Page 1
TBEN-S… Digital and Analog Modules Instructions for Use...
Page 2
Connecting a device in zone 2 and zone 22 ............ 29 Connecting a device to Ethernet ................ 30 6.2.1 Applications with QuickConnect (QC) and Fast Start Up (FSU) ........ 30 V06.00 | 2025/02 | 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 3
Configuring the device in Logix Designer................ 155 7.7.3 Parameterizing the device ....................... 156 7.7.4 Going online with the PLC ....................... 157 7.7.5 Reading process data......................... 159 V06.00 | 2025/02 | 3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 4
14.2 Techincal data – TBEN-S1-8DIP ................ 275 14.3 Techincal data – TBEN-S1-8DIP-D................ 276 14.4 Technical data – TBEN-S2-8DIP ................ 277 V06.00 | 2025/02 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 5
Example calculation: operational error limit and absolute max. total error .. 287 14.11 Technical data – TBEN-S2-4AO................. 288 15 Turck branches — contact data .................... 289 V06.00 | 2025/02 | 5 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Operating instructions TBEN-S2-2COM-4DXP (D301439) EU Declaration of Conformity (current version) Notes on Use in Ex zone 2 and 22 (100022986) Approvals V06.00 | 2025/02 | 6 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V06.00 | 2025/02 | 7 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Closing caps for M8 or M12 sockets Labeling clips Turck service Turck supports you in your projects – from the initial analysis right through to the commission- ing of your application. The Turck product database at www.turck.com offers you several software tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
4.1.1 Display elements The device is provided with the following LEDs: Power supply voltage Group and bus error Status Diagnostics V06.00 | 2025/02 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
500 mA per group V2 + AUX2 IN Diag 4 IN/OUT 3 V2 – OUT Diag Fig. 4: Block diagram – digital modules V06.00 | 2025/02 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 13
1 V2 + 2 AO + 3 GND Diag 4 AO – 5 FE Fig. 5: Block diagram – analog modules V06.00 | 2025/02 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Duty-Cycle (mark-to-space ratio): 0…100 in %, default 0, example: 20: Duty cycle 20 to 80 = ratio "on" to "off V06.00 | 2025/02 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 17
BEEP (Backplane Ethernet Extension Protocol) is a technology that is available in many digital Turck multi protocol block I/O modules. BEEP allows a network, of up to 33 participants (one controller and 32 devices) or 480 bytes of data, to appear to the PLC as a single device on a single connection using a single IP address.
Page 18
Product description Possible Ethernet network structures Possible Ethernet network structures PLC/HMI Service/Engineering 24 VDC Ethernet Fig. 7: Network structure, example 1 V06.00 | 2025/02 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 19
Possible Ethernet network structures PLC/HMI Service/Engineering 24 VDC Ethernet Fig. 8: Network structure, example 2 PLC/HMI/Service/Engineering 24 VDC Ethernet Fig. 9: Network structure, example 3 V06.00 | 2025/02 | 19 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Optionally available accessories for mounting, connecting and parameter setting can be found in the Turck product database at www.turck.com. Accessories are not supplied with the device. V06.00 | 2025/02 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 21
Fit the housing cover and screw on as shown in the following figure. The tightening torque for the Torx T8 screw is 0.5 Nm. Fig. 11: Installing the device in the TB-SG-S protective housing V06.00 | 2025/02 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 22
Repeat steps 1 to 4 until the module group in complete. Fig. 12: Step 1 Fig. 13: Step 2 Fig. 14: Step 3 Fig. 15: Step 4 V06.00 | 2025/02 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 23
Repeat steps 1 to 4 until the module group in complete. Fig. 16: Step 1 Fig. 17: Step 2 Fig. 18: Step 3 Fig. 19: Step 4 V06.00 | 2025/02 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 24
To increase stability on the DIN rail, end brackets can be mounted on the right and left of the module or the module combination. V06.00 | 2025/02 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fig. 24: TBEN-S2 analog modules – equivalent wiring diagram and shielding concept V06.00 | 2025/02 | 25 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 26
If direct grounding of the fieldbus shield is not desired, the grounding clip (1) must be removed. In this case, the fieldbus shield is connected to the module ground via an RC element. V06.00 | 2025/02 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 27
With mounted grounding clip: The shielding of the fieldbus is connected to the reference potential of the installation via the module grounding of the I/O level. V06.00 | 2025/02 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 28
With mounted grounding clip: The shielding of the fieldbus is connected to the reference potential of the installation via the module grounding of the I/O level. V06.00 | 2025/02 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 29
Use all connectors or seal them with screw caps or blind caps. The tightening torque for the screw caps is 0.5 Nm. Observe requirements for Ex approval. V06.00 | 2025/02 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 30
