Mitsubishi Electric Y Series Manual page 247

Hide thumbs Also See for Y Series:

Advertisement

B.S. Salt Protection Specifications
City Multi VRF Outdoor Units
Name
Base material
Alloyed galvanized
Bottom frame
sheet
Front panel
Galvanized sheet
Alloyed galvanized
Pillar
sheet
Compressor cover
Galvanized sheet
Galvanized
aluminum sheet
Fin guard
Steel wires
Fan guard & Drum
Plastic
Fan
Plastic
Motor
Frame; Spcc
Shaft; S35C
Motor support
Galvanized sheet
Heat exchanger
Aluminum plate
(Only fin)
Electrical parts box
Galvanized sheet
Galvanized
aluminum sheet
Printed circuit board Epoxy resin
Screw
Steel for screws
CAUTION:
1 Do not position the outdoor in a direct sea breeze.
2 Don't protect the unit from rain. (Rain will clean the salt from the coil).
3 Install the outdoor unit level to allow condensate drainage.
PUHY, PURY
YNW
YNW-BS
Salt
Standard
damage
protection
Polyester resin coating
Polyester resin coating
Polyester resin coating
Polyester resin coating
Polyester resin coating
No treatment
Polyester resin coating
Polyethylene resin
(Weather proof)
Polypropylene resin
(Weather proof)
Acrylics nitril styrene resin
Zinc plating filming
Rust prevention coloured
coating
No treatment
Polyester resin coating
Cellulose series and ure-
thane series resin coating
Cellulose series and ure-
thane series resin coating
No treatment
Polyester resin coating
Polyurethane coating
Polyurethane coating
Zinc-nickel alloy plating +
Geomet filming
Surface treatment
70μm or more
15μm or more
85μm or more
30μm or more
70μm or more
70μm or more
300μm or more
8μm or more
70μm or more
1μm or more
3μm or more
70μm or more
10μm or more
10μm or more
4 Wash the outdoor unit regularly.
5 Repair any scratches on the panels.
6 Inspect regularly. Paint or change parts as required.
Paint thickness
External
Internal
70μm or more
5μm or more
75μm or more
70μm or more
70μm or more
300μm or more
70μm or more
10μm or more