Integration with abb control builder m via profibus

Advertisement

Quick Links

Your Global Automation Partner
excom I/O System
Integration with ABB Control
Builder M via PROFIBUS
Integration Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the excom I/O System and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for turck excom I/O System

  • Page 1 Your Global Automation Partner excom I/O System Integration with ABB Control Builder M via PROFIBUS Integration Manual...
  • Page 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 3: Table Of Contents

    Adding excom I/O modules to the AC 800M ............ 27 Setting excom I/O module parameters .............. 29 Configuring I/O data .................... 31 Loading the current configuration into the AC 800M ...........  34 Online mode ........................ 35 Turck subsidiaries — contact information..................  36 V01.00 | 2022/06...
  • Page 4 Contents Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 5: About This Manual

    This symbol denotes actions that the user must carry out. RESULTS OF ACTION This symbol denotes relevant results of actions. Other documents Besides this document the following material can be found on the Internet at www.turck.com: Data sheets Quick start guide excom manuals...
  • Page 6: Notes On The System

    CAD files in numerous export formats. The contact details of Turck subsidiaries worldwide can be found on p. [} 36]. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 7: For Your Safety

    The product is designed according to state-of-the-art technology. However, residual risks still exist. Observe the following warnings and safety notices to prevent damage to persons and property. Turck accepts no liability for damage caused by failure to observe these warning and safety notices.
  • Page 8: Integrating An Excom System In Abb Compact Control Builder M

    AOH40EX analog output module PROFIBUS-DP cable DM80EX GDP-IS/FW2.3 DO40EX AIH40EX AOH40EX PSM24-3G.1 MT08-3G Fig. 1: Example setup of the excom station Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 9: Software Requirements

    GSD communication file V1.6.4 Turck software Gateway firmware V2.3 Installing a GSD configuration file The GSD file can be downloaded as a free Zip file from www.turck.com. „ Unpack the zip file. Adding a GSD configuration file to the library Proceed as follows to install the GSD file: „...
  • Page 10 Right-click Hardware Types. „ Click Insert/Replace Hardware Type(s)…. Fig. 4: Hardware Types – Insert/Replace Hardware Type(s)… The Insert Hardware Definitions window opens. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 11: Defining The Gsd Signal

    „ Select the *.gs? file type in the drop-down menu. „ Select the T164FF9F.GSD GSD configuration file. „ Click Open. Fig. 5: Selecting the GSD configuration file Defining the GSD signal Once the GSD configuration file has been selected, the Device Import Wizard opens. „...
  • Page 12 At to be used in the system select DefaultIOType in the drop-down menu. „ Click Next. Fig. 7: Selecting the DefaultIOType Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 13 The PROFIBUS GSD file import - Module selection window opens. „ Click Select all. „ Click Next. Fig. 8: PROFIBUS GSD file import - Module selection window V01.00 | 2022/06...
  • Page 14 If one or several modules have a red tick: Check whether the parameter settings of two configurations are the same. „ Click Next. Fig. 9: All modules defined Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 15: Setting Gsd Signals For Individual Modules

    4.3.1 Setting GSD signals for individual modules The settings for the I/O signals of the modules are stated in the system description for the excom I/O system at www.turck.com. Example: AIH40 1H „ In the PROFIBUS GSD file import – I/O settings window, select the AIH40 1H module in the left sidebar.
  • Page 16 Fig. 12: Selecting Bit Boolean =>Bool in the drop-down menu „ Configure the other three channels with the remaining bits following the same procedure. Click OK. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 17 The HART variable consists of Bytes 8…11. „ Select Byte 8…11 at Input area. „ The drop-down menu opens automatically. Select Real 32=>Real. Fig. 13: AIH40 1H – all channels and HART variables are set V01.00 | 2022/06...
  • Page 18 In the PROFIBUS GSD file import – I/O settings window, select the AOH40 module in the left sidebar. „ Click Customize output under Manual configuration to manually configure the module. Fig. 14: Manually configuring AOH40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 19 „ Select 15 bits for channel 1 in the PROFIBUS GSD file import – Out area of AOH40 window at Output area. In this example, Bit 0…6 of Byte 0 and Bit 0…7 of Byte 1. „ The drop-down menu opens automatically. Select UInt 16=>DInt. Fig. 15: Selecting UInt 16=>DInt in the drop-down menu „...
  • Page 20 Click Customize input or Customize output under Manual configuration to manually configure the module as required. Fig. 17: Manually configuring DM80 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 21 „ Select Bit 0 for channel 1. „ The drop-down menu opens automatically. Select 8X Bit Boolean. Fig. 18: Selecting 8X Bit Boolean in the drop-down menu „ Each bit can be set as an individual channel. The DM80 S module is provided with an additional status bit for each channel.
  • Page 22 In the PROFIBUS GSD file import – I/O settings window, select the DO40_ module in the left sidebar. „ Click Customize output under Manual configuration to manually configure the module. Fig. 20: Manually configuring DO40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 23 „ Select Bit 0…3. „ The drop-down menu opens automatically. Select 4X Bit Boolean. Fig. 21: Selecting 4X Bit Boolean in the drop-down menu Each bit can be set as an individual channel. Fig. 22: DO40 – all channels are set V01.00 | 2022/06...
  • Page 24: Gsd Signals - Setting Diagnostics