Do not use crossover cables in applications with QuickConnect (QC) and and Fast Start Up (FSU) applications. Connect incoming Ethernet cables to P1. Connect outgoing Ethernet cables to P2. V06.00 | 2025/02 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In case of an undervoltage at V2, the LED PWR changes from green to red. In case of an undervoltage at V1, the LED is turned off. V06.00 | 2025/02 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Connecting Connecting the supply voltage Analog modules Fig. 39: Power supply TBEN-S2-4AI Fig. 40: Power supply TBEN-S2-4AO V06.00 | 2025/02 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
4 BK ( ) 1 BN (+) C0...C7 With 3-wire connection, the actuator is supplied via pin 1 but is not switched. V06.00 | 2025/02 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 35
4 = Signal In/Out 1 BN (+) C0…C3 C0...C7 1 = V AUX2 3 = GND V2 4 = Signal In/Out C4…C7 V06.00 | 2025/02 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 36
2 = Signal In/Out 3 = GND V2 4 = Signal In/Out 5 = FE C2...C3 Supply VAUX (pin 1) switchable per connector V06.00 | 2025/02 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 37
3 = AI –/GND V1 4 = n.c. Current wiring type = single ended 5 = FE Flange = FE C0...C3 V06.00 | 2025/02 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 38
NOTE The 2 wire and 3 wire connection are only possible in the single ended voltage or current measurement mode. V06.00 | 2025/02 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 39
Connect only the necessary signals in 2- or 3-wire mode. Do not connect unused pins as shown in the respective wiring diagram. V06.00 | 2025/02 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 40
2 = AO + 3 = GND V2 4 = AO –/GND V2 5 = FE Flange = FE C0...C3 V06.00 | 2025/02 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Adjusting network settings NOTE Changes to network settings are only applied after restarting the device. The network settings can be adapted via TAS (Turck Automation Suite), the web server, the DTM, a DHCP server or PROFINET DCP. 7.1.1 Adjusting network settings via TAS (Turck Automation Suite) In the delivery state the device has the IP address 192.168.1.254.
Page 42
Change the device name, the IP address and the network mask if necessary. Save changes by clicking on APPLY . Fig. 49: Changing network settings in TAS V06.00 | 2025/02 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 43
Adjust the network settings. Write the changes into the device via SET NETWORK CONFIGURATION. Fig. 50: Web server – adjusting network settings V06.00 | 2025/02 | 43 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 44
The name must not have the form of an IP address (n.n.n.n, n = 0…999). Do not use special characters. Do not use capital letters. V06.00 | 2025/02 | 44 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 45
Fig. 51: TIA-Portal – assignment of the slots and sub slots on the example of an TBEN-S1-8DXP V06.00 | 2025/02 | 45 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 46
Set "Transmission rate/duplex" to a fix value. Deactivate auto-negotiation Fig. 52: TIA-Portal – port-settings for FSU V06.00 | 2025/02 | 46 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 47
Commissioning the devices in PROFINET Activate the prioritized start-up at the I/O device. Fig. 53: TIA-Portal – prioritized start-up, activation at the I/O device V06.00 | 2025/02 | 47 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 48
For PROFINET, the response monitoring time must be selected accordingly > 200 ms. It is not possible to use Fast Start-Up in an MRP network. V06.00 | 2025/02 | 48 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 49
… 0xAFEF 45040 0xAFF0 I&M0-functions read Identification & Maintaining 45041 0xAFF1 I&M1-functions STRING[54] read/ I&M Tag function and write location V06.00 | 2025/02 | 49 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 50
20…22 0x14 … reserved 0x16 0x17 Output data specific read/ Output data of the respect- write ive I/O-channel … … reserved V06.00 | 2025/02 | 50 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Adding the GSDML file: Click Options Ò Manage general station description files (GSD). Fig. 54: Manage general station description files (GSD) in TIA Portal V06.00 | 2025/02 | 51 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 52
Installing the GSDML file: Define the source path for the GSDML-file and click Install. The device is added to the hardware catalog. Fig. 55: TIA Portal – installing the GSDML file V06.00 | 2025/02 | 52 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 53
Select functions as operation mode, diagnostics etc. from the hardware catalog and add them to the devoce slots via drag&drop. Fig. 56: Configuring the device slots V06.00 | 2025/02 | 53 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 54
Functions Ò Assign PROFINET device name. Assign the desired PROFINET device name with Assign name. Fig. 57: TIA-Portal: Assigning the PROFINET device name V06.00 | 2025/02 | 54 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 55
Select Device view Ò register Properties Ò Ethernet addresses . Assign the desired IP address. Fig. 58: TIA-Portal: Assigning the IP address V06.00 | 2025/02 | 55 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 56
Select the device to be parameterized. Click Properties ÒGeneral ÒModule parameters. Set the device parameters. Fig. 59: Setting module parameters V06.00 | 2025/02 | 56 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 57
The PROFINET mapping corresponds to the data mapping described in the sections “Process input data [} 204] and „Process output data” [} 212]. V06.00 | 2025/02 | 57 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Process data of the inputs (identical to registers 0x0000…0x01FF) 0x9000…0x9FFF read/write Process data of the outputs (identical to registers 0x0800…0x09FF) V06.00 | 2025/02 | 58 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
0x113D. Both registers can also be written with one single request using the function codes FC16 and FC23. The parameters are reset to default values. Save changes via a subsequent Save service. V06.00 | 2025/02 | 60 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 61
TBEN-S2-8DXP 8 bit 8 bit Bit by bit TBEN-S2-4AI 8 byte Word by word TBEN-S2-4AO 8 byte Word by word V06.00 | 2025/02 | 61 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 62
TBEN-S1-8DIP – output registers Meaning of the process output data [} 212] Register no. Bit no. Latch reset 0x0800 Counter reset 0x0801 reset V06.00 | 2025/02 | 62 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 63
Counter value MSB Freq. Ch0 0x0005 Frequency MSB Frequency LSB Status 0x0006 Module status 0x0007 FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 63 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 64
DIFT DI0 DMOD_CNT DI0 Channel 1 0xB001 IST DI1 DIFT DI1 DMOD DI1 … Channel 7 0xB007 IST DI7 DIFT DI7 DMOD DI7 V06.00 | 2025/02 | 64 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 65
TBEN-S2-8DIP – output registers Meaning of the process output data [} 212] Register no. Bit no. Latch reset 0x0800 Counter reset 0x0801 reset V06.00 | 2025/02 | 65 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 77
ARGEE Diag Warn TBEN-S2-4AO – output registers Meaning of the process output data [} 216] Register Bit no. 0x0800 0x0801 0x0802 0x0803 V06.00 | 2025/02 | 77 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
System power supply too low (< 18 VDC). Channel diagnostics Cold junction error Overcurrent at the respective output LLVU Lower limit value underrun V06.00 | 2025/02 | 78 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 79
Thermocouple type Temperature unit Voltage range Voltage wiring type TBEN-S2-4AO Deactivate channel Deactivate diagnostics Data representation Output on fieldbus error V06.00 | 2025/02 | 79 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
"0" after the watchdog time has expired, unless another protocol (PROFINET, EtherNet/IP) has been activated in the meantime. V06.00 | 2025/02 | 80 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Used software The following software tools are used in this example: CODESYS 3.5.18.2 (can be downloaded for free under www.turck.com). V06.00 | 2025/02 | 81 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 82
Click Insert device. The Ethernet Adapter is added to the project tree as Ethernet (Ethernet). Fig. 61: Adding the Ethernet Adapter V06.00 | 2025/02 | 82 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 83
Select Add Device. Double-click Modbus TCP Master. The Modbus_TCP_Master is added to the project tree. Fig. 62: Adding the Modbus TCP Master V06.00 | 2025/02 | 83 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 84
Select Add Device. Double-click Modbus TCP Slave. The Modbus_TCP_Slave is added to the project tree. Fig. 63: Adding the Modbus TCP Slave V06.00 | 2025/02 | 84 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 85
Click Device Ò Scan network. Select Modbus TCP Master (here: TX715-P3CV01) and confirm with OK. Fig. 64: Configuring the network interface V06.00 | 2025/02 | 85 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 86
Open the dialog box Network Adapter by clicking the Browse… button in the register tab General. Select the interface TX715-P3CV01 (here: 192.168.145.72) Fig. 65: Selecting the interface V06.00 | 2025/02 | 86 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 87
Enter the slave IP address in the General register tab (here: 192.168.145.200). Fig. 66: Modbus TCP Slave: Setting the IP address V06.00 | 2025/02 | 87 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 88
Channel name Access type: Read Input Registers Offset: 0x0000 Length: 1 register Confirm with OK. Fig. 67: Defining the input register V06.00 | 2025/02 | 88 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 89
Access type Write Single Register Offset: 0x0800 Length: 1 register Confirm with OK. Fig. 68: Defining the output data register V06.00 | 2025/02 | 89 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 90
Connecting devices to a Modbus Client with CODESYS 7.5.5 Going online with the PLC Select the device. Click Online Ò Login. Fig. 69: Login V06.00 | 2025/02 | 90 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 91
Download the application to the PLC and start it via Debug Ò Start. The Modbus TCP communication is setup. Fig. 70: Modbus TCP communication V06.00 | 2025/02 | 91 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 92
Click onto register tab Modbus TCP Slave I/O Mapping. Set the function Always update variables to Enabled 1 (…). The process data are displayed. Fig. 71: Process data V06.00 | 2025/02 | 92 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 93
Deactivated For information on the correct connection of Ethernet cables in QuickConnect applications, please refer to the chapter Connecting [} 30]. V06.00 | 2025/02 | 93 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 94
Activate Quick Connect via Class Instance Attribute as follows: Class Instance Attribute Value 0xF5 0x01 0x0C 0: deactivated (default) 1: activated V06.00 | 2025/02 | 94 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 95
Ethernet traffic, so that a line topology is created for normal Ethernet telegrams. DLR mes- sages can continue to use the ring in both directions and thus continuously check the function of the ring. V06.00 | 2025/02 | 95 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Communications Adapter = 0x0C 0x03 Product UINT Identifies a special product in a code device type. default: 27247 = 0x6A6F V06.00 | 2025/02 | 96 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 97
