Bit no. Latch reset 0x0800 Counter reset 0x0801 reset Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 77
TBEN-S1-8DIP – parameter registers Parameter description [} 39] Register no. Bit no. Channel 0 0xB000 IST DI0 DIFT DI0 DMOD_CNT DI0 Channel 1 0xB001 IST DI1 DIFT DI1 DMOD DI1 … Channel 7 0xB007 IST DI7 DIFT DI7 DMOD DI7 TBEN-S1-8DIP-D – input registers Meaning of the process input data [} 44] Register no.
Page 78
DIFT DI0 DMOD_CNT DI0 Channel 1 0xB001 IST DI1 DIFT DI1 DMOD DI1 … Channel 7 0xB007 IST DI7 DIFT DI7 DMOD DI7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 79
TBEN-S2-8DIP – input registers Meaning of the process input data [} 44] Register no. Bit no. 0x0000 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 Diagn. 0x0001 VERR VERR VERR VERR Latch IN 0x0002 CNT Ch0 0x0003 Counter value LSB 0x0004 Counter value MSB Freq.
Page 91
TBEN-S2-4AO – input registers Meaning of the process input data [} 51] Register Bit no. Diagnostics Channel 1 Channel 0 0x0000 WBR OVL - Channel 3 Channel 2 0x0001 WBR OVL - Module status 0x0002 COM V1 ARGEE Diag Warn TBEN-S2-4AO – output registers Meaning of the process output data [} 56] Register Bit no.
System power supply too low (< 18 VDC). Channel diagnostics Cold junction error Overcurrent at the respective output LLVU Lower limit value underrun Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 93
Designation Meaning Overflow Overload/overcurrent RTDSC Overcurrent (RTD only) Underflow ULVE Upper limit value exceeded V1AOL Overcurrent VAUX1 Wire break Parameters The chapter Parameterizing and Configuring [} 39] contains a detailed parameter description. Digital modules DMOD Extended digital function DMOD_CNT Extended digital function counter DMOD_PWM Extended digital function PWM EN_DO...
"0" after the watchdog time has expired, unless another protocol (PROFINET, Eth- erNet/IP) has been activated in the meantime. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Turck-HMI TX507-P3CV01 (Modbus TCP Master, IP address: 192.168.1.15) Block module TBEN-S1-4DIP-4DOP (IP address: 192,168,201) Used software The following software tools are used in this example: CODESYS 3.5.8.1 (can be dwonloaded for free under www.turck.com) Prerequisites The programming software has been started. A new project has been created.
Ethernet Adapter Modbus TCP Master Modbus TCP Slave Adding the Ethernet adapter Right-click the Device (TX507-P3CV01). Fig. 58: Project tree Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 97
Select Add Device. Select the Ethernet Adapter Click Add Device. The Ethernet Adapter is added to the project tree as Ethernet (Ethernet). Fig. 59: Adding the Ethernet adapter V04.00 | 2021/05...
Page 98
Double-click Modbus TCP Master. The Modbus Master is added to the project tree as Modbus_TCP_Master. Fig. 60: Adding the Modbus master Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 99
Adding a Modbus slave Right-click the Modbus TCP Master in the project tree. Select Add Device. Double-click the Modbus TCP Slave. The Modbus Slave is added to the project tree as Modbus_TCP_Slave. Fig. 61: Adding a Modbus slave V04.00 | 2021/05...
Scan Network. Modbus Master (here: TX507-P3CV01) and confirm with OK. Fig. 62: Configuring the network interface to the Modbus master Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 101
Double-click Ethernet. Open the dialog box Network Adapter by clicking the … button in the register tab General. Select the interfac of the TX507 (here: 192.168.1.15). Fig. 63: Modbus master – selecting the interface V04.00 | 2021/05...
Enter the slave's IP address in the General register tab (here: 192.268.1.201). Fig. 64: Modbus TCP slave – configuring the IP address Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.7.5 Going online with the PLC Select the device. Ò Click Online Login. 8.7.6 Reading process data The process data can be interpreted by means of the mapping [} 76] if the device is connected to the PLC. Double-click the Modbus TCP Slave.
