SR - System Reset required - used on Switches used for Fan control
NF - No LED Activation - do not turn ON an addressable device's LED (and
activate sounder when present) when the device is active. The LED turn ON by
default and may only be changed to NF if the Authority Having Jurisdiction
allows.
Sens Columns
Sensitivity level for COSAP provides 6 levels of sensitivity, which are categorized as below:
Alarm 1 - Level 1 - 1%/ft of smoke. No delays from processed photo output.
Alarm 2 - Level 2 - 2%/ft of smoke. No delays from processed photo output.
Alarm 3 - Level 3 - 3%/ft of smoke. No delays from processed photo output.
Alarm 4 - Level 4 - 3%/ft of smoke. Maximum of 10 minutes delay from
processed photo output.
Alarm 5 - Level 5 - 4%/ft of smoke. Maximum of 10 minutes delay from
processed photo output.
Alarm 6 - Level 6 - Heat only alarm. If the heat level limits.
Once the CO cell has reached its end of life, and enters PTIR mode, the following
sensitivities apply:
Alarm 1 - Level 1 - 1%/ft of smoke. No delays from processed photo output.
Alarm 2 - Level 2 - 2%/ft of smoke. No delays from processed photo output.
Alarm 5 - Level 5 - 3%/ft of smoke. Time elapsed from smoke detection is
Alarm 6 - Level 6 - Heat only alarm. If the heat level on either thermistor
exceeds 1 limits.
CO Operation - CO Operation - CO only alarm.
Address Scheme
The configurator currently uses a sophisticated addressing scheme designed to avoid
conflicts with virtual devices. The different types of adder are described in the Address
Scheme.
113

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FleX-Net and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Flex-net fx-4000Fx-mns-6000

Table of Contents

Save PDF