Starts the reset service for the device 0x0E Get_Attribute_Single Returns the content of a specified attribute 0x10 Set_Attribute_Single Changes a single attribute V06.00 | 2025/02 | 97 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Dec. Hex. 0x01 Get_Attribute_All Returns a predefined list of object attributes. 0x0E Get_Attribute_Single Returns the content of a specified attribute. V06.00 | 2025/02 | 98 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 99
The port is set to autonegotiation. Auto negotiation 100BT/FD Defined setting of communication para- meters for the Ethernet port to: 100BaseT Full duplex V06.00 | 2025/02 | 99 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 100
Assignment similar to channel 1 (byte 14…17) 0x13 0x14 0x15 … Channel 7 0x26 Assignment similar to channel 1 (byte 14…17) 0x27 0x28 0x29 V06.00 | 2025/02 | 100 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Output data data – TBEN-S1-8DIP [} 212] Control word + 2 words Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 Reset V06.00 | 2025/02 | 109 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 110
Output data data – TBEN-S2-8DIP [} 212] Control word + 2 words Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 00002 Reset V06.00 | 2025/02 | 110 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 111
Output data data – TBEN-S1-8DIP-D [} 212] Control word + 2 words Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 Reset V06.00 | 2025/02 | 111 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Common services Service code Class Instance Meaning Dec. Hex. 0x54 FWD_OPEN_CMD (opens a connection) 0x4E FWD_CLOSE_CMD (closes a connection) 0x52 UNCONNECTED_SEND_CMD V06.00 | 2025/02 | 121 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 122
0x06 Host name STRING 0 = no host name configured 0x0C QuickConnect BOOL 0 = deactivate 1 = activate V06.00 | 2025/02 | 122 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 123
(for example, in non-volatile memory or via hardware switches, etc). 1…3 = reserved DNS Enable Always 0 5…31 Reserved Set to 0 V06.00 | 2025/02 | 123 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 124
The mechanism allows the DHCP client to transmit its host name to the DHCP server. The DHCP server then updates the DNS records on behalf of the client. V06.00 | 2025/02 | 124 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 125
3 = successfully negotiated speed and duplex 4 = autonegotiation not started, yet. Forced speed and duplex. V06.00 | 2025/02 | 125 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 126
TBEN-S1-4DIP-4DOP 0x9C Input Latch In- and output data for the TBEN-S1-4DIP-4DOP Channel 0…3 input latch function of the device TBEN-S1-4DXP V06.00 | 2025/02 | 126 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 127
24 VDC sensor and actuator supply 0xAB TBEN-S2-8DIP 0xBC Basic Data and parameters for the TBEN-S1-4DXP basic functions of the digital devices V06.00 | 2025/02 | 127 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 128
(cannot be deactivated via the EtherNet/IP interface). Bit 1: Deactivates Modbus TCP Bit 2: Deactivates PROFINET Bit 15: Deactivates the web server V06.00 | 2025/02 | 128 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 129
4: 100BaseT, full duplex, linear topology (AutoMDIX disabled) 0x73 I/O controller DWORD Only valid for instance 1: software revision Firmware version of the device V06.00 | 2025/02 | 129 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 130
2: -20…20 mA 0x07 Current wiring USINT 0 = differential type 1 = single ended 2 = differential without ground V06.00 | 2025/02 | 130 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 131
USINT 0: off sion 1: 50 Hz 2: 60 Hz 0x12 Upper limit USINT 0: - value 1: active exceeded V06.00 | 2025/02 | 131 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 132
Wire break USINT 0: - 1: active 0x19 Overcurrent USINT 0: - supply VAUX1 1: active 0x1A Input value UINT V06.00 | 2025/02 | 132 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 133
Substitute value to be transferred 0x0A Overload USINT 0: - 1: active 0x0B Wire break USINT 0: - 1: active 0x0C output UINT V06.00 | 2025/02 | 133 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 134
1: on 0x09 Input value ch6 USINT 0: off 1: on 0x0A Input value ch7 USINT 0: off 1: on V06.00 | 2025/02 | 134 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 135
1: on 0x0F Input value ch6 USINT 0: off 1: on 0x10 Input value ch7 USINT 0: off 1: on V06.00 | 2025/02 | 135 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 136
0x0F Diagnostics ch6 – overcurrent USINT 0: - 1: active 0x10 Diagnostics ch7 – overcurrent USINT 0: - 1: active V06.00 | 2025/02 | 136 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 137
Manual reset after USINT 0: no overcurr. ch2 1: yes 0x0C Manual reset after USINT 0: no overcurr. ch3 1: yes V06.00 | 2025/02 | 137 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 138
1: on 0x1F Input value ch4 USINT 0: off 1: on 0x20 Input value ch5 USINT 0: off 1: on V06.00 | 2025/02 | 138 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 139
4: Output value ch4 bit 5: Output value ch5 bit 6: Output value ch6 bit 7: Output value ch7 V06.00 | 2025/02 | 139 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 140
Bit 0: Output value ch4 bit 1: Output value ch5 bit 2: Output value ch6 bit 3: Output value ch7 V06.00 | 2025/02 | 140 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 141
Output value ch2 – USINT 0: off Latch reset 1: on 0x08 Output value ch3 – USINT 0: off Latch reset 1: on V06.00 | 2025/02 | 141 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 142
