Specifications
Model
Power Source
Capacity *1
Power input
Current input
COP (kW / kW)
Capacity *2
Power input
Current input
COP (kW / kW)
Seasonal space heating energy efficiency class for medium-temperature application
Seasonal space heating energy efficiency class for low-temperature application
Maximum current input *3
Water pressure drop *1
Temp range
Outlet water temp *4
Outdoor temp *4
Circulating water volume range
Sound Pressure level (measured in anechoic room) *1
Sound Pressure level (measured in anechoic room) *3
Diameter of water pipe
Inlet
Outlet
External finish
External dimension H × W × D
Net weight
Accessories
Design Pressure
R407C
Water
Drawing
Wiring
External
Heat exchanger
Water side
Air side
Type
Compressor
Maker
Starting method
Motor output
Case heater
Lubricant
FAN
Air flow rate
External static press *5
Type × Quantity
Control, Driving mechanism
Motor output
HIC circuit (HIC:Heat inter-Changer)
High pressure protection
Protection
Inverter circuit
Compressor
Fan motor
Defrosting method
Control
Type
GWP *6
Weight
Original charged
CO
*1 Under Normal heating conditions at
outdoor temp, 7ºC DB/6ºC WB(44.6°F
DB/42.8°F WB) outlet water temp
45ºC(113°F), inlet water temp
40ºC(104°F)
*2 Under Heating conditions at outdoor temp,
7ºC DB/6ºC WB(44.6°F DB/42.8°F WB),
outlet water temp 70ºC (158°F)
*3 Under Heating conditions at outdoor temp,
7ºC DB/6ºC WB(44.6°F DB/42.8°F WB)
when this unit is set to capacity priority
mode by non-voltage B contact
kW
kcal/h
BTU/h
kW
A
kW
kcal/h
BTU/h
kW
A
A
D.B
dB (A)
dB (A)
mm (in.)
mm (in.)
mm
in.
kg (lbs)
MPa
MPa
kW
kW
m³/min
L/s
cfm
kW
equivalent
2
*4
outdoor temp (°F DB)
-22
-2
18
38
58
78
98
118
80
172
70
152
60
132
50
112
40
92
30
72
20
52
10
0
32
-30 -20 -10
0
10
20
30
40
50
outdoor temp (°C DB)
Outdoor temp -20°C DB/ Outlet water temp 40~65°C
(Outdoor temp -4°F DB/ Outlet water temp 104°F~149°F)
Outdoor temp -10°C DB/ Outlet water temp 33°C~70°C
(Outdoor temp 14°F DB/ Outlet water temp 91°F~158°F)
Outdoor temp 0°C DB/ Outlet water temp 25°C~70°C
(Outdoor temp 32°F DB/ Outlet water temp 77°F~158°F)
CAHV-P500YB-HPB
3-phase 4-wire 380-400-415V 50/60Hz
38,700
153,540
21.78 - 20.69 - 19.94
38,700
153,540
43.17 - 41.01 - 39.53
57.77 - 54.88 - 52.90
12.9kPa (1.87psi)
25~70°C
77~158°F
-20~40°C
-4~104°F
7.5 m³/h-15.0m³/h
38.1 (Rc 1 1/2") screw
38.1 (Rc 1 1/2") screw
Acrylic painted steel plate <MUNSELL 5Y 8/1 or similar>
1,710 (without legs 1,650) × 1,978 × 759
67.3 (without legs 65.0) × 77.9 × 29.9
511 (1127)
Y strainer Rc 1 1/2
KC94R746
KC94R745
stainless steal plate and copper brazing
Plate fin and copper tube
Inverter scroll hermetic compressor
MITSUBISHI ELECTRIC CORPORATION
Inverter
7.5 × 2
0.045 × 2
MEL32
185 × 2
3,083 × 2
6,532 × 2
0Pa, 60Pa (0mmH ² O/6.1mmH ² O)
Propeller fan × 2
Inverter-control, Direct-driven by motor
0.46 × 2
Copper pipe
High pres.Sensor & High pres.Switch at 3.85MPa (643psi)
Over-heat protection, Over current protection
Over-heat protection
Thermal switch
Auto-defrost mode (Reversed refrigerant circle)
LEV and HIC circuit
R407C
1,774
161.3
*5 Dip SW on the unit control board need to be changed.
*6 This table is based on Regulation(EU) No517/2014
* Due to continuing improvement, the above specifications may be subject to change without notice.
* Please don't use the steel material for the water piping material.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use groundwater and well water.
* Install the unit in an environment where the wet bulb temp will not exceed 32ºC (89.6°F).
* The water circuit must use the closed circuit.
<External input/output from the unit>
Unit converter
*The unit can be operated and the operation
kcal/h =kW × 860
status can be monitored with
BTU/h =kW × 3,412
external input/output terminals.
cfm =m³/min × 35.31
lbs =kg/0.4536
SPECIFICATIONS
45
12.9
3.49
45
25.6
1.76
A++
A+
59
63
3.85
1.0
11.0
233

Advertisement

loading

This manual is also suitable for: