Toshiba LC531 Series Instruction Manual page 166

Single-loop controller
Table of Contents

Advertisement

Event
Trace Contents
Level
Timing
No
9138
Program DL error
Caution Executed Continued Code memory could
(2)
9139
Program DL error
Caution Executed Continued EA memory could not
(3)
913A
Program DL error
Caution Executed Continued Memory for copy
(4)
9300
Total control stop
Major
Executed Error
failure
9820
Transmission
Major
Executed Error
process
failure
initialization error
Table D-1 Error log (6/7)
Exec
Remark
Task Address Aux1
not be reserved.
be reserved.
command (local
instance) could not
be reserved.
Total control is in
rundown
congestion.
Error was detected in
rundown
initialization of
transmission process
(PCMP).
Aux2
Aux3
Cause
Insufficient free
If it occurred at batch DL, the amount
memory area
of instances used in the user
program exceeds memory capacity.
Check the user program again.
If it occurred at online DL, organize
memory by packing, and download
the program again.
RAM memory failure
If it does not recover from the error
after performing download again,
replace the CPU module and restart
the system,
Memory Clear and Batch DL.
RAM memory failure
If it does not recover from the error
after performing download again,
replace the CPU module and restart
the system,
Memory Clear and Batch DL.
Hardware failure
Reset the error and restart the
system.
If it does not recover, replace the
CPU module and restart the system.
After
execute Memory Clear and Batch
DL.
Start process of
Reset the error and restart the
transmission process
system. If it does not recover,
(PCMP) is congested.
replace the CPU module and restart
the system.
After replacing CPU module,
execute Memory Clear and Batch
DL.
Maintenance
and
then execute
and
then execute
replacing
CPU
module,