Toshiba LC531 Series Instruction Manual page 162

Single-loop controller
Table of Contents

Advertisement

Event
Trace
Level
Timing
No
Contents
8113
Memory
Major
Periodic
erased
failure
diagnosis
8119
User
Major
Initial
information DL
failure
diagnosis
error
8120
Packing
Caution
Executed
process
aborted(1)
8121
Packing
Caution
Executed
process
aborted(2)
8122
Packing
Caution
Executed
process
aborted(3)
8802
MAC address
Major
Executed
error
failure
8803
Ethernet initial
Major
Executed
diagnosis error
failure
Table D-1 Error log (2/7)
Exec
Remark
Task
Address
Error
Loss of memory
rundown
data in user data
area was
detected.
Error
Error was
Error
rundown
detected when
address
user information
was read from
flash ROM.
Continued Insufficient
instance
memory was
detected.
Continued Insufficient entry
code memory
was detected.
Continued Insufficient POU
code memory
was detected.
Error
MAC address
rundown
value is
abnormal.
Error
Ethernet
rundown
initialization
failed.
Aux1
Aux2
Aux3
Battery error or
being left without
battery. Or RAM
memory faulty.
Flash ROM or RAM
memory faulty
Block No. Number of
Entry serial No.
Insufficient capacity
blocks
(0 to 308)
in consecutive free
memory areas
Block No. Number of
Entry serial No.
Insufficient capacity
blocks
(0 to 308)
in consecutive free
memory areas
Block No. Number of
POU No.
Insufficient capacity
blocks
(0 to 2047)
in consecutive free
memory areas
MAC read error or
MAC chip error
Error in Ethernet
peripheral circuit
Cause
Maintenance
Replace the battery, then execute
Memory Clear and Batch DL and
restart the system. If it does not
recover from the error, replace the
CPU module and restart the system.
After replacing CPU module, execute
Memory Clear and Batch DL.
Execute Memory Clear and Batch DL
and restart. If it does not recover from
the error, replace the CPU module
and restart the system.
After replacing CPU module, execute
Memory Clear and Batch DL.
Execute Memory Clear and Batch DL
and restart.
Execute Memory Clear and Batch DL
and restart.
Execute Memory Clear and Batch DL
and restart.
Turn on the power again and restart
the system. If not starting up normally,
replace the CPU module and restart
the system.
After replacing CPU module, execute
Memory Clear and Batch DL.
Turn on the power again and restart
the system. If not starting up normally,
replace the CPU module and restart
the system.
After replacing CPU module, execute
Memory Clear and Batch DL.

Advertisement

Table of Contents
loading