Full duplex Topology linear AutoMDIX disabled Please read chapter "Connecting” [} 27]. for more information about the correct Ethernet- cabling in QC-applications. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 107
Activating QuickConnect via Configuration Assembly The Configuration Assembly is part of the Assembly Class of the device. Configuring the Configuration Assembly in RSLogix. Activate QuickConnect via byte 9, bit 0 = 1 in the Controller Tags. Fig. 68: Configuring QuickConnect in RSLogix Activating Quick Connect via Class Instance Attribute ...
8.8.5 Diagnostic messages via process data Besides the evaluation of diagnostic data via Explicit Messages, TBEN-S from firmware version 3.1.4.0 (digital modules) and Firmware-Version 3.1.2.0 (analog modules) with EtherNet/ IP offer the possibility of mapping diagnostic data into the process data. The diagnostic messages are directly mapped into the process data.
= 0 Configured TRUE = 1: The application in the device has been con- figured (default setting). reserved default = 0 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 111
The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 2.1 by ODVA & ControlNet International Ltd. and adapted to the Turck products. Class attributes Attr. no.
Page 112
The port is set to autonegotiation. 100BT/FD Defined setting of communication paramet- ers for the Ethernet port to: 100BaseT Full duplex Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 119
Configuration Assembly – TBEN-S2-4AI Byte no. Bit no. Dec. Hex. Device Configuration Data [} 112] 0…9 0x00… Eth2 Port- Eth1 Port- Quick 0x09 Setup Setup Connect Parameter data [} 39] Channel 0 0x0A Operation mode 0x0B Thermocouple type 0x0C Thermocouple cold junction compensation 0x0D Voltage range 0x0E...
Page 120
Assignment similar to channel 0 (byte 10…19) 0x27 Channel 3 40…49 0x28… Assignment similar to channel 0 (byte 10…19) 0x31 Channel 50…52 0x32… reserved 0x33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 121
Process data instances Instance 101 Contains the device input data (static length 256 byte) 2 byte status informationen [} 109] + process data Instance 102 Contains the device output data (static length 256 byte) 2 byte status Control word (mapped, but unused + process data Instance 103 and Instance 104 Instance 103 and Instance 104 are in- and output assembly instances with variable assembly...
Page 122
Output data – TBEN-S1-8DIP [} 53] Control word + 2 words Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 Reset Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 123
Input data – TBEN-S2-8DIP [} 44] Status word + 7 words Word no. Bit no. Status 0x0000 FCE - COM V1 ARGEE Diag Warn 0x0001 C7P4 C6P4 C5P4 C4P4 C3P4 C2P4 C1P4 C0P4 Diagn. 0x0002 VERR VERR VERR VERR V1 C3 V1 C2 V1 C1 V1 C0...
Page 124
Output data – TBEN-S1-8DIP-D [} 53] control word + 2 words Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 reset Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 125
Input data – TBEN-S1-8DOP [} 44] status word + 3 words Word no. Bit no. Status 0x0000 COM V1 ARGEE Diag Warn Diagnostics 0x0001 ERR7 ERR6 ERR5 ERR4 ERR3 ERR2 ERR1 ERR0 - VERR VERR Ch4-7 Ch0-3 diag. Ch 3 0x0002 PWM OUT ERR diag.
Page 126
0x0005 Counter value MSB Freq. Ch0 0x0006 Frequency MSB Frequency LSB Module status 0x0007 diag. Ch7 0x0008 PWM OUT ERR Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 127
Output data – TBEN-S1-4DIP-4DOP [} 53] control word + 4 words Word no. Bit no. Control 0x0000 0x0001 C7P4 C6P4 C5P4 C4P4 Latch reset 0x0002 CNT- reset 0x0003 reset PWM Ch7 0x0004 Duty Cycle V04.00 | 2021/05...
Page 131
Input data – TBEN-S2-8DXP [} 44] status word + 9 words Word no. Bit no. Status 0x0000 FCE - COM V1 ARGEE Diag Warn 0x0001 C3P2 C3P4 C2P2 C2P4 C1P2 C1P4 C0P2 C0P4 Diagn. 0x0002 ERR7 ERR6 ERR5 ERR4 ERR3 ERR2 ERR1 ERR0 - VERR VERR VERR...
Page 132
PWM Ch7 0x0005 Duty Cycle VAUX Control 0x0006 VAUX VAUX VAUX VAUX 1 P1 1 P1 1 P1 1 P1 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 133
Input data – TBEN-S2-4AI [} 51] status word + 7 words Word no. Bit no. Status 0x0000 COM V1 ARGEE Diag Warn 0x0001 Analog value channel 0 0x0002 Analog value channel 1 0x0003 Analog value channel 2 0x0004 Analog value channel 3 Diagn.
