Line 2 Cellular Test
Check this box to indicate that Line 2 dials a cell phone. Use the Spin box to specify
the day of the month (1 - 28) for the cell phone test.
Auto test at
Use this spin box to set the time for a daily test of land lines.
Dialer
Line Retries
Use this Spin Box to specify the number of retries to make (5-10)
Rings
Use this Spin box to specify the number of rings when dialing in to configure.
Warning: if set to zero the next dial in session will not be able to connect.
Mode
Choose between DACT and UDACT
Enable
Uncheck this box if you wish to set the dialer to the disabled state when you send the
job to the panel. If you receive a job from the panel when the dialer was temporarily
disabled then this check box will be un-checked. The dialer is enabled by default.
Aux disconnect
If enabled, the dialer will block the alarm and supervisory events from being reported
after the auxiliary disconnect button is pressed.
Advanced Addressing
In order to report Node address, Loop address and device address through UDACT,
we will need to use Advanced Addressing method which supports larger range of
device addresses.
99
Need help?
Do you have a question about the FleX-Net and is the answer not in the manual?
Questions and answers