Chapter 2 Installing, Removing and Connection
Grounding
2.5
2.5.1
Caution for grounding
■ Single grounding
■ Insulation from building
■ Circuit grounding and cabinet grounding
■ External signal cable
2.5.2
Grounding electrode
Prepare a grounding electrode exclusive to this system. Ground resistance must
be 100 or less (equivalent to Class D grounding).
38
6F8C1388
This unit should be grounded singly. Mixed grounding with other devices may
cause malfunction.
Insulate the cabinet from the building to prevent the noise current flowing in
the building from adversely affecting it.
Separate the N line (0V) of the power supply from the frame grounding wire.
Also, connect the frame grounding wiring to the grounding terminal at one
point.
Connect the shielding wire of a multi-core cable to the shield processing
terminal at the cabinet inlet. Wiring inside the cabinet should be free of
shielding wire, if possible, to save space and to ensure a sufficient cable
bending radius.