6.10 APM802 Controllers only. For the user-defined
digital inputs 1 to 5 on the RSA III, use the
controller digital inputs connections located on
TB10.
After the RSA III installation is complete,
these digital inputs are selected with SiteTecht
software
under the Product Connection Inputs
menu. Refer to the wiring diagram manual to
determine the connections on TB10 and
Figure 45
to
determine
designations.
Digital Inputs
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Digital Input 9
Digital Input 10
Digital Input 11
Digital Input 12
Digital Input 13
Digital Input 14
Digital Input 15
Digital Input 16
Figure 45 Digital Inputs on APM802 Controller
6.11 DEC 550 and DEC 6000 Controllers only. The
RSA III user inputs 1--3, when in the remote
connection, are tied to the controller digital
inputs. See Figure 46.
If required, the user-input selection tied to digital
inputs D7, D8, and/or D10 can be changed using
Menu 9, Input Setup. Refer to the DEC 550
(TP-6200) or DEC 6000 (TP-6750) controller
operation manual as needed.
RSA III User Inputs
(Remote)
1
2
3
Figure 46 RSA III Remote User Inputs with DEC 550
and DEC 6000 Controllers
TT-1625 7/17
the
digital
input
Designation
Low Fuel Level Switch
Breaker Open Status
Remote Reset
Aux Shutdown
High Fuel Level Switch
Aux Warning
Low Oil Level
Battery Charger Fault
Fuel Leak Alarm
Idle Mode
GFCI Tripped
Remote Speed Adjust Enable
Key Switch Enable
Load Shed Enable
Overcrank Test
Reserved for Factory Use
Tied to DEC 550 and 6000
Controller Digital Inputs
D7
D8
D10
6.12 DEC 8000
Controllers
user-defined digital inputs 1 to 5 on the RSA III,
use the controller binary inputs connections
located on
the customer connection block,
After the RSA III installation is complete, these
digital inputs are selected with SiteTecht
software
under the Product Connection Inputs
menu. Refer to the wiring diagram manual to
determine the connections on TB1 and to
Figure 47
to
determine
designations and functionality.
Binary Inputs
Binary Input 1
Binary Input 2
Binary Input 3
Binary Input 4
Binary Input 5
Binary Input 6
Binary Input 7
Binary Input 8
Figure 47 Binary Inputs on DEC 8000 Controller
6.13 Document the user-selected inputs for future
reference. If user-selected inputs 1 to 5 (remote)
are used, the user may add the identification on
the RSA III front panel strip.
permanent marker on the respective white blank
box to identify the user input. The user can also
fill in the generator ID location information if
needed.
Allow the marker ink to dry before
handling the RSA III front panel.
Other methods for adding the information to the
identification strip would be to use a PC and print
the information on an adhesive label or use a
label maker. The print font on the RSA III front
panel is Myriad bold 10 point. Attach the printed
label(s) to the white blank boxes on the RSA III
front panel.
only.
For
the
TB1.
the
binary
input
Default Definitions
Auxiliary Fault Shutdown
Auxiliary Warning --
Always/Anytime
Auxiliary Warning --
Running Only
Low Coolant Level
Ground Fault Detected
Remote Fault Reset
Remote Generator Circuit
Breaker Button (close/trip)
Auxiliary Slow Stop
Use a black
27