3. SIGNALS AND WIRING

3.7 Input power supply circuit

CAUTION
www.DataSheet4U.com

3.7.1 Connection example

Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as alarm
occurrence is detected and power is shut off.
A circuit breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
3-phase
200 to 230 VAC
Note. To use the built-in regenerative resistor, be sure to connect across P and D of the power supply connector (CNP1).
Always connect a magnetic contactor (MC) between the main circuit power supply
and L
L
and L
of the servo amplifier, and configure the wiring to be able to shut
,
,
1
2
3
down the power supply on the side of the servo amplifier's power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
Use the trouble (ALM) to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
POINT
The power supply connector (CNP1) is optional. Purchase it without fail.
Emergency
stop
OFF
NFB
MC
(Note)
Emergency stop
Servo-on
ON
MC
RA
MC
SK
CNP1
Servo amplifier
L
1
L
2
L
3
P
D
C
EMG
SON
VIN
VIN
ALM
SG
3 - 34
External
power
Trouble
supply
RA
24VDC