Frame
No
LED
No
Sw
No
LedGrp
No
Type
Yes
Assignment Yes
Node
Yes
Group
Priority
Yes
when Paste Special is used. The linked items can be viewed with the
Linked Items dialog.
The Frame Number. An adder may contribute several frames to an
annunciator. The frame numbers are zero based.
The number (zero based) of the first LED of a logical group. For
example, an HOA adder has three LEDs per slide switch. This column
would show 0 for Idx 0, 3 for Idx 1, etc. Due to the way some adders
are arranged (hardware) the LED numbers are in irregular
sequences.
The Switch number (if any) associated with the Idx.
An internal number, allocated when a LED is assigned a role other
than un-assigned. In the case of Linked Items, multiple LEDs can
share the same LedGrp and hence the same LED Definition,
behavior and correlations.
Initially unassigned this is the Type of display item. The values in the
combo box depend on the Adder/Frame type.
Dependent on the Type.
Applies only to common control switches. The column displays the
Node Group to which the common control operation is to be
limited. Global means that the operation is system wide and is the
default. If the user has created Node Groups, then one of those
groups can be chosen. The common control then applies only to the
member nodes of that group.
In a combined fire and Mass Notification System (M.N.S.)
installation where Node Grouping is used to separate the M.N.S.
nodes of from those nodes supporting fire, limit the common
controls to the appropriate group.
Specifies the priority to be given to digitized messages correlated to
correlatable switches. Choose from a range or priorities. -95%
(lowest) through Normal (default) to +95% (Highest). Activation of a
101