Page 134
Common services Service code Class Instance Meaning Dec. Hex. 0x54 FWD_OPEN_CMD (opens a connection) 0x4E FWD_CLOSE_CMD (closes a connection) 0x52 UNCONNECTED_SEND_CMD Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 135
TCP/IP Interface Object (0xF5) The following description of the Ethernet Link Object is taken from the CIP specification, Vol. 2, Rev. 1.1 by ODVA & ControlNet International Ltd. and adapted to the Turck products. Class attributes Attr. no. Designation Get/set...
Page 136
The device is capable of resolving host names by querying a DNS server. DHCP client This device supports network configuration via BOOTP. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 137
Configuration control The Configuration Control attribute is used to control network configuration options. Designation Meaning 0…3 Startup configuration Determines how the device shall obtain its initial config- uration. The device should use the previously stored interface configuration (for example, from non-volatile memory, set by hardware switch, etc.).
Page 138
3 = successfully negotiated speed and duplex 4 = Autonegotiation not started, yet Forced speed and duplex. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 139
Designation Meaning Default value Manual setting 0 = interface can activate changes to link paramet- requires reset ers (auto-negotiate, duplex mode, interface speed) automatically 1 = device requires a Reset service to be issued to its Identity Object in order to adapt the changes. Local Hardware 0 = interface detects no local hardware fault Fault...
TBEN-S1-8DIP-D TBEN-S1-8DXP TBEN-S2-8DIP TBEN-S2-8DXP 0xA5 Basic Data and parameters for the TBEN-S2-8DIP basic functions of 0xA8 TBEN-S2-8DXP the digital devices Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 141
Class code Name Description Applies to: Dec. Hex. 0xAA VAUX Control Parameters and diagnostics for the TBEN-S2-8DXP 24 V sensor and actuator supply. 0xAB TBEN-S2-8DIP 0xBC Basic Data and parameters for the TBEN-S1-4DXP basic functions of the digital devices V04.00 | 2021/05...
Page 142
(cannot be deactivated via the EtherNet/IP interface). Bit 1: Deactivates Modbus TCP Bit 2: Deactivates PROFINET Bit 15: Deactivates the web server Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 143
Miscellaneous Parameters Class (VSC 126) This class contains 2 instances Instance 1: Ethernet port ETH1 Instance 2: Ethernet port ETH2 Attribute no. Designation Get/set Type Meaning Dec. Hex. 0x6D Ethernet port paramet- DWORD 0: Autonegotiate, AutoMDIX 1: 10BaseT, half duplex, linear topology (AutoMDIX disabled) 2: 10BaseT, full duplex, linear to- pology (AutoMDIX disabled)
Page 144
10: Ni1000, -60…250 °C, -76…482 °F 11: Ni1000, -60…150 °C, -76…302 °F 0x0B USINT 0: 2-wire wiring type 1: 3-wire 2: 4-wire Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 145
Attribute no. Designation Get/Set Type Meaning Dec. Hex. 0x0C Data USINT 0: Standard representation 1: NE43 2: Extended range 0x0D Temperature USINT 0: Celsius unit 1: Fahrenheit 0x0E Input averaging USINT 0 = standard filter DIFT 1 = smooth 2 = fast 3: off 0x0F Deactivate...
Page 146
Substitute value to be transferred 0x0A Overload USINT 0: - 1: active 0x0B Wire break USINT 0: - 1: active 0x0C output UINT Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 147
Class 148 (0x94) – Basic This class data and parameters for the device’s basic functions. Applies to: TBEN-S1-8DIP Attribute no. Designation Get/Set Type Meaning Dec. Hex. Parameters 0x01 Diagnostics ch0…ch3 – USINT 0: - overcurrent VAUX1 1: active 0x02 Diagnostics ch4…ch7 – USINT 0: - overcurrent VAUX1...
Page 148
Manual reset after USINT 0: no overcurr. ch1 1: yes 0x03 Manual reset after USINT 0: no overcurr. ch2 1: yes Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 149
Attribute no. Designation Get/ Type Meaning Dec. Hex. 0x04 Manual reset after USINT 0: no overcurr. ch3 1: yes 0x05 Manual reset after USINT 0: no overcurr. ch4 1: yes 0x06 Manual reset after USINT 0: no overcurr. ch5 1: yes 0x07 Manual reset after overcurr USINT...
