Temperature Measuring Ranges And Measuring Accuracies With External Cold Junction Compensation; Voltage Measuring Ranges And Measuring Accuracies; Table 14: Technical Data - Temperature Measuring Ranges And Measuring; Table 15: Technical Data - Voltage Measuring Ranges And Measuring - WAGO 750 Series Manual

I/o system 8ai; tc; adjust 8-channel analog input; thermocouple; adjustable
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

WAGO I/O SYSTEM 750
750-498 8AI; TC; Adjust
3.6.4.2
Temperature Measuring Ranges and Measuring Accuracies with
External Cold Junction Compensation
Mounting position and air movement have no impact on the measurement
accuracy.
Table 14: Technical Data ‒ Temperature Measuring Ranges and Measuring Accuracies with External
Cold Junction Compensation for the all Mounting Positions
Sensor Type Temperature Range
B
C
E
J
K
N
R
T
S
3.6.4.3

Voltage Measuring Ranges and Measuring Accuracies

Mounting position and air movement have no impact on the measurement
accuracy.
Table 15: Technical Data ‒ Voltage Measuring Ranges and Measuring Accuracies for all Mounting
Positions
Measuring Range
−30 mV ... +30 mV
−60 mV ... +60 mV
−120 mV ... +120 mV
−240 mV ... +240 mV
*)
URV = upper-range value
+200 °C ... +600 °C
+600 °C ... +1820 °C
0 °C ... 1100 °C
1100 °C ... +2315 °C
−200 °C ... −100 °C
−100 °C ... +1000 °C
−210 °C ... −50 °C
−50 °C ... +1200 °C
−200 °C ... −50 °C
−50 °C ... +1370 °C
−200 °C ... −100 °C
−100 °C ... +1300 °C
−50 °C ... 250 °C
250 °C ... +1768 °C
−200 °C ... 0 °C
0 °C ... +400 °C
−50 °C ... 250 °C
250 °C ... +1768 °C
Device Description
Measuring Accuracy
≤ ±3.3 K
≤ ±1.2 K
≤ ±0.8 K
≤ ±1.6 K
≤ ±0.6 K
≤ ±0.8 K
≤ ±0.6 K
≤ ±0.2 K
≤ ±0.8 K
≤ ±0.5 K
≤ ±1.1 K
≤ ±0.5 K
≤ ±2.9 K
≤ ±0.8 K
≤ ±0.8 K
≤ ±0.3 K
≤ ±2.5 K
≤ ±0.8 K
Measuring Accuracy
≤ ±0,06 % of URV
≤ ±0,05 % of URV
≤ ±0,05 % of URV
≤ ±0,04 % of URV
29
Manual
Version 1.0.0