No.
880E
IP address overlap
Major
error
failure
880F
IP address setting
Major
error
failure
8E01
Battery error
Minor
status
failure
8E81
Recovery from
Recovery
battery error status
from
error
9100
User task stop
Major
illegal instruction
failure
detected
9101
Task stall occurred Major
failure
9102
User task stop
Major
boundary over
failure
9104
User task stop
Major
POU No.
failure
undefined
9106
User task stop
Major
operation stack
failure
error
Timing
Exec
Remark
Executed Error
IP address is
rundown
overlapping.
Executed Error
IP address is out of
rundown
range.
Periodic
Continued Battery error (voltage
diagnosis
drop) or no installation
is detected.
Periodic
Continued Recovered from
diagnosis
battery error (voltage
drop) or
non-installation
Executed Error
An instruction
rundown
undefined in user
program was detected.
Executed Error
Execution of main
rundown
scan is stalling or
stopped.
Executed Error
Execution occurred
rundown
over memory
boundary of user
program.
Executed Error
Function (block) could
rundown
not be found.
Executed Error
Operation stack input
rundown
count and output count
do not match.
Table D-1 Error log (3/7)
Task Address
Aux1
Aux2
Aux3
IP
IP
IR
(absolute)
(relative)
Status
Task stall
type
IP
IP
IR
(absolute)
(relative)
IP
IP
IR
(absolute)
(relative)
IP
IP
IR
(absolute)
(relative)
Cause
Maintenance
Device with same IP
Check the IP address setting
address exists on
(rotary switch) and set the correct
network.
IP address.
IP address is not in
Check the IP address setting
specified range
(rotary switch) and set the correct
(1-254).
IP address.
Expired battery life or
Replace the battery.
battery not installed
Do not turn off the power while
replacing the battery. Memory
may get lost.
Use of unsupported
Check if any unsupported
instruction or code
instruction is used.
memory error
If any unsupported instruction is
used, modify the user program. If
not, execute Memory Clear and
Batch DL, and restart the system.
Setting time of main
Review of the scan cycle setting
or review of the program is
scan is much smaller
required.
than program
execution time, or
infinite loop occurred
in part of program.
Memory failure
Execute Memory Clear and Batch
DL, and restart the system.
Function (block) does
If the POU number is wrong,
not exist or POU
modify the user program.
number is wrong.
If the function (block) does not
exist, add the function (block), and
download it again.
Compile is not normal. Compile the program, and
download it again.