Page 150
0x10 Manual reset after overcurr. ch7 USINT 0: no 1: yes 0x11 Overcurrent VAUX1 ch0…3 USINT 0: - 1: active Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 151
Attribute no. Designation Get/ Type Meaning Dec. Hex. 0x12 Overcurrent VAUX1 ch4…7 USINT 0: - 1: active 0x13 Diagnostics ch0 – overcurrent USINT 0: - 1: active 0x14 Diagnostics ch1 – overcurrent USINT 0: - 1: active 0x15 Diagnostics ch2 - overcurrent USINT 0: - 1: active...
Page 152
Bit 0: Output value ch4 bit 1: Output value ch5 bit 2: Output value ch6 bit 3: Output value ch7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 153
Class 156 (0x9C) – Input Latch (Channel 0…3) This class contains the in- and output data for the input latch function. Applies to: TBEN-S1-4DIP-4DOP TBEN-S1-4DXP Attribute no. Designation Get/set Type Meaning Dec. Hex. Parameters 0x01 Input value ch0 – USINT 0: - Latch input 1: active...
Page 154
0x04 Counter value UDINT 0x05 Counter frequency (hz) UINT 0x06 Status USINT 0x07 Counter reset USINT 0: inactive 1: active Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 155
Class 158 (0x9E) – Ext. Function Digital This class data and parameters for the extended digital functions. Applies to: TBEN-S1-8DIP TBEN-S1-8DIP-D TBEN-S1-4DIP-4DOP TBEN-S1-4DXP TBEN-S1-8DXP TBEN-S2-8DIP TBEN-S2-8DXP Attribute no. Designation Get/ Type Meaning Dec. Hex. Parameters 0x01 Extended digital function USINT 0: deactivated 1: Input filter and pulse stretch 0x02 Input filter...
Page 156
Overcurrent PWM output USINT 0: - 1: active 0x05 Overcurrent PWM output USINT 0: - 1: active 0x06 Duty Cycle USINT Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 157
Class 162 (0xA2) – Input Latch (Channel 0…7) This class contains the in- and output data for the input latch function. Applies to: TBEN-S1-8DIP TBEN-S1-8DIP-D TBEN-S1-8DXP TBEN-S2-8DIP TBEN-S2-8DXP Attribute no. Designation Get/Set Type Meaning Dec. Hex. Parameters 0x01 Input value ch0 – USINT 0: - Latch input...
Page 158
Applies to: TBEN-S2-8DXP Attribute no. Designation Get/Set Type Meaning Dec. Hex. Parameters 0x01 Activate output ch0 USINT 0: - 1: active Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 159
Attribute no. Designation Get/Set Type Meaning Dec. Hex. 0x02 Activate output ch1 USINT 0: - 1: active 0x03 Activate output ch2 USINT 0: - 1: active 0x04 Activate output ch3 USINT 0: - 1: active 0x05 Activate output ch4 USINT 0: - 1: active 0x06...
Page 160
4: Output value ch4 bit 5: Output value ch5 bit 6: Output value ch6 bit 7: Output value ch7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 161
Class 170 (0xAA) – VAUX Control This class contains parameters for of the 24 VDC sensor/ actuator supply. Applies to: TBEN-S2-8DXP Attr. no. Designation Get/Set Type Meaning Dec. Hex. Parameters 0x01 VAUX1 pin1 C0 (Ch0/1) USINT 0: 24 VDC 1: switchable 2: off 0x02 VAUX1 pin1 C1 (Ch2/3)
Page 162
1: yes 0x02 Activate output Ch1 USINT 0: no 1: yes 0x03 Activate output Ch2 USINT 0: no 1: yes Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 163
Attr. no. Designation Get/ Type Meaning Dec. Hex. 0x04 Activate output Ch3 USINT 0: no 1: yes 0x05 Manual reset after USINT 0: no overcurr. Ch0 1: yes 0x06 Manual reset after USINT 0: no overcurr. Ch1 1: yes 0x07 Manual reset after USINT 0: no...
Adding the devices from the Catalog files to the new project Right-click the device entry and use Copy. Fig. 71: RS Logix – copying device entry from Catalog file Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 165
Right-click the EtherNet/IP-Scanner in the 2nd instance of the RS Logix and add the device to the project via Paste. Fig. 72: RS Logix - adding the device to the project V04.00 | 2021/05...
