Node Tel Call
020
In
Alm Relay
021
Active
Spv Relay
022
Active
Trb Relay
023
Active
Node PTT
024
Pressed
025
Page Ready
Pre-Tone
026
Active
Microphone
027
Trouble
Node Amp
028
Trouble
031
Pretone Active Set to TRUE pre-tone is sounding on this node.
032
Latched Relays
Running a
033
Walktest
This status is TRUE when telephone is off hook, or when a user at a
Master Telephone presses Call Control.
Set to TRUE when the alarm relay on this node is active. The alarm
relay is active when there is an alarm on any of this node's
connected CPUs.
Set to TRUE when the supervisory relay on this node is active. The
supervisory relay is active when there is an active supervisory on
any of this node's connected CPUs.
Set to TRUE when the supervisory relay on this node is active. The
supervisory relay is active when there is an active supervisory on
any of this node's connected CPUs.
Set to TRUE of the PTT (Press To Talk) button is depressed on the
master telephone of this node.
Set to TRUE if the Audio Controller on this node is ready to page.
Set to TRUE when the pre-tone is playing on the Audio Controller
on this node.
Set to TRUE if any of the microphones on this node are in trouble.
Set to TRUE if any of the amplifiers on this node have a trouble
condition.
Set to TRUE if there are relays on this node that are latched and
awaiting a system reset or auxiliary reset.
Walktest in progress on this node.