Input Zones - Mircom FleX-Net Configurator Manual

Network intelligent fire alarm and audio system
Hide thumbs Also See for FleX-Net:
Table of Contents

Advertisement

Tag
The Tag label assigned to the device.

Input Zones

The list view displays the Input Zones. Input Zones are used to combine multiple input
circuits into zones which can then be correlated to signals and other outputs and to display
LEDs, etc.
Some columns containing advanced or internal information are normally hidden. They are
listed as Visible / No in the following table. Other columns are conditionally visible.
Name
Visible
Addr
No
Lp
No
Lp Addr No
Ckt No
No
Ckt No
No
CPU
Device
Yes
Type
Yes
SubType Yes
Priority Yes
Description
A sequentially assigned zone address. Allocated for consistency with
other loop types.
Loop Number. Not meaningful for zones
A sequentially assigned zone number or address.
An internal, sequentially assigned number.
An internal, sequentially assigned number: the CKT_NO within the
CKT_IPT_ZONES.
Always Input Zone.
The process Type (Alarm, etc.) of the Zone. Can be edited (combo box).
Additional refinement of the type. Always has a value of "None" for
Input Zones.
Specifies the priority to be given to digitized messages correlated to this
input zone. Choose from a range or priorities. -19 (lowest) through
Normal (default) to +19 (Highest). Activation of a zone with a higher
priority will cause its message to be played, and any lower priority
message will cease to play.