0x04 Counter value UDINT 0x05 Counter frequency (hz) UINT 0x06 Status USINT 0x07 Counter reset USINT 0: inactive 1: active V06.00 | 2025/02 | 142 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 143
Overcurrent PWM output USINT 0: - 1: active 0x03 Overcurrent PWM output USINT 0: - 1: active 0x04 Duty Cycle USINT V06.00 | 2025/02 | 143 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 144
Overcurrent PWM output USINT 0: - 1: active 0x05 Overcurrent PWM output USINT 0: - 1: active 0x06 Duty Cycle USINT V06.00 | 2025/02 | 144 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 145
Output value ch6 – Latch reset USINT 0: off 1: on 0x10 Output value ch7 – Latch reset USINT 0: off 1: on V06.00 | 2025/02 | 145 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 146
1: on 0x0B Input value ch6 USINT 0: off 1: on 0x0C Input value ch7 USINT 0: off 1: on V06.00 | 2025/02 | 146 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 147
0: - overcurrent VAUX1 pin1 C0 1: active 0x12 Diagnostics ch2/3 – USINT 0: - overcurrent VAUX1 pin1 C1 1: active V06.00 | 2025/02 | 147 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 148
1: on 0x23 Input value ch6 USINT 0: off 1: on 0x24 Input value ch7 USINT 0: off 1: on V06.00 | 2025/02 | 148 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 149
0x07 VAUX1 pin1 C2 (Ch4/5) USINT 0: on 1: off 0x08 VAUX2 Pin1 C0 (ch0/1) USINT 0: on 1: off V06.00 | 2025/02 | 149 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 150
1: yes 0x02 Activate output Ch1 USINT 0: no 1: yes 0x03 Activate output Ch2 USINT 0: no 1: yes V06.00 | 2025/02 | 150 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 151
Bit 0: Output value ch0 bit 1: Output value ch1 bit 2: Output value ch2 bit 3: Output value ch3 V06.00 | 2025/02 | 151 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The PLC and the scanner mentioned above have been added to the project in the second in- stance of Studio 5000. V06.00 | 2025/02 | 152 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 153
Adding the devices from the Catalog files to the new project Right-click the device entry and use Copy. Fig. 74: Logix Designer: copying the device entry from catalog file V06.00 | 2025/02 | 153 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 154
Right-click the EtherNet/IP Scanner in the 2nd instance of Logix Designer and add the device to the project via Paste. Fig. 75: Logix Designer: Adding the device to the project V06.00 | 2025/02 | 154 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 155
Set the IP address of the device (example: 192.168.145.181). Fig. 76: Setting module name and IP address Optional: Set the connection parameters. Fig. 77: Setting the connection parameters V06.00 | 2025/02 | 155 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Open the "Controller Tags" of the device. Parameterize the device by using the TBEN_S1_8DXP:C Controller Tags. Fig. 78: Parameterizing the Device V06.00 | 2025/02 | 156 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 157
Select the PLC. Set the communication path via Set Project Path. The communication path is set. Fig. 79: Setting the communication path V06.00 | 2025/02 | 157 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 158
Click Download in the following dialog (Connect To Go Online). Confirm all following messages. The program is downloaded to the PLC. The online connection is established. V06.00 | 2025/02 | 158 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 159
The access to the parameter data (TBEN_S…:C), input data (TBEN_S…:I) and output data (TBEN_S…:O) is possible. Fig. 81: Controller Tags in the project tree V06.00 | 2025/02 | 159 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 160
61451 (port number of server station for NodeSearch and IPAddressSet) 7.8.2 CSP+ files The CSP+ files can be downloaded free of charge at www.turck.com. V06.00 | 2025/02 | 160 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 175
RWw00 Analog value channel 0 RWw01 Analog value channel 1 RWw02 Analog value channel 2 RWw03 Analog value channel 3 V06.00 | 2025/02 | 175 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 180
Assignment s. B001 (channel 0) Assignment s. B001 (channel 0) B003 B004 B005 Extended digital function PWM Deactivated PWM output V06.00 | 2025/02 | 180 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 181
4…20 mA 0…20 mA 20…20 mA Current wiring type Differential Single ended Differential without ground Resistance wiring type 2-wire 3-wire 4-wire V06.00 | 2025/02 | 181 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 182
Type C, 0…2315 °C, 32…4199 °F Type G, 0…2315 °C, 32…4199 °F B001 Assignment s. B001 (channel 0) Assignment s. B001 (channel 0) B002 B003 V06.00 | 2025/02 | 182 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 183
2…10 V 0…5 V 1…5 V Substitute value B001 Assignment s. B001 (channel 0) Assignment s. B001 (channel 0) B002 B003 V06.00 | 2025/02 | 183 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 184
0x0000 error. A valid connection handle is 0xAD00…0xADFF, or 0 in case of failure. V06.00 | 2025/02 | 184 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 185
4. Close Connection: Device Write (0x1401) Device Code = 0xAC Add=0xACAC, Len=1 Data: 0xADxx (address of the previously used Open Connection) V06.00 | 2025/02 | 185 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 186
Accesses the diagnostic data data of one (sub)module. … Data is structured in the native order of that (sub)mod- 0x00… ule. V06.00 | 2025/02 | 186 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 187
Connecting devices to a CC-Link IE Field Basic client with GX Works3 Naming convention Turck uses the terms ”client” and ”server”. The following description uses the terms “Master Sta- tion” (client) and “Slave Station” (server) only because of the naming in Melsoft GX Works.