    If the Diagnostics pattern confirmation/edit appears, use the default settings and click Fig. 23: PROFIBUS GSD file import – Diagnostics settings Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 25 „ In the PROFIBUS GSD file import – Diagnostics settings window, select the module in the left sidebar. „ Under the required module select (here: AIH40 1H) ChannelDiagCommon. The different diagnostics data is shown in the Text column. The diagnostics are assigned to a variable in the Status bit column.
  • Page 26 The diagnostics settings are applied to all modules. „ In the system description for the excom I/O system check which diagnostics information is transferred. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 27: Adding Excom I/O Modules To The Ac 800M

    Adding excom I/O modules to the AC 800M Inserting the GSD configuration file in the AC 800M „ Right-click the PROFIBUS controller (here: NEWTON CI854) in ABB Compact Control Builder AC 800M. The Insert UNIT for CI854 window opens. „ Right-click excom (1_6_4).
  • Page 28 Set up the excom station according to the physical setup. Note the corresponding position on the rack (here: GDP C – Position: 0). „ Click Insert. Fig. 28: Example: GDP C – position 0 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 29: Setting Excom I/O Module Parameters

    Setting excom I/O module parameters Ò „ In Control Builder AC 800M at Controllers excom (1_6_4) select the module (here: GDP C). „ Right-click the module. „ Click Editor. The Hardware – PLC_1.1.5.0 window opens. Fig. 29: Selecting a module V01.00 | 2022/06...
  • Page 30 The different parameters can be viewed in the Parameter column. The values of the parameters can be set at Value. Fig. 30: Example setting of gateway parameters Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 31: Configuring I/O Data

    Configuring I/O data Ò „ Choose Turck_Test Applications. „ Right-click Diagrams at Application_1 – (PLC_1.Normal). „ Click New Diagram…. Fig. 31: Diagrams – New Diagram… V01.00 | 2022/06...
  • Page 32 In the Data Type column set the data type that was selected at the GSD signal import. Fig. 32: Variables – setting a data type Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 33 Module editor Ò „ In ABB Compact Control Builder AC 800M at Controllers excom (1_6_4) select the module (here: AIH40 1H). „ Right-click the module. „ Click Editor. The Hardware – PLC_1.1.5.0 window opens. „ Click the Connections tab. „ Select the required variable via the Insert Path from Tree icon and assign it to the channel.
  • Page 34: Loading The Current Configuration Into The Ac 800M

    The Compact Control Builder AC 800M - Turck_Test (Online) window opens. Fig. 35: Compact Control Builder AC 800N - Turck_Test (Online) window Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 35: Online Mode

    Online mode After the download, the view switches to Online mode. In Online mode, the diagnostics information and read data can be read in the modules used. In this example Input 1, Input 3, Input 5 and Input 7 represent the measured input current. Input 1 and Input 3 also represent the substitute value.
  • Page 36: Turck Subsidiaries - Contact Information

    Turck Banner Malaysia Sdn Bhd Unit A-23A-08, Tower A, Pinnacle Petaling Jaya, Jalan Utara C, 46200 Petaling Jaya Selangor www.turckbanner.my Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
  • Page 37 Mexico Turck Comercial, S. de RL de CV Blvd. Campestre No. 100, Parque Industrial SERVER, C.P. 25350 Arteaga, Coahuila www.turck.com.mx Netherlands Turck B. V. Ruiterlaan 7, NL-8019 BN Zwolle www.turck.nl Austria Turck GmbH Graumanngasse 7/A5-1, A-1150 Wien www.turck.at Poland TURCK sp.z.o.o.