037
**-**-**-ST-037
038
**-**-**-ST-038
039
**-**-**-ST-039
040
**-**-**-ST-040
041
**-**-**-ST-041
042
**-**-**-ST-042
043
**-**-**-ST-043
044
**-**-**-ST-044
045
**-**-**-ST-045
This status is set to TRUE if the conditions which
Trbl Buzzer
would cause the buzzer to sound at the trouble rate
are true.
This status is set to TRUE if the alarm buzzer is
Alm Buzzer
currently silenced. The buzzer resounds, and the
Silence
status goes to FALSE if there is a new alarm, if the
system is reset or if the alert resound timer expires.
This status is set to TRUE if the supervisory buzzer is
Supv
currently silenced. The buzzer resounds, and the
Buzzer
status goes to FALSE if there is a new supervisory
Silence
alarm, if the system is reset or if the alert resound
timer expires.
This status is set to TRUE if the trouble buzzer is
Trb Buzzer
currently silenced. The buzzer resounds, and the
Silence
status goes to FALSE if there is a new trouble, if the
system is reset or if the alert resound timer expires.
Relay Auto
Set to TRUE when any of this job's nodes have their
Test Active
"Relay Auto Test Active" status equal to TRUE.
Ground
Set to TRUE if there is a ground fault (positive or
Fault
negative) on any of the job's nodes.
This status is TRUE if the job was configured (or set
Auto
through the menu) to automatically change
Day/Night
between "prime time" and "after hours"
This status is TRUE if the job was configured (or set
through the menu) to automatically change
Off Hours
between "prime time" and "after hours" and the
current system time lies within the configured after
hours times.
Pre-alarm
Set to TRUE when any of this job's nodes have their
active
"Pre-alarm" status equal to TRUE.