Under CC-Link IEF Baisc Settings, set the option To Use or Not to Use CC-Link IEF Basic Setting to Use in order to activate Fig. 83: GX Works3: Activate CC-Link IEF Basic on CPU V06.00 | 2025/02 | 188 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 189
Under Module Parameters Ò CC-Link IEF Basic Settings open the function Network Configuration Settings. Fig. 84: GX Works3: Network Configuration Settings V06.00 | 2025/02 | 189 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 190
Scan the CC-Link IEF Basic network under CC-Link IEF Basic Configuration via Detect Now. Fig. 85: GX Works3: scanning the CC-Link IEF Basic network V06.00 | 2025/02 | 190 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 191
For devices that can be integrated with different process data variables (profiles) (here: TBEN-S2-4IOL): select the requested profile under Station Type. V06.00 | 2025/02 | 191 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 192
All parameters for one slot (in the example below: Slot 1) must be set. It is not pos- sible to set individual parameters for a slot. V06.00 | 2025/02 | 192 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 193
Connecting devices to a CC-Link IE Field Basic client with GX Works3 Set the parameters and store the settings via Execute. Fig. 88: GX Works3: Parameterizing the device V06.00 | 2025/02 | 193 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 194
Accept the changes in the network structure under Module Parameters with Apply. Fig. 90: GX Works3: Module Parameters, accept changes V06.00 | 2025/02 | 194 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 195
Fig. 91: GX Works3: Process data mapping in Refresh Settings NOTE Adjusting the mapping may require a voltage reset of the control unit. V06.00 | 2025/02 | 195 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 196
Write the configuration to the PLC via Online Ò Write to PLC. Fig. 92: GX Works3: Writing the configuration to the PLC V06.00 | 2025/02 | 196 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 197
If necessary, define which data have to be written and press Execute. Fig. 93: GX Works3: Selecting data to be written V06.00 | 2025/02 | 197 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 198
The mapping shows a signal at the 2nd Digital input of the 1st CC-Link device (station ad- dress 2, TBEN-LL-8DIP-8DOP) [} 189]. V06.00 | 2025/02 | 198 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 199
0x02 The 24 VDC sensor/actuator supply at pin 1 of the connector is switched off. V06.00 | 2025/02 | 199 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 200
Pt1000, -200…850 °C, -328…1562 °F 0x09 Pt1000, -200…150 °C, -328…302 °F 0x0A Ni1000, -60…250 °C, -76…482 °F 0x0B Ni1000, -60…150 °C, -76…302 °F V06.00 | 2025/02 | 200 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 201
Differential input operation 0x01 Single ended Connection of sensors with common ground [} 37] mode 0x02 differential Differential input without ground V06.00 | 2025/02 | 201 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 202
Set the measurement range of the voltage out- 0x01 0…10 V put. 0x02 2…10 V 0x03 0…5 V 0x04 1…5 V V06.00 | 2025/02 | 202 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Explicit deactivation of the Ethernet I/O-ASSISTANT Force protocols or web server Mode Deactivate EtherNet/IP 0 Deactivate Modbus TCP Deactivate WEB server V06.00 | 2025/02 | 203 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 204
Counter value MSB Frequency Ch0 0x0005 Frequency MSB Frequency LSB Status 0x0006 Module status 0x0007 FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 204 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 205
0x0004 Counter value MSB Frequency ch0 0x0005 Frequency MSB Frequency LSB Status 0x0006 - Module status 0x0007 - COM V1 ARGEE DIAG V06.00 | 2025/02 | 205 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 206
Frequency LSB Status 0x0006 PWM Diagnostics Ch7 0x0007 PWM OUT ERR Module status 0x0008 FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 206 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 207
Frequency LSB Status 0x0006 PWM Diagnostics Ch3 0x0007 PWM OUT ERR Module status 0x0008 FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 207 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 208
0x0007 PWM OUT ERR PWM Diagnostics Ch7 0x0008 PWM OUT ERR Module status 0x0009 FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 208 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 209
Counter value of the 32 bit counter Frequency Frequency for the 32-bit counter Example: Value 50 (dec.) = 50 Hz Diagnostics V06.00 | 2025/02 | 209 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 210
ULVE RTDSC CJE LLVU UFL OFL WBR V1 ULVE RTDSC CJE Module status 0x0006 - FCE - COM V1 ARGEE DIAG V06.00 | 2025/02 | 210 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 211
The measured temperature lies more than 1 % above the nominal range. V1AOL Overcurrent VAUX1 The sensor supply is not within the permissible range. V06.00 | 2025/02 | 211 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 212
Counter reset 0x0002 CNT_ Reset TBEN-S1-8DIP-D Word no. Bit no. Control 0x0000 Latch reset 0x0001 Counter reset 0x0002 CNT_ Reset V06.00 | 2025/02 | 212 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 215
Pin 1 Duty Cycle Mark-to-space ratio: 10…90 % VAUX1/VAUX2 P1 C… Switches the sensor/actuator supply at pin 1 of the connector. V06.00 | 2025/02 | 215 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 216