Set the IP address of the device (example: 192.168.145.181). Fig. 73: Setting module name and IP address Optional: Set the connection parameters. Fig. 74: Setting the connection parameters Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
8.9.3 Parameterizing the device Open the "Controller Tags" of the device. Parameterize the device by using the TBEN_S1_8DXP:C Controller Tags. Fig. 75: Parameterizing the Device V04.00 | 2021/05...
Select the PLC. Set the communication path via Set Project Path. The communication path is set Fig. 76: Setting the communication path Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 169
Select the PLC. Click Go online. Fig. 77: Going online with the device Click Download In the following dialog (Connect To Go Online). Confirm all following messages. The project is loaded to the PLC. The online connection is established. V04.00 | 2021/05...
The access to the parameter data (TBEN_S1_8DXP:C), input data (TBEN_S1_8DXP:I) and output data (TBEN_S1_8DXP:O) is possible. Fig. 78: "Controller Tags" in the project tree Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Operating LED displays The device has the following LED indicators: Power supply Group and bus errors Status Diagnostics 9.1.1 Module LEDs TBEN-S LED PWR Meaning No voltage connected or under voltage at V1 Green Voltage on V1 or respectively V1 and V2 OK No voltage connected or under voltage at V2 (only valid for devices with V2 power supply) LED BUS...
Evaluating diagnostic data The diagnostics of the TBEN-S devices are mapped into the process data [} 44]. 9.2.1 PROFINET diagnostics TBEN-S1-8DIP – diagnostic data mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 VERR V1 VERR V1 ch4-7...
Page 175
TBEN-S1-8DOP – diagnostic data mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 VERR V2 VERR V2 ch4-7 ch0-3 n + 1 ERR7 ERR6 ERR5 ERR4 ERR3 ERR2 ERR1 ERR0 PROFINET error codes Station diagnostics (slot 0) PROFINET diagnostics Diagnostics...
Page 176
Overcurrent supply VAUX2 at channel 4…7 VERR V2 ch4-7 0x0121 Overcurrent at output Overcurrent ERR4 0x0001 ERR5 0x0001 ERR6 0x0001 ERR7 0x0001 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 177
TBEN-S1-4DXP – diagnostic data mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 VERR V2 VERR V1 Ch2-3 K0-1 n + 1 ERR3 ERR2 ERR1 ERR0 PROFINET error codes Station diagnostics (slot 0) PROFINET diagnostics Diagnostics Error code...
Page 178
Short-circuit at output Overcurrent ERR0 0x0001 ERR1 0x0001 ERR2 0x0001 ERR3 0x0001 ERR4 0x0001 ERR5 0x0001 ERR6 0x0001 ERR7 0x0001 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 179
TBEN-S2-8DXP – diagnostic data mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 VERR V2 VERR V2 VERR V1 VERR V1 P1 ch6-7 P1 ch4-5 P1 ch2-3 P1 ch0-1 n + 1 ERR7 ERR6 ERR5...
Page 180
(ULVE) Overflow (OFL) 0x0007 Lower limit value un- 0x0008 derrun (LLVU) Underflow (UFL) 0x0008 Cold junction error 0x0019 (CJE) Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 181
TBEN-S2-4AO – diagnostic data mapping Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Channel Channel n + 1 Channel n + 2 Channel n + 3 PROFINET error codes Station diagnostics (slot 0) PROFINET diagnostics Diagnostics Error code...
0010 0000 > -0.0500 V "Lower limit value underrun" OFF 0000 > -0.10000 V "Lower limit value underrun" ON 0000 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 183
2…10 V Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. Value × 2.441 × 10 ) V + 2 V > 10.1000 V "Upper limit value exceeded” ON 32767 7FFF < 10.0500 V "Upper limit value exceeded" OFF 32767 7FFF 10.0000 V...
Page 184
> -502.5 mV "Lower limit value underrun" OFF -32768 8000 < -505.0 mV "Lower limit value underrun" ON -32768 8000 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 185
-100…100 mV Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. value × 3.0519 × 10 > 101.000 mV "Upper limit value exceeded” ON 32767 7FFF < 100.500 mV "Upper limit value exceeded" OFF 32767 7FFF 100.00 mV Nominal range 32767 7FFF 99.999 mV...
