WAGO I/O SYSTEM 750
750-498 8AI; TC; Adjust
Table 47: Behavior in the Event of an I/O Module Error Dependent on the Configuration
Configuration
Wire break
monitoring
OFF
OFF
On
ON
The limiting values for detecting an underrange / overrange, a wire break or a
limiting value underrange / overrange and the output process values are
specified in the process image tables (see section "Process Image").
A general error signals a diagnosed error status. A general error is displayed if
one or more of the error status named in this section occur or other internal error
statuses for the I/O module are present.
Note how long diagnostics are displayed!
A diagnosed error status is displayed at least 100 ms even if the detected error
status is no longer present in this period. If a higher-priority error status occurs in
this period, the higher-priority error status is displayed for 100 ms and the lower-
priority error status is lost.
I/O module behavior for
Underrange/
range violation
overrange
monitoring
Process value is saturated,
OFF
no change in statues byte,
error LED off
Process value is saturated,
error bit (bit 0: Underrange or
bit 1: Overrange),
ON
general error (bit 6: General
Error) is set,
error LED ON
Process value is saturated,
OFF
no change in statues byte,
error LED off
Process value is saturated,
error bit (bit 0: Underrange or
bit 1: Overrange) is set,
ON
general error
bit 6: General Error) is set,
error LED ON
Diagnostics
85
I/O module behavior for
wire break
Process value is saturated,
no change in statues byte,
error LED off
Process value is saturated,
error bit (bit 1: Overrange),
general error (bit 6: General
Error) is set,
error LED ON
Process value is saturated,
error bit (bit 5: Wire Break) is
set, general error (bit 6:
General Error) is set,
error LED ON
Process value is saturated,
error bit (bit 5: Wire Break) is
set,
general error (bit 6: General
Error) is set,
error LED ON
Manual