0x0001 Analog value channel 0 0x0002 Analog value channel 1 0x0003 Analog value channel 2 0x0004 Analog value channel 3 V06.00 | 2025/02 | 216 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Data transfer, 10 Mbit/s LED C7 or C4 Meaning (2nd LED) White flashing Wink command active: helps to localize the module V06.00 | 2025/02 | 217 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 218
Measurement range: Voltage: overflow Overflow/underflow wire break upper limit value exceeded/lower limit value underrun Red flashing (0.5 Hz) Wire break V06.00 | 2025/02 | 218 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 229
0010 0000 > -0.0500 V “Lower limit value underrun” OFF 0000 > -0.10000 V “Lower limit value underrun” ON 0000 V06.00 | 2025/02 | 229 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 230
“Lower limit value underrun” ON 0000 > 0.75 V “Wire break” OFF 0000 < 0.70 V “Wire break” EIN 0000 V06.00 | 2025/02 | 230 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 231
> -502.5 mV ”Lower limit value underrun” OFF -32768 8000 < -505.0 mV “Lower limit value underrun” ON -32768 8000 V06.00 | 2025/02 | 231 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 232
> -50.30 mV ”Lower limit value underrun” OFF -32768 8000 < -50.50 mV “Lower limit value underrun” ON -32768 8000 V06.00 | 2025/02 | 232 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 233
”Lower limit value underrun” OFF > -138 > FF76 < -0.10 V “Lower limit value underrun” ON < -276 < FEEC V06.00 | 2025/02 | 233 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 234
> EDC0 ”wire break” OFF < -0.296 V ”Lower limit value underrun” and < -4865 < ECFF ”wire break” ON V06.00 | 2025/02 | 234 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 235
”Lower limit value underrun” OFF > -32071 > 82B9 > -588 mV “Lower limit value underrun” ON < -32513 > 80FF V06.00 | 2025/02 | 235 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 236
”Lower limit value underrun” OFF > -32050 > 82CE < -58.8 mV “Lower limit value underrun” ON < -32492 < 8114 V06.00 | 2025/02 | 236 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 237
> -30 > FFE2 and ”underflow” OFF < -0.05 V ”Lower limit value underrun” and < -50 < FFCE ”underflow” ON V06.00 | 2025/02 | 237 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 238
> -60 > FFC4 and ”underflow” OFF < -0.05 V ”Lower limit value underrun” and < -100 > FF9C ”underflow” ON V06.00 | 2025/02 | 238 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 239
> D6FC flow” ON > -1.099 V “Underflow” OFF > -10990 > D512 < -1.100 V “Underflow” ON < -11000 > D508 V06.00 | 2025/02 | 239 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 240
> D6FC flow” ON > -0.1099 mV “Underflow” OFF > -10990 > D512 < -0.1100 mV “Underflow” ON < -11000 > D508 V06.00 | 2025/02 | 240 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 241
> -164 > FF5C and ”underflow” OFF < -0.20 mA ”Lower limit value underrun” and < -328 > FEB8 ”underflow” ON V06.00 | 2025/02 | 241 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 242
”Lower limit value underrun” OFF > -138 > FF76 < -0.20 mA “Lower limit value underrun” ON < -276 < FEEC V06.00 | 2025/02 | 242 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 243
> -32080 > 82B0 break” OFF < -23.519 mA ”Lower limit value underrun” and ”wire < -32513 > 80FF break” ON V06.00 | 2025/02 | 243 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 244
< -2000 > F830 > -0.10 mA “Underflow” OFF > -100 > FF9C < -0.20 mA “Underflow” ON < -200 > FF38 V06.00 | 2025/02 | 244 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 245
< -21000 > ADF8 > -21.80 mA “Underflow” OFF > -21800 > AAD8 < -22.00 mA “Underflow” ON < -22000 > AA10 V06.00 | 2025/02 | 245 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 246
0 Ω 0000 ≥ 0 Ω ”Lower limit value underrun” OFF 0000 < -1 Ω “Lower limit value underrun” ON 0000 V06.00 | 2025/02 | 246 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 247
Wire break (WBR): no Pt/Ni sensor connected, process value is set to 0x8000. Upper limit value exceeded (ULVE) Lower limit value underrun (LLVU) V06.00 | 2025/02 | 247 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 248
0 °C 0000 1 °C 000 A 250 °C 2500 09C4 252.5 °C “Upper limit value exceeded” ON 2525 09DD V06.00 | 2025/02 | 248 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 249
-1 °C 0 °C 2338.15 °C 2315 °C Type G 0…2315 °C -1 °C 0 °C 2338.15 °C 2315 °C V06.00 | 2025/02 | 249 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 250
Wire break (WBR): no Thermocouple sensor connected, process value is set to 0x8000. Cold junction error (CJE) Upper limit value exceeded (ULVE) Lower limit value underrun (LLVU) V06.00 | 2025/02 | 250 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 258
10.001 V 10000 2710 Nominal range 10.000 V 4000 0FA0 4.000 V 2000 07D0 2.000 V 0001 0.001 V 0000 V06.00 | 2025/02 | 258 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 259
5.500 V 5000 1388 Nominal range 5.000 V 4000 0FA0 4.000 V 2000 07D0 2.000 V 0001 0.001 V 0000 V06.00 | 2025/02 | 259 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 260
4.0000 mA … … … -16384 C000 4.0000 mA … … … -32767 8001 4.0000 mA -32767 8000 4.0000 mA V06.00 | 2025/02 | 260 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 261
-27664 93F0 0.0000 mA -32512 8100 0.0000 mA -32513 80FF 0.0000 mA -32752 80F0 0.0000 mA -32767 8000 0.0000 mA V06.00 | 2025/02 | 261 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 262
-27664 93F0 0.0000 mA -32512 8100 0.0000 mA -32513 80FF 0.0000 mA -32752 80F0 0.0000 mA -32767 8000 0.0000 mA V06.00 | 2025/02 | 262 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 263