Page 186
"Lower limit value underrun" OFF > -138 > FF76 < -0.10 V "Lower limit value underrun" ON > -276 < FEEC Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 187
2…10 V Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. Value × 2.8934 × 10 ) V + 2 V > 11.41 V "Upper limit value exceeded” ON > 32527 > 7F0F < 11.28 V "Upper limit value exceeded" OFF >...
Page 188
"Lower limit value underrun" OFF > -32071 > 82B9 > -588 mV "Lower limit value underrun" ON < -32513 < 80FF Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 189
-100…100 mV Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. value × 3.6164 × 10 ) mV > 117.6 mV "Upper limit value exceeded” ON > 32519 > 7F07 < 116.0 mV "Upper limit value exceeded" OFF > 32076 <...
Page 190
> -30 > FFE2 and "Underrun" OFF < -0.05 V "Lower limit value underrun" > -50 < FFCE and "Underrun" ON Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 191
2…10 V Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. value × 10 > 11 V "Overload/Overcurrent" ON > 11000 > 2AF8 11.00 V 11000 2AF8 < 10.95 V "Overload/Overcurrent" OFF > 10950 < 2AC6 > 10.50 V "Upper limit value exceeded”...
Page 192
"Underrun" ON > -1.099 V "Underflow" OFF > -10990 > D512 < -1.100 V "Underflow" ON > -11000 < D508 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 193
-500…500 mV Diagnostics decimal hexadecimal (two's complement) Voltage value U = (dec. value × 10 )/2 V > 0.5500 mV "Overload/Overcurrent" ON > 11000 > 2AF8 < 0.5495 mV "Overload/Overcurrent" OFF > 10990 < 2AEE > 0.5250 mV "Upper limit value exceeded” ON >...
Page 194
> -164 > FF5C and "Underrun" OFF < -0.20 mA "Lower limit value underrun" < -328 < FEB8 and "Underrun" ON Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 195
4…20 mA Diagnostics decimal hexadecimal (two's complement) Current value I = (dec. value × 4.883 × 10 ) mA > 20.20 mA "Upper limit value exceeded” ON 32767 7FFF < 20.10 mA "Upper limit value exceeded" OFF 32767 7FFF 20 mA Nominal range 32767 7FFF...
Page 196
> 82B0 "Wire break" OFF < -23.519 mA "Lower limit value underrun" and > -32513 < 80FF "Wire break" ON Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 197
Current – NE43 0…20 mA Diagnostics decimal hexadecimal (two's complement) Current value I = (dec. value × 10 ) mA > 22.00 mA "Overload/Overcurrent" ON > 22000 > 55F0 < 21.80 mA "Overload/Overcurrent" OFF > 21800 > 5528 > 21.00 mA "Upper limit value exceeded”...
Page 198
< ADF8 > -21.80 mA "Underflow" OFF > -21800 > AAD8 < -22.00 mA "Underflow" ON > -22000 < AA10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 199
Resistance 0…100 Ω Diagnostics Decimal hexadecimal (two's complement) Resistance R = (dec. value × 0,0030519) Ω > 214,00 Ω "Wire break" ON 37767 7FFF > 102,00 Ω "Upper limit value exceeded” ON 37767 7FFF < 101,00 Ω "Upper limit value exceeded" OFF 37767 7FFF 100,00 Ω...
Page 200
Wire break (WBR): no Pt/Ni sensor connected, process data will be set to 0x8000. Upper limit value exceeded (ULVE) Lower limit value underrun (LLVU) Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 201
RTD (with extended temperature range) Pt100/Pt200/Pt500/Pt1000, temperature range -200…850 °C, -328…1562 °F Celsius Measured value Diagnostics Decimal hexadecimal (two's complement) > -202 °C "Lower limit value underrun" ON -2020 F81C -200 °C Nominal range -2000 F830 -135°C -1350 FABA -1 °C FFF6 0 °C 0000...
Page 202
-1 °C 0 °C 2338.15 °C 2315 °C Type G 0...2315 °C -1 °C 0 °C 2338.15 °C 2315 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 203
Thermocouple Fahrenheit Lower limit value underrun Upper limit value exceeded Type K -270…1370 °F -458.86 °F -454 °F 2522.66°F 2498 °F Type B 100...1820 °F 210.2 °F 212 °F 3340.76 °F 3308 °F Type E -270…1000 °F -458.86 °F -454 °F 1850 °F 1832 °F Type J -210...1200 °F...
