SPECIFICATIONS
98
S-Series
PUMY-SP YKMD-A(-BS)
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input A
COP
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
Current input A
COP
Temp. range of
Indoor
heating
Outdoor
Indoor unit
Total capacity
connectable
Model/
Quantity
Sound pressure level
(measured in anechoic room)
Refrigerant piping
Liquid pipe
diameter
Gas pipe
Fan
Type × Quantity
Airflow rate
Motor output kW
Compressor
Type × Quantity
Starting method
Motor output kW
External finish
External dimension H × W × D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Net weight
Heat exchanger
Defrosting method
Optional parts
Notes:
*1,*2 Nominal conditions
Cooling
Heating
*3 10 to 52°C(D.B.): When connecting following models such as PKFY-P10/15/20/25/32VLM, PFFY- P20/25/32VLE(R)M, PFFY-P20/25/32VKM, and M series, S series, and P series type indoor unit.
*4 −15 to 52°C(D.B.): When using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit listed in *3.
*5 95 (209), for PUMY-SP80/112/125/140YKMD-A-BS.
*Nominal conditions *1,*2 are subject to ISO 15042.
*Due to continuing improvement, above specifications may be subject to change without notice.
PUMY-SP80YKMD-A(-BS)
3-phase 380-400-415 V, 50 Hz;
3-phase 380 V, 60 Hz
*1 kW
*1 Btu/h
kW
3.37-3.21-3.09
kW/kW
W.B.
15 to 24°C (59 to 75°F)
D.B.
-5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F) -5 to 52°C *3,*4 (23 to 126°F)
*2 kW
*2 Btu/h
kW
3.63-3.45-3.32
kW/kW
D.B.
15 to 27°C (59 to 81°F)
W.B.
-20 to 15°C (-4 to 59°F)
50 to 130% of
outdoor unit capacity
CITY MULTI
Branch box
Mixed
Branch box
CITY MULTI P10-P100
system
1 unit
Branch box P22-P100
Branch box
CITY MULTI P10-P100
2 units
Branch box P22-P100
dB <A>
mm (inch)
9.52 (3/8) Flare
mm (inch)
15.88 (5/8) Flare
Propeller Fan × 1
m³/min
L/s
cfm
Twin rotary hermetic
compressor × 1
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
mm
981 × 1,050 × 330 (+25)
inch
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
Overcurrent detection, Overheat
detection(Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage
R410A × 3.5 kg (8 lb)
kg (lb)
Cross Fin and Copper tube Cross Fin and Copper tube Cross Fin and Copper tube Cross Fin and Copper tube
Reversed refrigerant circuit Reversed refrigerant circuit Reversed refrigerant circuit Reversed refrigerant circuit
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Indoor
Outdoor
27ºC DB/19ºC WB
35ºC DB(95ºF DB)
(81ºF DB/66ºF WB)
20ºC DB(68ºF DB)
7ºC DB/6ºC WB(45ºF DB/43ºF WB)
PUMY-SP112YKMD-A(-BS)
3-phase 380-400-415 V, 50 Hz;
3-phase 380 V, 60 Hz
9.0
12.5
30,700
42,700
2.11
3.10
4.96-4.71-4.54
4.27
4.03
15 to 24°C (59 to 75°F)
10.0
14.0
34,100
47,800
2.27
3.17
5.07-4.82-4.64
4.41
4.42
15 to 27°C (59 to 81°F)
-20 to 15°C (-4 to 59°F)
50 to 130% of
outdoor unit capacity
P10-P100/9
P10-P140/12
P22-P80/5
P22-P100/7
5
4
2
P10-P140
5
2
3
4
P22-P100
4
3
2
P10-P140
3
3
4
P22-P100
5
51/54
52/54
9.52 (3/8) Flare
15.88 (5/8) Flare
Propeller Fan × 1
75/75
77/75
1250/1250
1283/1250
2649/2649
2719/2649
0.20 × 1
0.20 × 1
Twin rotary hermetic
compressor × 1
Inverter
Inverter
2.1
3.1
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
981 × 1,050 × 330 (+25)
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
Overcurrent detection, Overheat
detection(Heat sink thermistor)
Compressor thermistor,
Overcurrent detection
Overheating, Voltage
protection
protection
R410A × 3.5 kg (8 lb)
94 (207) *5
94 (207) *5
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Pipe length
Level diff erence
7.5m (24-9/16ft.)
7.5m (24-9/16ft.)
PUMY-SP125YKMD-A(-BS)
PUMY-SP140YKMD-A(-BS)
3-phase 380-400-415 V, 50 Hz;
3-phase 380-400-415 V, 50 Hz;
3-phase 380 V, 60 Hz
3-phase 380 V, 60 Hz
14.0
47,800
3.84
6.14-5.83-5.62
7.00-6.65-6.41
3.65
15 to 24°C (59 to 75°F)
15 to 24°C (59 to 75°F)
16.0
54,600
3.90
6.24-5.93-5.71
6.43-6.11-5.89
4.10
15 to 27°C (59 to 81°F)
15 to 27°C (59 to 81°F)
-20 to 15°C (-4 to 59°F)
-20 to 15°C (-4 to 59°F)
50 to 130% of
50 to 130% of
outdoor unit capacity
outdoor unit capacity
P10-P140/12
P10-P140/12
P22-P100/8
P22-P100/8
4
P10-P140/5
P10-P140/5
5
P22-P100/5
P22-P100/5
2
P10-P140
3
2
P10-P140
6
P22-P100
6
7
P22-P100
53/56
9.52 (3/8) Flare
9.52 (3/8) Flare
15.88 (5/8) Flare
15.88 (5/8) Flare
Propeller Fan × 1
Propeller Fan × 1
81/83
1350/1383
2861/2931
0.20 × 1
Twin rotary hermetic
Twin rotary hermetic
compressor × 1
compressor × 1
Inverter
3.5
Galvanized Steel Sheet
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
Munsell No. 3Y 7.8/1.1
981 × 1,050 × 330 (+25)
981 × 1,050 × 330 (+25)
38-5/8 × 41-3/8 × 13 (+1)
38-5/8 × 41-3/8 × 13 (+1)
High pressure Switch
High pressure Switch
Overcurrent detection, Overheat
Overcurrent detection, Overheat
detection(Heat sink thermistor)
detection(Heat sink thermistor)
Compressor thermistor,
Compressor thermistor,
Overcurrent detection
Overcurrent detection
Overheating, Voltage
Overheating, Voltage
protection
R410A × 3.5 kg (8 lb)
R410A × 3.5 kg (8 lb)
94 (207) *5
Joint: CMY-Y62-G-E
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Header: CMY-Y64/68-G-E
0m (0ft.)
0m (0ft.)
15.5
52,900
4.38
3.54
16.5
56,300
4.02
4.10
3
2
7
8
54/56
81/83
1350/1383
2861/2931
0.20 × 1
Inverter
3.7
protection
94 (207) *5