3600 0E10 3.600 mA 3599 0E0F 3.599 mA 2000 07D0 2.000 mA > 1999 07CF 1.999 mA 0001 0.000 mA V06.00 | 2025/02 | 263 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If the malfunction persists, the device is faulty. In this case, decommission the device and re- place it with a new device of the same type. V06.00 | 2025/02 | 264 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TCP network. This enables a firmware update to be performed for multiple devices at once. V06.00 | 2025/02 | 265 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 266
Click START to start the firmware update. Fig. 98: Firmware update progress The progress of the firmware update is displayed. V06.00 | 2025/02 | 266 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 267
Click Firmware Ò SELECT FIRMWARE FILE. Select the new firmware file and load it via Open. Fig. 99: Webserver – Selecting the firmware file V06.00 | 2025/02 | 267 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 268
The progress of the firmware update is displayed. Fig. 101: Webserver – Firmware update running Restart the device after the update process has been completed. V06.00 | 2025/02 | 268 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 269
Example: Update the Firmware with the PACTware FDT Frame Application Launch PACTware. Right-click HOST PC Ò Add device. Fig. 102: Adding a device in PACTware V06.00 | 2025/02 | 269 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 270
Fig. 103: Selecting the Ethernet interface Double-click the connected device. PACTware opens the bus address management. Fig. 104: Opening the busaddress management V06.00 | 2025/02 | 270 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 271
PACTware shows the progress of the firmware update with a green bar at the bottom of the screen. Fig. 107: Firmware update running V06.00 | 2025/02 | 271 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Disposal The devices must be disposed of properly and do not belong in the domestic waste. V06.00 | 2025/02 | 272 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Device Level Ring (DLR) Supported Quick Connect (QC) < 500 ms Min. RPI (Requested Packet Interval) 2 ms Number of TCP connections V06.00 | 2025/02 | 273 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 274
Part 15 of the FCC regulations. Operation of this device in a residential area may cause harmful interference. In this case users must rectify the interference at their own cost. V06.00 | 2025/02 | 274 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 275
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 319 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 275 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 276
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 287 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 276 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 277
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 314 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 277 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 278
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 283 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 278 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 279
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 264 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 279 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 280
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 307 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 280 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 281
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 248 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 281 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 282
Galvanic isolation to P1/P2, voltage proof up to 500 VDC General information MTTF 238 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 282 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 283
0…20 mA, 4…20 mA, -20…20 mA Mains suppression Off, 50 Hz, 60 Hz Cycle time ≤ 4 ms Basic error < 0,1 % V06.00 | 2025/02 | 283 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 284
< 100 ppm/°C of full scale Measurement error total (FSR) [} 286] General information MTTF 145 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 284 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 285
Type C 0…2315 °C ≤ 0.2 % Type G 0…2315 °C ≤ 1.6 % Only valid for lower measurement range V06.00 | 2025/02 | 285 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 286
Type C 0…2315 °C ≤ 0.75 % Type G 0…2315 °C ≤ 2.25 % Only valid for lower measurement range V06.00 | 2025/02 | 286 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 287
This results in the following tolerance range for the temperature measuring range, e.g. for 200 °C (at -40 °C operating temperature): 192.775 °C < 200 °C < 207.225 °C V06.00 | 2025/02 | 287 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 288
Isolation voltage V1/ V2/Ethernet Min. 500 V General information MTTF 244 years acc. to SN 29500 (Ed. 99) 20 °C V06.00 | 2025/02 | 288 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 289
Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V06.00 | 2025/02 | 289 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 290
United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V06.00 | 2025/02 | 290 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 291
Over 30 subsidiaries and 60 representations worldwide! 100001931 | 2025/02 100001931 www.turck.com...
Need help?
Do you have a question about the TBEN-S Series and is the answer not in the manual?
Questions and answers