… … … 0001 0.000305 V 0000 FFFF … … … -16384 C000 … … … -32767 8001 -32767 8000 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 205
Decimal hexadecimal 0…5 V (two's complement) Dec. value = 1638.35 (1/V) × U 32767 7FFF Nominal range 5.0000 V 32766 7FFE 4.9998 V … … … 16384 4000 2.5001 V … … … 0001 0.000152 V 0000 FFFF … … …...
Page 206
-27664 93F0 -10.0058 V -32512 8100 -11.759 V -32513 80FF -11.760 V -32752 80F0 -11.846 V -32767 8000 -11.852 V Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 207
Decimal hexadecimal 0…10 V (two's complement) Dec. value = 2764.8 (1/V) × U 32767 7FFF 11.851 V 32752 7FF0 11.846 V 32512 7F00 11.760 V 32511 7EFF 11.759 V 32496 7EF0 11.75 V 27664 6C10 10.0058 V 27649 6C01 10.0004 V 27648 6C00 Nominal range...
Page 209
Decimal hexadecimal 2…10 V (two's complement) Dec. value = 3456 (1/V) × U 32767 7FFF 11.4812 V 32752 7FF0 11.4769 V 32512 7F00 11.4074 V 32511 7EFF 11.4041 V 32496 7EF0 11.4028 V 27664 6C10 10.0046 V 27649 6C01 10.0003 V 27648 6C00 Nominal range...
Page 210
1.0000 V FFFF -162 FFF0 -6912 E500 -27648 9400 -27649 93FF -27664 93F0 -32512 8100 -32513 80FF -32752 80F0 -32767 8000 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 211
Voltage – NE43 Decimal hexadecimal -10…10 V (two's complement) Dec. value = 2764.8 (1/V) × U 32767 7FFF 11.00 V 11001 2AF9 11.000 V 11000 2AF8 11.000 V 10501 2905 10.501 V 10500 2904 10.500 V 10001 2711 10.001 V 10000 2710 Nominal range...
Page 212
5.500 V 5000 1388 Nominal range 5.000 V 4000 0FA0 4.000 V 2000 07D0 2.000 V 0001 0.001 V 0000 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 213
Current – standard Decimal hexadecimal 0…20 mA (two's complement) Dec. value = 1638.35 (1/mA) × I (mA) 32767 7FFF Nominal range 20.0000 mA 32766 7FFE 19.9994 mA … … … 16384 4000 10.0003 mA … … … 0001 0.0006103 mA 0000 0.0000 mA FFFF...
Page 214
-27664 93F0 0.0000 mA -32512 8100 0.0000 mA -32513 80FF 0.0000 mA -32752 80F0 0.0000 mA -32767 8000 0.0000 mA Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 215
Decimal hexadecimal 4…20 mA (two's complement) dec. value = 1728 (1/mA) × (I (mA) - 4 mA) 32767 7FFF 22.962 mA 32752 7FF0 22.954 mA 32512 7F00 22.815 mA 32511 7EFF 22.814 mA 32496 7EF0 22.806 mA 27664 6C10 20.0096 mA 27649 6C01 20.0006 mA...
Page 216
3600 0E10 3.600 mA 3599 0E0F 3.599 mA 2000 07D0 2.000 mA > 1999 07CF 1.999 mA 0001 0.000 mA Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Troubleshooting If the device does not function as expected, first check whether ambient interference is present. If there is no ambient interference present, check the connections of the device for faults. If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type.
Right-click HOST PC Add device. Fig. 79: Adding a device in PACTware Select BL Service Ethernet and confirm with OK. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 219
Fig. 80: Select the Ethernet interface Double-click the connected device. PACTware opens the Busaddress management function. Fig. 81: Opening Busaddress management V04.00 | 2021/05...
Page 220
Select the required device. Fig. 82: Selecting the device Click Firmware Download to start the firmware update. Fig. 83: Starting the firmware update Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 221
Select the storage location and confirm with OK. PACTware shows the progress of the firmware update with a green bar at the bottom of the screen. Fig. 84: Firmware update in progress V04.00 | 2021/05...
Disposal The devices must be disposed of correctly and must not be included in general household garbage. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Technical Data 14.1 General technical data Technical data Power supply Supply voltage 24 VDC Permisible range 18…30 VDC Total current Max. 4 A per voltage group V1 + V2 max. 5.5 A at 70 °C per module Potential isolation Galvanic isolation of V1 and V2 voltage groups Connectors Ethernet 1 x M8 (IN),...
Page 224
FCC Rules. Operation of this equipment in a residential area may cause harm- ful interference. In this case, the user must correct the interference at his own ex- pense. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.2 Techincal data – TBEN-S1-8DIP The device has eight digital inputs for 3-wire PNP sensors. Technical data Power supply Operating current (from V1) < 150 mA Sensor/actuator supply VAUX1 Supply connector C0…C7 from V1 short-circuit proof, 0.5 A per group C0…C3, C4…C7 Potential isolation From V1 and V2 voltage group,...
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 287 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.4 Technical data – TBEN-S2-8DIP The device offers eight digital inputs for 3-wire PNP sensors. The module offers channel dia- gnostics Technical data Power supply Operating current (from V1) < 150 mA Sensor/actuator supply VAUX1 Supply connector C0…C3 from V1, supply at pin1 of the switchable per connector, short-circuit proof, 0.5 A per connector Potential isolation...
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 283 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.6 Technical data – TBEN-S1-4DIP-4DOP The station offers four digital inputs for 3-wire PNP-sensors and for digital outputs for DC actu- ators. Technical data Power supply Operating current (from V1) < 150 mA Sensor/actuator supply VAUX1 Supply connector C0…C3 from V1 short-circuit proof, 0.5 A per group C0…C3 Sensor/actuator supply VAUX2 Supply connector C4…C7 from V2...
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 307 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.8 Technical data TBEN-S1-8DXP The device has eight DXP channels. Up to eight 3-wire PNP sensors or eight PNP DC actuators can be connected. Technical data Power supply Operating current (from V1) < 150 mA Sensor/actuator supply VAUX1 Supply connector C0…C3 from V1 short-circuit proof, 0.5 A per group C0…C3 Sensor/actuator supply VAUX2 Supply connector C4…C7 from V2...
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 238 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.10 Technical data – TBEN-S2-4AI The module provides four analog inputs, which can be configured as voltage, current, RTD or thermo couple input. Technical data Power supply Operating current V1: min. 100 mA, max. 240 mA Sensor/actuator supply VAUX1 Supply connector C0…C3 from V1 -circuit proof, 1 A per group C0…C3 Potential isolation V1/V2/Ethernet Galvanic isolation from V1 and V2 voltage group,...
Page 234
< 100 ppm/°C of full scale Measurement error total (FSR) [} 236] General information MTTF 145 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Type C 0…2315 °C ≤ 0.75 % Type G 0…2315 °C ≤ 2.25 % Only valid for lower measure- ment range Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
14.10.3 Example calculation: operational error limit and absolute max. total error Calculation: operational error limit Operation mode: RTD/ resistance Measurement range: Pt100 -200°C…850°C Basic error at 25 °C: < 0,2 % Max. measuring range end value: 850 °C Calculation of the operational error limit: 850 °C ×...
Isolation voltage V1/ V2/Ethernet Min. 500 V General information MTTF 244 years acc. to SN 29500 (Ed. 99) 20 °C Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Appendix: Approvals and markings Approvals Marking according to EN 60079-0/-7/-31 ATEX directive ÉII 3 G ATEX approval no.: Ex ec IIC T4 Gc ÉII 3 D TÜV 20 ATEX 264795 X Ex tc IIIC T115 °C DC IECEx approval no.: Ex ec IIC T4 Gc IECEx TUN 20.0010X Ex tc IIIC T115 °C DC...
Turck Banner Malaysia Sdn Bhd Unit A-23A-08, Tower A, Pinnacle Petaling Jaya, Jalan Utara C, 46200 Petaling Jaya Selangor www.turckbanner.my Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 243
Mexico Turck Comercial, S. de RL de CV Blvd. Campestre No. 100, Parque Industrial SERVER, C.P. 25350 Arteaga, Coahuila www.turck.com.mx Netherlands Turck B. V. Postbus 297, NL-8000 AG Zwolle www.turck.nl Austria Turck GmbH Graumanngasse 7/A5-1, A-1150 Wien www.turck.at Poland TURCK sp.z.o.o.
Page 244
Over 30 subsidiaries and over 60 representations worldwide! 100001931 | 2021/05 100001931 www.turck.com...